<strong>St<strong>at</strong>ion</strong> Blackout <strong>at</strong> <strong>Browns</strong><br />

<strong>Ferry</strong> <strong>Unit</strong> <strong>One</strong>—Accident<br />

Sequence Analysis<br />

D. H. Cook S. R. Greene<br />

R. M. Harrington S. A. Hodge<br />

D. D. Yue<br />

OAK RIDGE NATIONAL LABORATORY<br />

CENTRAL RESEARCH LIBRARY<br />

CIRCULATION SECTION<br />

4500N ROOM 175<br />

LIBRARY LOAN COP<br />

DO NOT TRANSFER TO ANOTHER PERSON<br />

If you wish someone else to see this<br />

report, send in name with report and<br />

the library will arrange a loan.<br />

Prepared for the U.S. Nuclear Regul<strong>at</strong>ory Commission<br />

Office of Nuclear Regul<strong>at</strong>ory Research<br />

Under Interagency Agreements DOE 40-551-75 and 40-552-75


Printed in the <strong>Unit</strong>ed St<strong>at</strong>es of America. Available from<br />

N<strong>at</strong>ional Technical Inform<strong>at</strong>ion Service<br />

U.S. Department of Commerce<br />

5285 Port Royal Road, Springfield, Virginia 22161<br />

Available from<br />

GPO Sales Program<br />

Division of Technical Inform<strong>at</strong>ion and Document Control<br />

U.S. Nuclear Regul<strong>at</strong>ory Commission<br />

Washington, D.C. 20555<br />

This report was prepared as an account of work sponsored by an agency of the<br />

<strong>Unit</strong>edSt<strong>at</strong>es Government. Neitherthe<strong>Unit</strong>edSt<strong>at</strong>esGovemment noranyagency<br />

thereof, nor any of their employees, makes any warranty,express or implied,or<br />

assumes any legal liability or resoonsibility for the accuracy, completeness, or<br />

usefulness of any inform<strong>at</strong>ion, appar<strong>at</strong>us, product, or process disclosed, or<br />

represents th<strong>at</strong> its use would not infringe priv<strong>at</strong>ely owned rights. Reference herein<br />

to any specific commercial product, process, or service by trade name, trademark,<br />

manufacturer, or otherwise, does not necessarily constitute or imply its<br />

endorsement, recommend<strong>at</strong>ion, or favoring by the <strong>Unit</strong>ed St<strong>at</strong>es Government or<br />

any agency thereof. The views and opinions of authors expressed herein do not<br />

necessarily st<strong>at</strong>e or reflect those of the <strong>Unit</strong>ed St<strong>at</strong>es Government or any agency<br />

thereof.


Contract No. W-7405-eng-26<br />

Engineering Technology Division<br />

STATION BLACKOUT AT BROWNS FERRY UNIT ONE<br />

ACCIDENT SEQUENCE ANALYSIS<br />

D. H. Cook S. R. Greene<br />

R. M. Harrington S. A. Hodge<br />

D. D. Yue<br />

Manuscript Completed — October 6, 1981<br />

D<strong>at</strong>e Published — November 1981<br />

NUREG/CR-2182, Vol. I<br />

ORNL/NUREG/TM-455/VI<br />

Dist. C<strong>at</strong>egory RX, IS<br />

Notice: This document contains inform<strong>at</strong>ion of a preliminary<br />

n<strong>at</strong>ure. It is subject to revision or correction and therefore<br />

does not represent a final report.<br />

Prepared for the<br />

U. S. Nuclear Regul<strong>at</strong>ory Commission<br />

Office of Nuclear Regul<strong>at</strong>ory Research<br />

Under Interagency Agreements DOE 40-551-75 and 40-552-75<br />

NRC FIN No. B0452<br />

Prepared by the<br />

OAK RIDGE NATIONAL LABORATORY<br />

<strong>Oak</strong> <strong>Ridge</strong>, Tennessee 37830<br />

oper<strong>at</strong>ed by<br />

UNION CARBIDE CORPORATION<br />

for the<br />

DEPARTMENT OF ENERGY<br />

OAK RIDGE NATIONAL LABORATORY LIBRARY<br />

3 445b DDEllfifl 4


XXI<br />

CONTENTS<br />

SUMMARY v<br />

ABSTRACT 1<br />

1. INTRODUCTION 1<br />

2. DESCRIPTION OF STATION BLACKOUT 5<br />

3. NORMAL RECOVERY 7<br />

4. COMPUTER MODEL FOR SYSTEM BEHAVIOR PRIOR TO LOSS OF<br />

INJECTION CAPABILITY 17<br />

5. INSTRUMENTATION AVAILABLE DURING STATION BLACKOUT AND<br />

NORMAL RECOVERY 30<br />

6. OPERATOR ACTIONS DURING STATION BLACKOUT AND NORMAL<br />

RECOVERY 33<br />

7. COMPUTER PREDICTION OF THERMAL-HYDRAULIC PARAMETERS FOR<br />

NORMAL RECOVERY 36<br />

7.1 Introduction 36<br />

7.2 Conclusions 36<br />

7.2.1 Normal recovery — conclusions 36<br />

7.2.2 Loss of 250 vdc — conclusions 37<br />

7.3 Normal Recovery 37<br />

7.3.1 Normal recovery — assumptions 37<br />

7.3.2 Normal recovery — results 38<br />

7.4 Loss of 250 vdc B<strong>at</strong>teries 50<br />

7.4.1 Loss of 250 vdc b<strong>at</strong>teries —assumptions 50<br />

7.4.2 Loss of 250 vdc b<strong>at</strong>teries — results 50<br />

8. FAILURES LEADING TO A SEVERE ACCIDENT 59<br />

8.1 Induced Failure of the HPCI and RCIC Systems 62<br />

8.2 Stuck-Open Relief Valve 65<br />

8.3 Loss of 250-Volt DC Power 68<br />

9. ACCIDENT SEQUENCES RESULTING IN CORE MELTDOWN 71<br />

9.1 Introduction 71<br />

9.2 Accident Phenomenology 71<br />

9.2.1 Accident progression resulting in core<br />

melt 71<br />

9.2.2 Containment failure modes 72<br />

9.3 Event Trees 74<br />

9.3.1 Event trees for accident sequences resulting<br />

in core melt 74<br />

9.3.2 Core damage event tree 74<br />

9.3.3 Containment event tree 74<br />

9.4 Accident Sequences 78<br />

9.4.1 MARCH computer code 78<br />

9.4.2 Accident progression sign<strong>at</strong>ures 78<br />

9.5 Containment Responses 123<br />

9.5.1 Drywell responses 123<br />

9.5.2 Wetwe 11 responses 149<br />

10. PLANT STATE RECOGNITION AND OPERATOR MITIGATING<br />

ACTION 161<br />

10.1 Introduction 161<br />

10.2 Plant St<strong>at</strong>e Recognition 161<br />

Page


10.3 Oper<strong>at</strong>or Key Action Event Tree<br />

10.4 Oper<strong>at</strong>or Mitig<strong>at</strong>ing Actions<br />

11. INSTRUMENTATION AVAILABLE FOLLOWING LOSS OF 250 VOLT<br />

DC POWER<br />

12. IMPLICATIONS OF RESULTS<br />

12.1 Instrument<strong>at</strong>ion<br />

12.2 Oper<strong>at</strong>or Preparedness<br />

12.3 System Design<br />

13. REFERENCES<br />

ACKNOWLEDGEMENT<br />

APPENDIX A. Computer Code used for Normal Recovery<br />

XV<br />

APPENDIX B. Modific<strong>at</strong>ions to the March Code<br />

APPENDIX C. March Code Input (TB')<br />

APPENDIX D. Pressure Suppression Pool Model<br />

D.l Introduction<br />

D.2 Purpose and Scope<br />

D.3 Description of the System<br />

D.4 Identific<strong>at</strong>ion of the Phenomena<br />

D.5 Pool Modeling Consider<strong>at</strong>ions<br />

APPENDIX E. A Compendium of Inform<strong>at</strong>ion Concerning the<br />

<strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 High-Pressure Cooling<br />

Injection System<br />

E.l Purpose<br />

E.2 System Description<br />

E.3 HPCI Pump Suction<br />

E.4 System Initi<strong>at</strong>ion<br />

E.5 Turbine Trips<br />

E.6 System Isol<strong>at</strong>ion<br />

E.7 Technical Specific<strong>at</strong>ions<br />

APPENDIX F. A Compendium of Inform<strong>at</strong>ion Concerning the<br />

<strong>Unit</strong> 1 Reactor Core Isol<strong>at</strong>ion Cooling System<br />

F.l Purpose<br />

F.2 System Description<br />

F.3 RCIC Pump Suction<br />

F.4 System Initi<strong>at</strong>ion<br />

F.5 Turbine Trips<br />

F.6 System Isol<strong>at</strong>ion<br />

F.7 Technical Specific<strong>at</strong>ions<br />

APPENDIX G. Effect of TVA-Estim<strong>at</strong>ed Seven Hour B<strong>at</strong>tery<br />

Life on Normal Recovery Calcul<strong>at</strong>ions<br />

Page<br />

163<br />

163<br />

165<br />

167<br />

167<br />

170<br />

172<br />

173<br />

177<br />

179<br />

197<br />

199<br />

205<br />

205<br />

205<br />

206<br />

207<br />

211<br />

217<br />

217<br />

217<br />

219<br />

220<br />

221<br />

221<br />

222<br />

223<br />

223<br />

223<br />

225<br />

225<br />

226<br />

227<br />

228<br />

229


SUMMARY<br />

This study describes the predicted response of <strong>Unit</strong> 1 <strong>at</strong> the <strong>Browns</strong><br />

