26<br />

Comparison of FSAR and BWR-LACP calcul<strong>at</strong>ions of drywell temper<strong>at</strong>ure<br />

was performed for the "Loss of All AC Power" results shown on Fig.<br />

Q.14.2-1 of the BFNP FSAR. Plant conditions assumed by the FSAR calcula<br />

tions include:<br />

1. Initial power = 100%.<br />

2. Loss of all AC power <strong>at</strong> time = 0.<br />

3. Drywell perfectly insul<strong>at</strong>ed on outside.<br />

4. He<strong>at</strong> capacity of interior equipment and structures is negligible.<br />

5. Energy input from primary surfaces is initially 2000 kW.<br />

6. He<strong>at</strong> transfer coefficient between <strong>at</strong>mosphere and wall is 11.36<br />

w/m**2°C (2 Btu/h ft2 °F) without steam condens<strong>at</strong>ion.<br />

7. Drywell coolers lost <strong>at</strong> time = 0 and not restarted.<br />

8. Steam leak = 0<br />

The conditions assumed for this analysis are of the same order as those<br />

assumed for the "Normal Recovery" part of the <strong>St<strong>at</strong>ion</strong> Blackout as dis<br />

cussed in this report. Comparisons of various predictions of drywell<br />

<strong>at</strong>mosphere temper<strong>at</strong>ure to the FSAR result are shown on Fig. 4.4. The drywell<br />

temper<strong>at</strong>ure climbs rapidly during the first 5 to 10 min, before he<strong>at</strong><br />