<strong>Ferry</strong> Nuclear Plant to a hypothetical <strong>St<strong>at</strong>ion</strong> Blackout. This accident<br />

would be initi<strong>at</strong>ed by a loss of offsite power concurrent with a failure of<br />

all eight of the onsite diesel-gener<strong>at</strong>ors to start and load; the only re<br />

maining electrical power <strong>at</strong> this three-unit plant would be th<strong>at</strong> derived<br />

from the st<strong>at</strong>ion b<strong>at</strong>teries. It is assumed th<strong>at</strong> the <strong>St<strong>at</strong>ion</strong> Blackout occurs<br />

<strong>at</strong> a time when each of the <strong>Browns</strong> <strong>Ferry</strong> units is oper<strong>at</strong>ing <strong>at</strong> 100% power<br />

so th<strong>at</strong> there is no opportunity for use of the b<strong>at</strong>teries for units 2 or 3<br />

in support of unit 1.<br />

The design basis for the 250 volt DC b<strong>at</strong>tery system <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong><br />

provides th<strong>at</strong> any two of the three unit b<strong>at</strong>teries can supply the electri<br />

cal power necessary for shutdown and cooldown of all three units for a<br />

period of 30 minutes with a design basis accident <strong>at</strong> any one of the units.<br />

It is further provided th<strong>at</strong> the system voltage <strong>at</strong> the end of the 30 minute<br />

period will not be less than 210 volts, and th<strong>at</strong> all DC equipment supplied<br />

by this system must be operable <strong>at</strong> potentials as low as 200 volts.<br />

It is clear th<strong>at</strong> the 250 volt system was not designed for the case of<br />

a prolonged <strong>St<strong>at</strong>ion</strong> Blackout, and the period of time during which the DC<br />

equipment powered by this system could remain oper<strong>at</strong>ional under these con<br />

ditions can only be estim<strong>at</strong>ed. It would certainly be significantly longer<br />

than 30 minutes since all three b<strong>at</strong>teries would be available, the equip<br />

ment is certified to be operable <strong>at</strong> 200 volts, and there would be no de<br />

sign basis accident. In response to AEC inquiry in 1971, during the pe<br />

riod of plant construction, TVA estim<strong>at</strong>ed th<strong>at</strong> the steam-driven High Pres<br />

sure Coolant Injection (HPCI) and Reactor Core Isol<strong>at</strong>ion Cooling (RCIC)<br />

systems, which use DC power for turbine control and valve oper<strong>at</strong>ion, could<br />

remain oper<strong>at</strong>ional for a period of four to six hours. A period of four<br />

hours has been assumed for this study.*<br />

Within 30 seconds following the inception of a <strong>St<strong>at</strong>ion</strong> Blackout, the<br />

reactor would have scrammed and the reactor vessel would be isol<strong>at</strong>ed be<br />

hind the closed main steam isol<strong>at</strong>ion valves (MSIV's). The initial phase<br />

of the <strong>St<strong>at</strong>ion</strong> Blackout extends from the time of reactor vessel isol<strong>at</strong>ion<br />

until the time <strong>at</strong> which the 250 volt DC system fails due to b<strong>at</strong>tery ex<br />

haustion. During this period, the oper<strong>at</strong>or would maintain reactor vessel<br />

w<strong>at</strong>er level in the normal oper<strong>at</strong>ing range by intermittent oper<strong>at</strong>ion of the<br />

RCIC system, with the HPCI system available as a backup. Each of these<br />

w<strong>at</strong>er-injection systems is normally aligned to pump w<strong>at</strong>er from the conden<br />

s<strong>at</strong>e storage tank into the reactor vessel via a feedw<strong>at</strong>er line.<br />

*It should be noted th<strong>at</strong> the events subsequent to failure of the 250<br />

volt DC system are rel<strong>at</strong>ively insensitive to the time <strong>at</strong> which this fail<br />

ure occurs. This is because the only parameter affecting the subsequent<br />

events which is dependent upon the time of failure is the slowly-varying<br />

decay he<strong>at</strong>.<br />

As part of a requested review of the results of this study, TVA per<br />

formed a b<strong>at</strong>tery capacity calcul<strong>at</strong>ion which shows th<strong>at</strong> the unit b<strong>at</strong>teries<br />

can be expected to last as long as seven hours under <strong>blackout</strong> conditions.<br />

In Appendix G, the effect of a b<strong>at</strong>tery lifetime of seven vice four hours<br />

upon study results is shown to be limited to timing.


vx<br />

The oper<strong>at</strong>or would also take action during the initial phase to con<br />

trol reactor vessel pressure by means of remote-manual oper<strong>at</strong>ion of the<br />

primary relief valves; sufficient stored control air would remain avail<br />

able to permit the desired remote-manual valve oper<strong>at</strong>ions for well over<br />

four hours. The Control Room instrument<strong>at</strong>ion necessary to monitor reactor<br />

vessel level and pressure and for oper<strong>at</strong>ion of the RCIC and HPCI systems<br />

would also remain available during this period.<br />

There is no Emergency Oper<strong>at</strong>ing Instruction for a <strong>St<strong>at</strong>ion</strong> Blackout <strong>at</strong><br />

<strong>Browns</strong> <strong>Ferry</strong>. However, the existing written procedure for oper<strong>at</strong>or action<br />

following reactor isol<strong>at</strong>ion behind closed MSIV's provides for the reactor<br />

vessel level control and pressure control described above. The primary<br />

relief valves would actu<strong>at</strong>e autom<strong>at</strong>ically to prevent vessel over pressuriz<strong>at</strong>ion<br />

if the oper<strong>at</strong>or did not act; the purpose of pressure control by<br />

remote-manual oper<strong>at</strong>ion is to reduce the total number of valve actu<strong>at</strong>ions<br />

by means of an increased pressure reduction per valve oper<strong>at</strong>ion and to<br />

permit the steam entering the pressure suppression pool to be passed by<br />

different relief valves in succession. This provides a more even spacial<br />

distribution of the transferred energy around the circumference of the<br />

pressure suppression pool.<br />

The initial phase of a <strong>St<strong>at</strong>ion</strong> Blackout has been analyzed in this<br />

study by use of a rel<strong>at</strong>ively simple computer code developed specifically<br />

for this purpose. This coding uses the Continuous Systems Modeling Pro<br />

gram (CSMP) language of the IBM computer system to simul<strong>at</strong>e the response<br />

of <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 to postul<strong>at</strong>ed oper<strong>at</strong>or actions. The analysis<br />

shows, because of the loss of the drywell coolers, th<strong>at</strong> it is necessary<br />

for the oper<strong>at</strong>or to begin to reduce the reactor vessel pressure to about<br />

0.791 MPa (100 psig) within one hour of the inception of the <strong>St<strong>at</strong>ion</strong><br />

Blackout. This depressuriz<strong>at</strong>ion reduces the temper<strong>at</strong>ure of the s<strong>at</strong>ur<strong>at</strong>ed<br />

fluid within the reactor vessel and thereby decreases the driving poten<br />

tial for he<strong>at</strong> transfer into the drywell, yet keeps the vessel pressure<br />

high enough for continued oper<strong>at</strong>ion of the RCIC system steam turbine.<br />

With this action, the drywell average ambient temper<strong>at</strong>ure can be kept be<br />

low 149°C (300°F) throughout the initial phase of a <strong>St<strong>at</strong>ion</strong> Blackout;<br />

tests have shown th<strong>at</strong> both the drywell structure and the equipment loc<strong>at</strong>ed<br />

therein can be expected to survive temper<strong>at</strong>ures of this magnitude.<br />

The analysis also reveals an important second reason for oper<strong>at</strong>or ac<br />

tion to depressurize the reactor vesel early in the initial phase of a<br />

<strong>St<strong>at</strong>ion</strong> Blackout. This depressuriz<strong>at</strong>ion removes a gre<strong>at</strong> deal of steam and<br />

the associ<strong>at</strong>ed stored energy from the reactor vessel <strong>at</strong> a time when the<br />

RCIC system is available to inject replacement w<strong>at</strong>er from the condens<strong>at</strong>e<br />

storage tank and thereby maintain the reactor vessel level. Subsequently,<br />

when w<strong>at</strong>er injection capability is lost for any reason, remote-manual re<br />

lief valve oper<strong>at</strong>ion would be termin<strong>at</strong>ed and there would be no further<br />

w<strong>at</strong>er loss from the reactor vessel until the pressure has been restored to<br />

the setpoint [7.72 MPa (1105 psig)] for autom<strong>at</strong>ic relief valve actu<strong>at</strong>ion.<br />

Because of the large amount of w<strong>at</strong>er to be rehe<strong>at</strong>ed and the reduced level<br />

of decay he<strong>at</strong>, this repressuriz<strong>at</strong>ion would require a significant period of<br />

time. In addition, the subsequent boiloff* would begin from a very high<br />

*The term "boiloff" is used to signify a monotonic decrease in re<br />

actor vessel w<strong>at</strong>er level due to intermittent loss of fluid through the<br />

primary relief valves without replacement.


vxx<br />

vessel level because of the increase in the specific volume of the w<strong>at</strong>er<br />

as it is he<strong>at</strong>ed and repressurized. Thus, an early depressuriz<strong>at</strong>ion will<br />

provide a significant period of valuable additional time for prepar<strong>at</strong>ive<br />

and possible corrective action before core uncovery after injection capa<br />

bility is lost.<br />

<strong>One</strong> design fe<strong>at</strong>ure of the HPCI system logic was brought into question<br />

by the analysis. The existing logic provides for the suction of the HPCI<br />

system pump to be autom<strong>at</strong>ically shifted from the condens<strong>at</strong>e storage tank<br />

to the pressure suppression pool upon high sensed suppression pool level.<br />

During a <strong>St<strong>at</strong>ion</strong> Blackout, this would occur after about three hours when<br />

the average suppression pool temper<strong>at</strong>ure has reached about 71°C (160°F).*<br />

Since the lubric<strong>at</strong>ing oil for the HPCI turbine Is cooled by the w<strong>at</strong>er be<br />

ing pumped, this would thre<strong>at</strong>en the viability of the HPCI system.<br />

The r<strong>at</strong>ionale for the autom<strong>at</strong>ic shift in HPCI pump suction on high<br />

sensed pool level is not explained in the liter<strong>at</strong>ure available to this<br />

study. There is no corresponding provision for a shift of the RCIC pump<br />

suction on high pool level, and a separ<strong>at</strong>e logic is provided for an auto<br />

m<strong>at</strong>ic shift of the HPCI pump suction should the supply of w<strong>at</strong>er from the<br />

condens<strong>at</strong>e storage tank become exhausted. For these reasons, it is recom<br />

mended th<strong>at</strong> the desirabilty of the autom<strong>at</strong>ic shift of HPCI pump suction on<br />

high sensed suppression pool level be reexamined.<br />

The plant response during the initial phase of a <strong>St<strong>at</strong>ion</strong> Blackout can<br />

be summarized as an open cycle. W<strong>at</strong>er would be pumped from the condens<strong>at</strong>e<br />

storage tank into the reactor vessel by the RCIC system as necessary to<br />

maintain level in the normal oper<strong>at</strong>ing range. The injected w<strong>at</strong>er would be<br />

he<strong>at</strong>ed by the reactor decay he<strong>at</strong> and subsequently passed to the pressure<br />

suppression pool as steam when the oper<strong>at</strong>or remote-manually opens the re<br />

lief valves as necessary to maintain the desired reactor vessel pressure.<br />

Stable reactor vessel level and pressure control is maintained during this<br />

period, but the condens<strong>at</strong>e storage tank is being depleted and both the<br />

level and temper<strong>at</strong>ure of the pressure suppression pool are increasing.<br />

However, without question, the limiting factor for continued removal of<br />

decay he<strong>at</strong> and the prevention of core uncovery is the available of DC<br />

power.<br />

The sequence of events used for the fission product release analysis<br />

for a prolonged <strong>St<strong>at</strong>ion</strong> Blackout was established by this study under the<br />

assumption th<strong>at</strong> no independent secondary equipment failures would occur.<br />

Dependent secondary failures, i.e., those caused by the conditions of a<br />

<strong>St<strong>at</strong>ion</strong> Blackout, were included in the development of the sequence, but<br />

with the assumption th<strong>at</strong> the oper<strong>at</strong>or does take action to depressurize the<br />

reactor vessel and thereby prevent drywell temper<strong>at</strong>ures of the magnitude<br />

th<strong>at</strong> could severely damage the equipment therein. The point is important<br />

because the oper<strong>at</strong>or would probably be reluctant to depressurize; current<br />

training stresses concern for high suppression pool temper<strong>at</strong>ures (based on<br />

LOCA consider<strong>at</strong>ionst) and the oper<strong>at</strong>or would recognize th<strong>at</strong> suppression<br />

pool cooling is not available during a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

*It is expected th<strong>at</strong> any accident sequence resulting in high sup<br />

pression pool level would also produce an associ<strong>at</strong>ed high pool tempera<br />

ture.<br />

Blackout.<br />

tThere is currently no written procedure for the case of <strong>St<strong>at</strong>ion</strong>


viii<br />

This study has established th<strong>at</strong> the possible dependent secondary<br />

failure of a stuck-open relief valve would not reduce the reactor vessel<br />

pressure below th<strong>at</strong> necessary for oper<strong>at</strong>ion of the RCIC steam turbine dur<br />

ing the period in which DC power would remain available. However, during<br />

this period all of the energy transferred to the pressure suppression pool<br />

would pass through the tailpipe of this one relief valve and would be con<br />

centr<strong>at</strong>ed near its terminus. This would reduce the steam-quenching capac<br />

ity of the pool to th<strong>at</strong> provided by the effective volume of w<strong>at</strong>er sur<br />

rounding this one tailpipe. Local boiling in this area would pass most of<br />

the relief valve discharge directly to the pool surface and could result<br />

in early containment failure by overpressuriz<strong>at</strong>ion.<br />

The question of suppression pool effectiveness in quenching relief<br />

valve steam discharge in cases which involve highly localized energy<br />

transfer from the reactor vessel is important to a complete analysis of<br />

any severe accident in which the pressure suppression pool is used as a<br />

he<strong>at</strong> sink. This question has not been resolved, <strong>at</strong> least in the non-pro<br />

prietary liter<strong>at</strong>ure, and has been recently adopted as a dissert<strong>at</strong>ion topic<br />

for a University of Tennessee doctorial candid<strong>at</strong>e working with the Severe<br />

Accident Sequence Analysis (SASA) project. Pending the results of this<br />

work, pool-averaged temper<strong>at</strong>ures are used in this study.<br />

The MARCH code has been used in support of the analysis of the second<br />

phase of a <strong>St<strong>at</strong>ion</strong> Blackout, i.e., the period after the 250 volt DC system<br />

fails because of b<strong>at</strong>tery exhaustion. The existing versions of MARCH are<br />

too crude to permit modeling plant response to a series of postul<strong>at</strong>ed op<br />

er<strong>at</strong>or actions such as those previously discussed for the initial phase of<br />

a <strong>St<strong>at</strong>ion</strong> Blackout. Therefore, in the event sequence modeled by the MARCH<br />

code, the reactor vessel remains pressurized with pressure control by<br />

autom<strong>at</strong>ic relief valve actu<strong>at</strong>ion and level control by autom<strong>at</strong>ic oper<strong>at</strong>ion<br />

of the HPCI system. As before, averaged suppression pool temper<strong>at</strong>ures are<br />

used, and it is assumed th<strong>at</strong> injection capability is lost after four<br />

hours, when the unit b<strong>at</strong>tery is exhausted.<br />

In the MARCH event sequence, the reactor vessel w<strong>at</strong>er level is in the<br />

normal oper<strong>at</strong>ing range and the vessel is pressurized <strong>at</strong> the four-hour<br />

point when boiloff begins due to loss of injection capability.* The MARCH<br />

results predict core uncovery 62 minutes after the beginning of boiloff,<br />

followed by the inception of core melting 53 minutes l<strong>at</strong>er. The model<br />

provides th<strong>at</strong> the melted core slumps down to the bottom of the reactor<br />

vessel and this results in a predicted failure of the reactor vessel bot<br />

tom head <strong>at</strong> approxim<strong>at</strong>ely three hours after injection capability is lost.<br />

The subsequent breaching of the primary containment because of failure of<br />

the electrical penetr<strong>at</strong>ion modules by overtemper<strong>at</strong>ure is predicted <strong>at</strong><br />

about four and one-half hours after the inception of boiloff. The detailed<br />

*These conditions <strong>at</strong> the beginning of boiloff are similar to those<br />

predicted by the previously discussed sequence which models the plant re<br />

sponse to oper<strong>at</strong>or actions during the initial phase because in th<strong>at</strong> sequ<br />

ence, the reactor vessel would have to repressurize before boiloff could<br />

begin. The difference is in the timing. If injection capability were<br />

lost <strong>at</strong> the four-hour point, the boiloff would begin immedi<strong>at</strong>ely if the<br />

vessel is pressurized, but would be delayed if the vessel were depressur-<br />

ized.


ix<br />

thermo-hydraulic parameters needed for the analysis of fission product re<br />

lease from the fuel rods and the subsequent transport of fission products<br />

to the environment were taken from the MARCH results for this sequence.<br />

An estim<strong>at</strong>e of the magnitude and timing of the release of the noble<br />

gas, cesium, and iodine-based fission products to the environment is pro<br />

vided in Volume 2 of this study. Under the conditions of a <strong>St<strong>at</strong>ion</strong> Black<br />

out, fuel rod cladding failure would occur while the reactor vessel was<br />

pressurized. The distribution of both solid and gaseous fission products<br />

within the <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 core <strong>at</strong> the present time has been obtained<br />

through use of the 0RIGEN2 code; the results show th<strong>at</strong> internal gas pres<br />

sure under <strong>St<strong>at</strong>ion</strong> Blackout conditions could not increase to the magni<br />

tude necessary to cause cladding failure by rod burst. Accordingly, the<br />

cladding has been assumed to fail <strong>at</strong> a temper<strong>at</strong>ure of 1300°C.


STATION BLACKOUT AT BROWNS FERRY UNIT ONE -<br />

ACCIDENT SEQUENCE ANALYSIS<br />

D. H. Cook S. R. Greene<br />

R. M. Harrington S. A. Hodge<br />

D. D. Yue<br />

ABSTRACT<br />

This study describes the predicted response of <strong>Unit</strong> 1 <strong>at</strong><br />

the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant to <strong>St<strong>at</strong>ion</strong> Blackout, defined as<br />

a loss of offsite power combined with failure of all onsite<br />

emergency diesel-gener<strong>at</strong>ors to start and load. Every effort<br />

has been made to employ the most realistic assumptions during<br />

the process of defining the sequence of events for this hypo<br />

thetical accident. DC power is assumed to remain available<br />

from the unit b<strong>at</strong>teries during the initial phase and the oper<br />

<strong>at</strong>or actions and corresponding events during this period are<br />

described using results provided by an analysis code developed<br />

specifically for this purpose. The <strong>St<strong>at</strong>ion</strong> Blackout is as<br />

sumed to persist beyond the point of b<strong>at</strong>tery exhaustion and<br />

the events during this second phase of the accident in which<br />

DC power would be unavailable were determined through use of<br />

the MARCH code. Without DC power, cooling w<strong>at</strong>er could no<br />

longer be injected into the reactor vessel and the events of<br />

the second phase include core meltdown and subsequent contain<br />

ment failure. An estim<strong>at</strong>e of the magnitude and timing of the<br />

concomitant release of the noble gas, cesium, and iodine-based<br />

fission products to the environment is provided in Volume 2 of<br />

this report.<br />

1. INTRODUCTION<br />

The Tennessee Valley Authority (TVA) oper<strong>at</strong>es three nearly identical<br />

reactor units <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant loc<strong>at</strong>ed on the Tennessee<br />

River approxim<strong>at</strong>ely midway between Athens and Dec<strong>at</strong>ur, Alabama. The Gen<br />

eral Electric Company and the Tennessee Valley Authority jointly partici<br />

p<strong>at</strong>ed in the design; TVA performed the construction of each unit. <strong>Unit</strong> 1<br />

began commercial oper<strong>at</strong>ion in August 1974, <strong>Unit</strong> 2 in March 1975, and <strong>Unit</strong><br />

3 in March 1977.<br />

Each unit comprises a boiling w<strong>at</strong>er reactor steam supply system fur<br />

nished by the General Electric Company. Each reactor is designed for a<br />

power output of 3440 MWt, for a corresponding gener<strong>at</strong>ed 1152 MWe; the<br />

maximum power authorized by the oper<strong>at</strong>ing license is 3293 MWt, or 1067<br />

net MWe. The primary containments are of the Mark I pressure suppres<br />

sion pool type; the drywells are light bulb shape and both torus and drywell<br />

are of steel vessel construction. The three units share a reactor


uilding-secondary containment of the controlled leakage, elev<strong>at</strong>ed release<br />

type.<br />

Safety systems for each unit include a Reactor Protection System, a<br />

Standby Liquid Control System for Poison injection, and the Emergency Core<br />

Cooling Systems: High-Pressure Coolant Injection (HPCI), Autom<strong>at</strong>ic De<br />

pressuriz<strong>at</strong>ion (ADS), Residual He<strong>at</strong> Removal (RHR), and Core Spray (CS).<br />

The Reactor Core Isol<strong>at</strong>ion Cooling (RCIC) system is also provided for the<br />

removal of post-shutdown reactor decay he<strong>at</strong> as a consequence limiting sys<br />

tem.<br />

Several components and systems are shared by the three <strong>Browns</strong> <strong>Ferry</strong><br />

units. A complete description of these shared fe<strong>at</strong>ures is given in the<br />

Final Safety Analysis Report;! the shared Safeguards systems and their<br />

supporting auxiliary equipment are listed in Table 1.1. With the assumption<br />

th<strong>at</strong> the interfaces with the other two units do not interfere with the op<br />

er<strong>at</strong>ion of any shared system as applied to the needs of the unit under<br />

study, the existence of the shared systems does not significantly compli<br />

c<strong>at</strong>e the analysis of an accident sequence <strong>at</strong> any one unit.<br />

The results of a study of the consequences <strong>at</strong> <strong>Unit</strong> 1 of a <strong>St<strong>at</strong>ion</strong><br />

Blackout (loss of all AC power) <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant are pre<br />

sented in this report. Section 2 provides a description of the event and<br />

discussion of the motiv<strong>at</strong>ion for consider<strong>at</strong>ion of this event. The normal<br />

recovery from a <strong>St<strong>at</strong>ion</strong> Blackout is described in Sect. 3, the computer<br />

model used for the normal recovery analysis is discussed in Sect. 4, and<br />

the instrument<strong>at</strong>ion available to the oper<strong>at</strong>or is described in Sect. 5.<br />

The actions which the oper<strong>at</strong>or should take to prolong the period of decay<br />

he<strong>at</strong> removal are discussed in Sect. 6, and computer predictions of the be<br />

havior of the thermal-hydraulics parameters during the period when a nor<br />

mal recovery is possible are displayed in Sect. 7.<br />

A Severe Accident by definition proceeds through core uncovery, core<br />

meltdown, and the release of fission products to the surrounding <strong>at</strong>mo<br />

sphere. The equipment failures which have the potential to extend a Sta<br />

tion Blackout into a Severe Accident are discussed in Sect. 8, and the<br />

Severe Accident sequences which would follow during a prolonged <strong>St<strong>at</strong>ion</strong><br />

Blackout are presented in Sect. 9. The consequences of each of these se<br />

quences after the core is uncovered differ only in the timing of events;<br />

the actions which might be taken by the oper<strong>at</strong>or to mitig<strong>at</strong>e the conse<br />

quences of the Severe Accident are discussed in Sect. 10. The instrumenta<br />

tion available following the loss of injection capability during the pe<br />

riod in which severe core damage occurs is described in Sect. 11.<br />

The conclusions of this <strong>St<strong>at</strong>ion</strong> Blackout analysis and the implica<br />

tions of the results are discussed in Sect. 12. This includes considera<br />

tion of the available instrument<strong>at</strong>ion, the level of oper<strong>at</strong>or training, the<br />

existing emergency procedures, and the overall system design.<br />

Appendix A contains a listing of the computer program developed to<br />

model oper<strong>at</strong>or actions and the associ<strong>at</strong>ed system response during the per<br />

iod when normal recovery is possible. The MARCH code was used for analy<br />

ses of the severe accident sequences; the modific<strong>at</strong>ions made to this code<br />

are described in Appendix B and an input listing is provided in Appendix<br />

C.<br />

The pressure suppression pool is the key to the safe removal of decay<br />

he<strong>at</strong> from an isol<strong>at</strong>ed Boiling W<strong>at</strong>er Reactor, but no s<strong>at</strong>isfactory method


Table 1.1 Shared safeguards systems and their auxiliary support systems<br />

System Quantity Function<br />

Standby AC Power Supply System Four diesel gener<strong>at</strong>ors each cou<br />

pled as an altern<strong>at</strong>e source of<br />

power to four Independent shutdown<br />

boards for <strong>Unit</strong>s 1 and 2. Four<br />

additional dtesel gener<strong>at</strong>ors serve<br />

as altern<strong>at</strong>e power sources to four<br />

<strong>Unit</strong> 3 shutdown boards.<br />

250V DC Power Supply System Three b<strong>at</strong>teries, one per unit.<br />

The 250V DC power supplies for the<br />

DC-powered redundant services of<br />

each unit are normally derived<br />

from separ<strong>at</strong>e b<strong>at</strong>teries. A fourth<br />

b<strong>at</strong>tery is provided for common<br />

st<strong>at</strong>ion service.<br />

Control Rod Drive Hydraulic<br />

System<br />

Reactor Building Closed Cooling<br />

W<strong>at</strong>er System<br />

Gaseous Radwaste System<br />

A spare control rod drive hydrau<br />

lic pump Is shared between <strong>Unit</strong>s 1<br />

and 2.<br />

Two pumps and two he<strong>at</strong> exchangers<br />

per unit with one common spare<br />

pump and he<strong>at</strong> exchanger for all<br />

three units<br />

System is unitized except for a<br />

common discharge plenum, ducting,<br />

and the 600-ft stack<br />

<strong>St<strong>at</strong>ion</strong> Drainage System<br />

<strong>One</strong> common drain header Into which<br />

each of the three unit reactor<br />

Standby Coolant Supply System<br />

building floor drainage pumps dis<br />

charge<br />

Completely shared system<br />

RHR Service W<strong>at</strong>er System<br />

Emergency Equipment Cooling<br />

W<strong>at</strong>er System<br />

Standby Gas Tre<strong>at</strong>ment System<br />

Completely shared system<br />

Completely shared system<br />

Completely shared system used only<br />

when an abnormal activity release<br />

occurs<br />

Supply emergency power during loss of<br />

offsite power conditions<br />

Supply DC power when b<strong>at</strong>tery chargers<br />

are not functioning<br />

Provide driving force for normal rod<br />

movement<br />

Provide cooling w<strong>at</strong>er to reactor<br />

auxiliary equipment<br />

Obtain elev<strong>at</strong>ed discharge from the<br />

Standby Gas Tre<strong>at</strong>ment System<br />

Pass reactor building drainage to re<br />

ceiver tanks<br />

Provide means for core cooling fol<br />

lowing a complete failure of the Re<br />

sidual He<strong>at</strong> Removal (RHR) cooling<br />

complex<br />

Provide an assured he<strong>at</strong> sink for<br />

long-term removal of decay he<strong>at</strong> when<br />

the main condensers are not available<br />

for any reason<br />

Distribute raw cooling w<strong>at</strong>er to equip<br />

ment and auxiliary systems which are<br />

required for shutdown of all three<br />

units<br />

Filter and exhaust the air from a<br />

unit zone and the refueling zone, the<br />

refueling zone only, or the entire<br />

secondary containment<br />

for the analysis of the response of the torus and pool under severe acci<br />

dent conditions currently exists, <strong>at</strong> least in the non-proprietary litera<br />

ture. The n<strong>at</strong>ure of the problem and the measures being taken <strong>at</strong> ORNL to<br />

improve the analysis capability are discussed in Appendix D.<br />

In the event of a <strong>St<strong>at</strong>ion</strong> Blackout, the reactor vessel will be iso<br />

l<strong>at</strong>ed behind the closed Main Steam Isol<strong>at</strong>ion Valves (MSIVs) with pressure<br />

maintained by periodic blowdowns through the relief valves to the pressure<br />

suppression pool. Makeup w<strong>at</strong>er to maintain the reactor vessel level must<br />

be injected either by the High Pressure Coolant Injection (HPCI) or the<br />

Reactor Core Isol<strong>at</strong>ion Cooling (RCIC) systems. The oper<strong>at</strong>ion of these im<br />

portant systems is discussed in Appendices E and F.


As a portion of their review of the draft of this report, the Elec<br />

trical Engineering Branch <strong>at</strong> TVA performed a b<strong>at</strong>tery capacity calcul<strong>at</strong>ion<br />

which shows th<strong>at</strong> the unit b<strong>at</strong>teries <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> plant can be ex<br />

pected to provide power for as long as seven hours under st<strong>at</strong>ion <strong>blackout</strong><br />

conditions. Since a b<strong>at</strong>tery life of four hours was assumed for the calcu<br />

l<strong>at</strong>ions of this work, a new Appendix G has been added in which all of the<br />

possible failure modes other than b<strong>at</strong>tery exhaustion th<strong>at</strong> were considered<br />

in Sections 3, 7, and 8 are re-examined for applicability to the period<br />

between four and seven hours after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

The magnitude and timing of the release of the fission product noble<br />

gases and various forms of iodine to the <strong>at</strong>mosphere are discussed in<br />

Volume 2. This includes the development of release r<strong>at</strong>e coefficients for<br />

the escape of these fission products from fuel as a function of tempera<br />

ture, specific<strong>at</strong>ion of the various chemical forms, determin<strong>at</strong>ion of the<br />

optimum str<strong>at</strong>egy for the modeling of precursor/daughter exchange, and the<br />

study of the particular auxiliary systems involved to determine the appli<br />

cable fission product release p<strong>at</strong>hways. These results are incorpor<strong>at</strong>ed<br />

into a vehicle for the calcul<strong>at</strong>ion of the transport of the individual fis<br />

sion products from the reactor core, through the primary and secondary<br />

containments to the <strong>at</strong>mosphere, control volume by control volume.<br />

The primary sources of inform<strong>at</strong>ion used in the prepar<strong>at</strong>ion of this<br />

report were the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant (BFNP) Final Safety Analysis<br />

Report (FSAR), the Nuclear Regul<strong>at</strong>ory Commission BWR Systems Manual, the<br />

BFNP Hot License Training Program Oper<strong>at</strong>or Training Manuals, the BFNP <strong>Unit</strong><br />

1 Technical Specific<strong>at</strong>ions, the BFNP Emergency Oper<strong>at</strong>ing Instructions, and<br />

various other specific drawings, documents, and manuals obtained from the<br />

Tennessee Valley Authority*. Additional inform<strong>at</strong>ion was g<strong>at</strong>hered by means<br />

of one visit to the BFNP and several visits to the TVA Power Oper<strong>at</strong>ions<br />

Training Center <strong>at</strong> Soddy-Daisy, Tennessee. The excellent cooper<strong>at</strong>ion and<br />

assistance of Tennessee Valley Authority personnel in the g<strong>at</strong>hering of in<br />

form<strong>at</strong>ion necessary to this study are gr<strong>at</strong>efully acknowledged.<br />

*The setpoints for autom<strong>at</strong>ic action used in this study are the<br />

safety limits as given in the FSAR. In many cases these differ slightly<br />

from the actual setpoints used for instrument adjustment <strong>at</strong> the BFNP be<br />

cause the instrument adjustment setpoints are established so as to provide<br />

margin for known instrument error.


2. DESCRIPTION OF STATION BLACKOUT<br />

A <strong>St<strong>at</strong>ion</strong> Blackout is defined as the complete loss of AC electrical<br />

power to the essential and nonessential switchgear buses in a nuclear<br />

power plant.2 At the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant, a <strong>St<strong>at</strong>ion</strong> Blackout<br />

would be caused by a loss of offsite power concurrent with the tripping of<br />

the turbine gener<strong>at</strong>ors and a subsequent failure of all onsite diesel gen<br />

er<strong>at</strong>ors to start and load. After these events, the only remaining sources<br />

of electrical power would be the b<strong>at</strong>tery-supplied 250 volt, 48 volt, and<br />

24 volt DC electrical distribution systems; AC power would be limited to<br />

the instrument<strong>at</strong>ion and control circuits derived from the feedw<strong>at</strong>er in<br />

verter or the unit-preferred and plant-preferred motor- gener<strong>at</strong>or sets<br />

which are driven by the DC systems.<br />

The reliability of offsite power <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong> has been excellent.<br />

There are two independent and separ<strong>at</strong>ed sources of 161 KV offsite power to<br />

the plant, each from a different nearby hydroelectric st<strong>at</strong>ion. In the<br />

near future, offsite power will become even more reliable. System modifi<br />

c<strong>at</strong>ions will permit any of the three reactor units <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong>, in the<br />

event of a gener<strong>at</strong>or trip, to receive reverse power from the TVA 500 KVA<br />

grid which these units normally feed.<br />

However, should all offsite power be lost together with the tripping<br />

of the turbine gener<strong>at</strong>ors, there remain eight diesel gener<strong>at</strong>ors <strong>at</strong> <strong>Browns</strong><br />

<strong>Ferry</strong> which are designed to autom<strong>at</strong>ically start and load whenever normal<br />

AC power is lost. By design, all equipment required for the safe shutdown<br />

and cooldown of the three <strong>Browns</strong> <strong>Ferry</strong> units can be powered by six* of<br />

these diesel units, even with the assumption of a design basis accident on<br />

any one unit.3<br />

Therefore, a <strong>St<strong>at</strong>ion</strong> Blackout is an extremely unlikely event. Never<br />

theless, the consequences of a <strong>St<strong>at</strong>ion</strong> Blackout should be studied. It is<br />

important to recall th<strong>at</strong> one <strong>Browns</strong> <strong>Ferry</strong> unit suffered a loss of electri<br />

cal power to all of its emergency core-cooling systems during the March<br />

22, 1975 electrical cable tray fire.4* To determine if <strong>Browns</strong> <strong>Ferry</strong> and<br />

similar nuclear plants can recover from the loss of other combin<strong>at</strong>ions of<br />

AC powered machinery, it will prove most efficient to first consider the<br />

plant response to a loss of all AC powered equipment, as in a <strong>St<strong>at</strong>ion</strong><br />

Blackout.<br />

This study considers the effect on <strong>Unit</strong> 1 <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong> of a Sta<br />

tion Blackout which begins with a loss of offsite power, associ<strong>at</strong>ed tur<br />

bine gener<strong>at</strong>or trip, and failure of all diesels to start. Barring further<br />

equipment failures, the b<strong>at</strong>tery powered systems have the capability to<br />

supply the power necessary to oper<strong>at</strong>e the high-pressure w<strong>at</strong>er injection<br />

systems to maintain the reactor in a stable cooled st<strong>at</strong>e for several<br />

hours. The first seven sections of this report pertain to the methods<br />

which can be used to prolong this period of w<strong>at</strong>er injection capability and<br />

decay he<strong>at</strong> removal for as long as possible.<br />

*With oper<strong>at</strong>or action, any six diesel gener<strong>at</strong>ors would be s<strong>at</strong>isfac<br />

tory. However, for adequ<strong>at</strong>e short term shutdown and cooldown response<br />

without oper<strong>at</strong>or action, the six operable diesel gener<strong>at</strong>ors would have to<br />

comprise three of the four provided for the <strong>Unit</strong> 1/<strong>Unit</strong> 2 complex and<br />

three of the four provided for <strong>Unit</strong> 3.


However, injection capability would ultim<strong>at</strong>ely be lost during an ex<br />

tended <strong>St<strong>at</strong>ion</strong> Blackout, either through exhaustion of the installed b<strong>at</strong><br />

tery capacity or earlier, through secondary failures of vital equipment.<br />

Once injection capability is lost, the <strong>St<strong>at</strong>ion</strong> Blackout would become a<br />

Severe Accident with inevitable core uncovery. The remainder of this re<br />

port proceeds from an assumption th<strong>at</strong> the Blackout does develop into a<br />

Severe Accident, involving core meltdown and subsequent fission product<br />

release to the <strong>at</strong>mosphere.


cfl fi s rH CU > CJ >. 1-1 XI CU cu MH CO ^ cu CM CU cu u CU cu CD u Sh •H •H rH 3 •H cfl CD iH cfl > > CO O<br />

3 0 > M CU CJ CO CO O a CU > CO 3 > •H B CD 4-1 cu a. > 4-1 4-1 CU X X CU CD Ph a<br />

H o cu O cu iH u cu )-l > •H •H S-l M CO CU a* cu rH r-i o CU CO 4-1 a. cfl cfl cfl > u 4-1 Sh Sh 0) B cfl CU CU G Qh •H<br />

O w XI Sh XI O o XI cu o s 4H M XI CO cu Sh cu •fi C XI CO CU Sh U CU<br />

§ 3 U CM axi CO i-H XI CD rH 4-1 4-1 B 4-> 4-1<br />

H CO 60 CO •t CO B G B 4-1 4-1 CO 3 rH 4-1 4-1 B cfl XI o u 3 CO XI 60 cu c CJ . CJ CJ < MH a CD 3 CD c M cu CO m 4-1 •H 4-1 cu H B 60 0 ^ cfl u fi B 3 C cu CU rH >M iH<br />

cj cO o /^ o CJ o CO •r-l O 0 4-1 M 3 4H •H cfl XI o Sh X3 Sh X CU B cfl > XI CU CU 4-1 4H 3 cfl cfl C B •H • 4-1 % CU N--' •H B CO CU CU CU B ^h 3 >, CU MH #H CU X B 4-1 . XI o<br />

J<br />

S-l o a 4-1 U i-H cfl 4-1<br />

s<br />

XI CM 4-1 w u 4J CO O •H B Sh CO XI s 3 CU C X) (U 4-1 C CO Sh ^ CD CU CD CU CN a -H H 4-1<br />

XI c 4-1 4-1 •H CD CU -) CJ u CU CO B CO > fa e i-H CO o •H 4-1 O Sh CU 4-1 C O CU 4-1 O XI B 4-> • B CU 3 c >-> 4-1 rH O 4-1 ^-> • CU<br />

o C 3 cu o X> a M 4-1 XI •H CO cu cfl i? X) m cfl rH CJ 4-1 CD •H B a. rl cfl 3 CU fi rH CU 4-1 o CO •H CD Cfl 4-1 CO CU CD<br />

2; •H Pi •H CU •H cj B 4-1 CU CU B o 4-1 CJ B CO 6 cfl CJ 4-1 4-1 X CU O X) cfl a, -h X CO u •H B u •H<br />

H<br />

4J B pd O o o TJ r-i •H CO 01 4J o •H c rH •H 4-i 4J CU O rH B 3 4-1 CU 4-1 CU •H u-| CJ<br />

. o •H x; cu CU 4J XI CU B O CO 4-1 CU u o •H r-H <br />

4-) m >~> r-i 3 V4 CJ XI B o Cfl O 4-1 •H c CU 4-1 O c CU B c >. 4J B B Sh CO XI CJ CU u CJ rH 4J CU<br />

u o X CO CO B rH CU CO Cfl CU 4-1 o rH 3 2 3 60 Sh 4-1 O •H Sh o 3 CD rH 60 CO CU •H cfl 4-1 4-1 • cu CJ •H rH<br />

CU 4-> •H 60 Cfl cfl cu a. •H CU 3 . cfl O . #. S B 3 O 4-1 60 a. 4-1 •iH CU Sh •H Sh CJ CD rH CU 4H CU 4-1 UH B<br />

•I-) XI T3 c a a > T3 r-t B O 4J CO CU<br />

•H •H 13 t-H 3 rH B rH rH XI CU >S CO 3 4-J 4J B o 4-1 o cu X3 a, CU B CO o •H CU cu £2 X H c CD cfl a. rH o rH rH 4-1<br />

)-l •H o O O O cu 4-1 >-l r^ XI O e a O B • «\ CU •H s O CU 4-1 CU CU<br />

O (U > o ^ u Cfl CU CU 60 J4 Xl cfl cfl CJ XI c rH a Sh CO CU O 4J CO •rl Sh CJ CD CO c o 4-1 > 3 > 3 g<br />

4J a O cj CJ CJ X 4-1 CJ a o XI 60 rH O B > •H 4H tH rH rH rH<br />

>v 4-1 a. CU rH CU cfl •H rH u T-f CO<br />

s cfl 4-1 cu cr 3 H C 3 4-1 cfl C XI o •H >-, 3 M CD CO CU CD<br />

4-1 c H" PQ CO M 3 h Xt •H X) XI PQ M CU o • cO >, CO cu O u o •H rH a •H B Sh 4-1 rH Q. co CD U B u •H 60 > CD<br />

•H cfl CO 3 cu CU CU 3 •H 4-i e 4-1 CU B XI ro 4J XI rH CO u 3 o 4-1 60 o CO cO c V4 cfl 4-1 CJ B 22 CU CU O CD XI B -H CO<br />

iH o •H CO C XI CO 4-1 u-i T3 CO rH Cfl B 3 •H 4-1 u cu CO CU CU 4-1 • CU o 4-1 cu CD CJ rH u X a c u •H 3 rH O •r-l CD CU O, a) 4-1 cfl 4-1 CJ ><br />

43 XI a. 3 CJ 3 Cfl Cfl<br />

cfl •H u H 4J MH CJ i-H a, 4-1 CO 4-1 CD X! CO •H CU •H u CO > cu o 4H XI c > cu Cfl a> U •H U •H 4-1 3 CD . U CU<br />

c u CM cfl o cu rH o 4-1 XI B B Cfl Xl o CU cr o CU O CO CO O 4-1<br />

s<br />

w 4-1 o >-. CO CD CO XI PQ 4-1 4-1 O XI cfl CU 3 O CO XI CO XI XI CJ M o Cfl X1 B x; CU s CO C •H CU CO CU >s 4J CO a CJ rH rH u /-N •H u a M CJ 4J CO 4-1 4J • •* CU Jrf 4-1 cu 4-1 CO Sh a o 4J CU CU ^-^ 4-1 Sh r^<br />

o •H 4-1 u S-i CO M 4J a G XI o CO O CU CU cu Sh CJ CJ CU u S O o rl CO Sh 60 XJ a '-n 3 .<br />

C iH B u cfl u CO •H B >. CO B CU CO Cfl . B 4-1 * Cfl X) o XI CO Oh X CO •H rH 4-1 •H o s-^ w 4J .<br />

cfl u O o o CO a •H •H Cfl 3 CU CO cu rH •H B 4J cfl 4-1 o X U rH •H CU a CU o fi<br />

rH 3 c ~, 4-1 B<br />

CO -*i •rH o a •H<br />

4-1 w CXXI •rH M cu rH B T-{<br />

e<br />

3 XI O CJ CJ o CU B 3 XI 3 CU CO cfl •rl rH B o /—N v£> in q CN<br />

•H o 4J . •H cu 3 Cfl 4-1 B CO u o CU a, B 4-1 a, fi O 4-> CD CU C CJ CO c rH B f=j rH tH 4-1 . .—1 o> -H 00<br />

cfl cfl CO 4-1 •»» e o XI O CJ H S 3 CO 60 8 B O cfl 4-1 •H CO 4-1 c 4J CU O CJ o • cfl M cu O B Cfl 3 B . . CO<br />

C rH rH a cfl CO cu B 4-1 J4 • 60 cfl CD •H 1 o O CJ CU CU CD o CU Sh CJ o rH X) CU CJ CO •H cu cfl B J«S cfl •H CN CN CO s-^<br />

CO PQ o cu u B 4-1 o a B B CU U O rH CJ •H XI CO CU cfl X XI CU CU CJ CU B fa CO 4-1 XI CD Sh c cu<br />

>u CO 4-1 o cu CO B 4-1 cfl o O -H x> a r-t X) CU CD 4-1 Sh c XI X! 4-1 rH > XI cu cfl 4-1 4-> O cfl CD vX CO xi a B<br />

04 O c M CO 4-> 4-) kS •H O ^H H •H 3 CO CJ B CO cfl CO 3 >. CU 3 CU cu o 4J 4J 3 rH (U o cu > Sh CO C 4J Sh r^ •H B "H<br />

sh TJ •H Cfl •3 X Cfl CU CJ 4-1 X3 cu CU XI 4-1 CJ •H C cu CU CU 4J CD CJ A 0, B cfl CU Sh rH 4-1 •H >><br />

u CO y O XI >H }-4 o 3 •H CD O U CM XI 4J rH X! I-H B CM X) CO cfl XI cfl CJ (U CU a. 3 CO B •H Sh 4-1 4-) CU cfl<br />

o a pi o Sh CU 4-1 SQ a i-H T) iH 4-1 cu O 4-1 PQ 4-1<br />

crt Cfl CO XI 4-1 CU •H rH Sh > CO •H Sh O •H O X CO<br />

4J o 3 \s CU cu 60 60 •H XI B rH B >-. -l «. 3 2 B Sh Sh < 1 cfl •H > XI a •rH CO<br />

o 1 CO X) , am 1 X> CU rH •H CU XI<br />

0) C 1 CJ . V4 CU TJ O CO 1 4J 1 CO •rl XI iH 3 O rH Sh >^Xl CU X CU m XI 4-1<br />

CO cfl 1-1 a Cfl CO co cu i-H o CJ 3 X 3 i-H cu 4-1 CO o O * CO •H X) 1 1 4-1 CO XI o 4J<br />

CO >» o •H cu 4-1 CO rH CO CO u cu . a CO rH •H B Oh CD CU CU rH<br />

CD 4-1 ^-s U •H u •H B cfl CO 3 co rH o XI o CO ^i CO CJ u CJ cu CU CO a. rH CU C CU > • cfl 3 o cu cu 4-1 e s > rH<br />

> cfl cj a. •H cu •H o E H CO CJ 4-1 cfl Si o cfl CU rH >.4H tH 3 C CU c cfl CJ CO u Sh 4-1 60 c 4-1 •H 4-1 rH X 3


a r-. 3 CD B rl •H cfl 43 > O (U fa CO 44 a rH 3 CU Cfl -tf 3 60 cu c 3 u CO CO o 3 a Sh P 60 4H s CU CD O fi a C C<br />

0) CJ 4-1 4-1 CU X 4-1 o rH a CU cO O cu CO rH > rH P C 44 •H CO cu r->X> C XJ cu . CD P •H CU ^ XI •> tH •H P (U<br />

4-1 cu 4-1 CO 4-1 CO rl Sh cu >. 44 43 CM cu MH CO o cfl U<br />

S CO 44 M rH CU P a 44 44 44 CU o-o CU Sh > cfl m tH XI<br />

CO CM Xi c rS CD iH 3 O CO rH cu 3 U 44 U en XI CU CO C<br />

>> o iH CO >^ 4-1 Oh cu a CO > CTl CO >> Cfl o 43 fi 44 o 44 CU • S fi c c 44 P CU >> cfl CO 44 c o U xi CU CO CD 43 w CO 3 cu y<br />

CD 60 O. •U O CU •H 44 3 a CD « • 44 Cfl CU rH > •H rH U rH C P cu i-H rH 44 u Cfl p CD B •H m CO OJ cu a 44 CO CO rl<br />

rH rH fi C CJ -rl 43 CD o CO O CU u 44 CO 44 CJ rH . P rH rH 44 CO Sh a CO 60 fi fa 44 c TH Oh O rH<br />

m CD a<br />

s, XI CO rH 3 fi rH 43 cu a fa fi u CO 44 P 3 rH CO 44 4a cfl 60 Oh «t (U 44 X) 44 •H 03 cu 43 XI -H . U<br />

rH > C en o cfl •H rH 44 rH CD CU 0 O a c CU CO X Sh CO B cfl co 3 fi a >s > 44 fi CD a o rH MH XI 44 B 44 t U O<br />

PO CU c tH CD O Sh •H • •H 44 43 O •H •H c 44 CJ CD rl fi •H 3 rH o •H P u cfl 9! 2 p CU o c<br />

C O MH<br />

. rH o CO 0. • 4J 4-1 rH 3 > CN CO 43 Oh 43 CD 43 fi CU CO Oh 43 B 3 CO m fi cfl 44 44 H « y 44 CO u CO CO B CO XI<br />

Sh 4-1 XI < o fi cfl •H a co —' 44 44 O XI 44 I-H U >> p r XI CO •H U rH CO CO m Oh OJ r U CU<br />

> 43 CM . —i y P 3 43 •H 43 a 44 0.-H<br />

CO 4-1 43 tH rH rH XI 44 43 Sh rH cu o . CU c •H > C p CJ 43 3 p . 44 •H P 43 cu cu 60 P CO n-' a MH Oh 44 Oh 44 3 P P Cfl<br />

(r. 3 •H H >-. CD<br />

CO CO CD c o 44 CO 60 43 cfl X) O a P •H rH M 44 P a<br />

S<br />

r^ fi 44 U •H 3 rH 3 u cu XJ Oh a MH<br />

4-1 fi rH 4-1 > C >> Oh CO Oh CO • fi 44 •H Oh o X 44 CJ CJ 3 CD cu CO y Sh Q o<br />

g 3f0-H 60X1 > O rH CO •H S Oh<br />

O XI U O XI H X «t M O ••> CO 44 tH 44 fi > CO CO 44 o CD 44 iH •H p 13 Sh CD rH P P y a M CD P Cfl Sh CU 44 P CO<br />

in 4-1 x) CD l£> 4-1 CO •H cu O a CU CU 3 •H rt rH CM 43 X><br />

§ 44 •H P rH 44 X 3 44 44 cfl ^\ cu a 44 44 44 MH 3 cO<br />

\^r fi a. ^-^ CJ XI 44 44 u C 44 44 CO q u PQ MH 44 fi rH cfl 44 CJ H fi p Oh CO 44 XJ cu CO C U iH (U<br />

O XI 4-1 CO >Mfa •rl > CU 44 CO a Sh CO 60 44 CU P S. 3 44 fi CD CD H M Sh 44 44 CO M 60 cfl 44 fi y XI rH C<br />

O cu 4-1 cfl O tH rH CO CD CO M CJ CU S CJ 43 Sh 43 44 fi P fi CJ X 0 XI •H tH CO CJ rl tH fi cfl CO CD 3 O<br />

«t a M MH CD o CJ -* 3 O o o iH p rH MH 43 43 1 a rH CD Oh CJ O • 4-1 rH 44 fa •* 44 U CJ CJ | XI 44 CD rH CO Oh CO •H >. >. 44 43 cm CU rl<br />

Oh V0 93 fi a >> CU * CO CO O Sh 92 CO i-H O 44 CD B Sh CU fi 0 CD rH c •H P rH S3 cfl rH y 43 Oh CD cfl 3 c CU CU 44 XI<br />

CN cu tH O . • CU 43 44 Oh 44 44 CD CO CU o •H Oh u CO PQ M CD 44 CD 43 rS N-' CJ 0) 60 ••> y 43 XI<br />

a M 00<br />

CU<br />

U 1<br />

CU<br />

u 13 1 m cu CD<br />

XI<br />

CU X" 1<br />

1<br />

CO<br />

1<br />

fi 44<br />

CU<br />

CU 43 CU 60


CTi<br />

XI XI 1 1 CO<br />

1 ^N fi 1 fi CU 1 CO | fi . •h y<br />

y y<br />

co r^ >s CD U 0) XI u CO CO fi 1 N CO P tH co p CO 1 rH CO !>> 3<br />

1 •H r^ 43 1 1<br />

cu X 44 o Oh CU 1 o 3 •H U tH fi H 43 cu •H c M y o •H MH 43 XI 4-1 CD 44 ^-\ 44 >> Oh p o.<br />

u fi Cfl 44 •H 44 P 44 44 •> y cu u CD Oh 44 u 44 CO fi •H 44 CD CU X rl . P CD y MH fi CO 60 rH P 44 3<br />

0. p XI CD y o. CO 44 y y .*> tH Oh a 3 CD 0. Oh CO cfl 44 3 43 43 cfl tH 44 CO Sh • * p y y a tH y a CO<br />

tH CU M rt rH u 3 co Cfl 60 44 p P CO 43 P CO fi 44 0> 44 CO 44 •H CO fi >* 01 P B 0> u tH y p co y o y Sh<br />

CU 44 rH 43 CD MH tH p cfl cu •H<br />

CO 44 •H tH 0) CO 43<br />

g£<br />

1 44 rH CU rH > 44 01 > OhiH 3 44 Oh c 43 O y<br />

xi y P 44 u 0> cfl rH u y co >> cu 43 43 Sh P O 44 P 0) i-H a PmrH CO 44 •H y 44 3 •H CO 44 44 sh<br />

44 CU P •H 44 MH •H Oh p rH U CO y C CO 44 MH % XI rH CU P fi 44 44 P p a Cfl O tH cu y CU tH 44 44<br />

J cfl Q C 44 •H >> cfl 44 c rH y a > cn y cfl CO<br />

MH 44<br />

s<br />

60 43 OhiH CU MH fa a x> 0) XI • > P 43 XI CO rl 43 CO CM cfl CO 44 P<br />

•H 44 44 CD Sh rl rH • a 01 Cfl > tH Sh rH U 44 44 c 44 c •H co CD p<br />

£ 2 P 43 tH CO 44 rH r^ y fi T) w<br />

3 H CO 44 3 CO cfl 44 CT\ /~\<br />

22 rl rH rH P P Cfl tH p 3 tH XI 0.X) 43 43 •H 44 44 CO y co . y > p 3<br />

r-H tH Sh y 43 CD 3 cu i-~ 60 in tH 2 C 44 > CO >> C y X 0) 43 60 P 01 44 44 tH 44<br />

CO CD y<br />

> rH tH C xi<br />

• rH O XI P P tH 43 XI P CO . •rl. -3" OJ Cfl > 0> cfl U CU CD 44 y fi •> r. > -d •H t u > 44 CO 43 rH CO 44 y y<br />

44 iH rH MH Oh U H c Oh r^ CO CO 43 > rH u MH P CO 0) CD 01 rH rt •H tH C O 3 3 CO 0 X) V CO y H 2 > 0. Sh<br />

3 60 3 44 cfl 0) Oh ' cfl MH P cu CD 3 co 3 43 rH 43 tH •5 U > 3 u<br />

o co a P C 44 CO MH u u o p 0) CO Oh tH 44 CO 44 44 43 cfl y 3 3 y 0. XI CO P c cfl CD o o 0) 44 y 44 xj y<br />

44 cfl tH 3 P CU tH • CO P cfl P m CO CU •H P rH CD 01 cfl rH p XJ a o> c tH 0) 44 44 Oh y • a MH tH y C MH<br />

y n-* 44 •H 60X1 rH •- MH CM cfl rH 43 rH cu cu CU U X Sh u •rl CO M<br />

p 44 01 rt 01 u P 43 /-n tH y 44 cfl Cfl CO<br />

rt rt CO 44 Sh P > CD CO rH Cfl 44 01 43 1) U 43 0) CU CD Cfl CO B 0) I^S •H tH 44 ^ tH > cfl 44 60 P •H<br />

C<br />

rH 44 y tH y Cfl rH P rH y CU 44 rH 60 Sh 44 > H fi CO XI Oh > m 0> Sh 01 Sh tH 44 XI u y rH y >^ tH OnrH 1 MH « cfl<br />

PQ P tH 43 cu H cfl a CO M > CU w c fi CO rH rH 44 C p cfl 44 3 44 P MH Cfl C tH p cfl u rH y CO 44 y P P C U<br />

43 U 44 . 44 tH a 3 rH CD tH Cfl 0) 0> MH 2 rt CO fi 13 c CD CD CO CO fa SH P 43 . CO > rH rH Oh y u 44 y 44<br />

B X CO o CU 44 fi P Cfl co 3 y rl 43 p > 3 • CO cfl tH Sh Sh >^ CO >. CO 0) y 44 CO Cfl XI CO y co 3 u On<br />

OPS • «* a Sh 60 fi p cu CO > 0) fa p tH 44 fi B 44 •H cfl CO CD CO tH Oh u cfl O . 01 3 >^o MH cfl y p >><br />

tH CO rH 44 0) a cfl CU •H 43 rl a rH co 3 c MH<br />

IS >» . CD rt SH /TS P 44 rH cu CO CU 44 B y o 44 p 43 60<br />

44 CO 44 44 Sh CO 44 rH 01 Cfl rH CD CT MH p cu rH rl s~\ 43 CO CO 0. C • CO 3 rH > CO > CO 2 CTi CO fi a J^ u<br />

Cfl 0) CD CD CO CU CO CD CO CO CO o p > 01 P tH •H 1 CO 44 CU 60 XJ cu tH O 44 CU 01 q co •H CD 44 r^ rH a p y Sh CO 3 y y<br />

44 43 fi 43 >, Sh ' ** CD MH C CU U v© MH rH U 4-1 rH CU >% c > •H X) cu > 43 rH •H 3 > > 44 CU > Cfl P r 44 XJ 3 y c •H c<br />

CO tH Sh CO 3 rl 2 s p Sh XI 3 00 2 c CJ 44 CO 0) tH CO rH N rH H CD 4 OH rH y Sh y rH > CO 01 B P 43 43 44 y<br />

XJ X CD CO 3 3 a 01 44 P • 44 > CO p 3 rl P 44 01 Oh 3 •H 2 >-' CO y 44 co cfl CO o 0) Cfl 1 tH 44 >> Cfl rH a 44 y CO<br />

C0 rH U > cu CO 44 y o. 44 MH r~~ Cfl •H tH 44 B rl 44 y P Sh > CO cu y > > rH MH Sh > y CO P U *—' 3<br />

I * 43 44<br />

3 3 P CO 01 u 3 X MH 01 MH 43 44 y CU<br />

O 3 3 CD •>-i P - Sh CO 0) H CO cfl 43 z$ o CO MH • > C H MH CU XI g X fi CU CD tH rH Sh HIH ]| rH XI 60 43<br />

a rH 44 Sh cu CD 44 P Sh 60MH Sh rH CD Sh U rH 4) /—\ u cu tH CO Sh tH H O X) 44 CO rH Sh MH CD rH > CO y fi y<br />

CO rl 0) 3 0> 44 fi u CO fi 3 tH 01 . a P P P P I4(n XI p u rH<br />

0) C rH MH •H tH CO<br />

32 * y P P U v^ i-H 44 44 •H > >*<br />

Sh CD 44 P MH Sh CU 3 0. P CO 44 rH r< a p MH 44 MH Sh fi 44 13 CO Oh 0) Sh P 01 44 > >> CD 0. 44 y co o CO Sh rH Cfl<br />

3 44 CO 3 P s<br />

Ifi I CO 3 60 fa Oh CU rH p 44 •H MH Cfl CO u w y 3 -H rl 44 Cfl P CO 43 rH fi cfl > 44 tH 22 cfl y<br />

o rt >><br />

CO C<br />

. p rH U Sh u c 0) XI cfl CO 44 •H 44 Sh 44 CD CO P u fa y 3 > y<br />

43 3 co A c 44 cu CO •H in "t u o2 rt 22 •H tH P 0) (^ m u 01 >, a CD CO cfl to a co a Sh fi fi U o CO a MH y p P XI<br />

X) p . S*. Sh 0) U . o 0) Cfl y 3 cfl CO CJ 44 m oo Oh u u CD U y 44 q u tH rl P p 44 44 rt y 43 CO rH MH<br />

CD rH M 0) tH rH rSrH 0. c tH CU rH U 0) B ^ tH P Cfl >~* n en tH P CO an XJ rH rl p 44 a CO CU 0. 0H CU tH MH CO 44 P U C O rH cfl tH 43<br />

rl P fa a cfl u 60 cu rH cr 3 > P CU rH 01 CO cfl u CO •H >S43 1 a X X) rH Cfl y o> p co y CO . rH 44<br />

43 0.33 3 U 44 X) 3 43 cu CO CU cfl Oh 44 43<br />

H Sh N CU a a fa rl CO 44 3 tH p fi U 0 XI >-» rl OntH • M y fi •~N y<br />

44 o. 0) c OJ P 44 a u CO cfl > > c o. 44 tH 3 o a Sh MH 0. O 60 CO 44 3 tH Sh CD rH y CD P CO vX y p •H u y<br />

fi r. 0. p XJ rl cfl CU fa tH . y p C rl rS rH tH P C 01 rH C rt 44 XJ 0. Oh Sh co y 3 •H CO 44<br />

44 O P 60 P CJ tH P CU fi ri a MH 43 CD 43 CJ M MH o 3 rl >-.vO CO Cfl 01 p y tH CU XI «t c •H 0. P 3 0) y XI 43 X) 44 Oh cfl 3<br />

CO tH fi > CO 44 44 p o. y U 44 P P y co a i-H • CTl >>43 tH 3 * rl 43 cu 0) rH o > 3 CO 43 y B 4J y y 43 •<br />

rl CO CJ tH XI CU P fi CO tH


10<br />

As in the case of reactor vessel level control, it is intended th<strong>at</strong><br />

the most realistic assumptions concerning pressure control be used in this<br />

study. Accordingly, it will be assumed th<strong>at</strong> the oper<strong>at</strong>or does take the<br />

actions in regard to pressure control as described above. However, it<br />

should be noted th<strong>at</strong> without oper<strong>at</strong>or action, the pressure would cycle be<br />

tween the limits of 7.377 and 7.722 MPa (1055 and 1105 psig); unfortun<strong>at</strong>e<br />

ly, it is probable th<strong>at</strong> this would occur through the repe<strong>at</strong>ed oper<strong>at</strong>ion of<br />

the same relief valve causing severe localized he<strong>at</strong>ing in the vicinity of<br />

the tailpipe discharge in the suppression pool.<br />

Short-term Plant St<strong>at</strong>us. Within minutes after the inception of a<br />

<strong>St<strong>at</strong>ion</strong> Blackout, both reactor vessel level control and pressure control<br />

will be achieved with or without oper<strong>at</strong>or action. An open cycle will<br />

exist, with w<strong>at</strong>er pumped from the condens<strong>at</strong>e storage tank into the reactor<br />

vessel, converted to steam there by reactor decay he<strong>at</strong>, and subsequently<br />

passed to the pressure suppression pool and condensed. S<strong>at</strong>isfactory re<br />

actor cooling is provided, but both the pressure suppression pool level<br />

and temper<strong>at</strong>ure are increasing, as is the drywell ambient temper<strong>at</strong>ure due<br />

to loss of the drywell coolers. The reserve DC power stored in the b<strong>at</strong><br />

teries is being dissip<strong>at</strong>ed.<br />

There is a 250V DC b<strong>at</strong>tery for each unit <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong>, plus a sta<br />

tion b<strong>at</strong>tery for common loads. Each unit b<strong>at</strong>tery is designed to provide a<br />

guaranteed supply of direct current for the first 30 minutes of a design<br />

basis accident. Under the less severe conditions of a <strong>St<strong>at</strong>ion</strong> Blackout,<br />

and assuming prudent actions by the oper<strong>at</strong>or to conserve b<strong>at</strong>tery poten<br />

tial, DC power should be available for the first 4-6 hours of a <strong>St<strong>at</strong>ion</strong><br />

Blackout.<br />

Long-Term Consider<strong>at</strong>ions. Once DC power is lost, the HPCI and RCIC<br />

systems will be inoperable and cooling w<strong>at</strong>er can no longer be injected<br />

into the reactor vessel. With prudent and realistic oper<strong>at</strong>or actions,<br />

this should not occur until 4-6 hours* after the inception of a <strong>St<strong>at</strong>ion</strong><br />

Blackout. However, there are other consider<strong>at</strong>ions which must be properly<br />

addressed during this 4-6 hour period during which all efforts would be<br />

made to accomplish the restor<strong>at</strong>ion of AC power.<br />

First, since all plant ventil<strong>at</strong>ion is stopped during a <strong>St<strong>at</strong>ion</strong> Black<br />

out, the ambient temper<strong>at</strong>ure near the RCIC turbine may reach 93.3°C<br />

(200°F), causing an autom<strong>at</strong>ic isol<strong>at</strong>ion of the RCIC system. This is un<br />

likely since the RCIC system will be oper<strong>at</strong>ed only intermittently, and the<br />

turbine is not loc<strong>at</strong>ed in a closely confined space. If isol<strong>at</strong>ion does oc<br />

cur, the isol<strong>at</strong>ion signal can be overridden by the placing of rubber insu<br />

l<strong>at</strong>ion between the appropri<strong>at</strong>e relay contacts in the auxiliary instrumen<br />

t<strong>at</strong>ion room, or the HPCI system can be used as a backup.<br />

Second, a relief valve might stick open although it should be noted<br />

th<strong>at</strong> the currently installed two-stage Target Rock valves are much less<br />

prone to this malfunction than their three-stage predecessors. A stuckopen<br />

relief valve would produce difficulties with localized suppression<br />

pool he<strong>at</strong>ing, but reactor vessel pressure would not decrease to the point<br />

th<strong>at</strong> the HPCI or RCIC system turbines could not be used. This eventuality<br />

is discussed in more detail in Section 8.2.<br />

*Recent b<strong>at</strong>tery capacity calcul<strong>at</strong>ions have indic<strong>at</strong>ed th<strong>at</strong> DC power<br />

may remain available for as long as seven hours.


11<br />

A third consider<strong>at</strong>ion would be the continued availability of conden<br />

s<strong>at</strong>e storage tank w<strong>at</strong>er for injection into the reactor vessel. As previ<br />

ously discussed, there is a guaranteed minimum stored supply of 511.0 m3<br />

(135,000 gallons) available to the HPCI or RCIC systems. As illustr<strong>at</strong>ed<br />

in Section 7, only about 359.6 m3 (95,000 gallons) would be used during<br />

the first five hours of a <strong>St<strong>at</strong>ion</strong> Blackout. It can be concluded th<strong>at</strong> an<br />

adequ<strong>at</strong>e supply of condens<strong>at</strong>e storage tank w<strong>at</strong>er is provided for injection<br />

during the period in which DC power will remain available.<br />

A fourth consider<strong>at</strong>ion is the availability of sufficient stored drywell<br />

control air to permit the desired number of remote-manual relief<br />

valve actu<strong>at</strong>ions during the period of <strong>St<strong>at</strong>ion</strong> Blackout. The accumul<strong>at</strong>ors<br />

provided for the six relief valves associ<strong>at</strong>ed with the ADS system are<br />

sized to permit five oper<strong>at</strong>ions per valve, or a total of 30 actu<strong>at</strong>ions.<br />

As illustr<strong>at</strong>ed in Section 7, less than 25 relief valve actu<strong>at</strong>ions will be<br />

required during the first five hours of a <strong>St<strong>at</strong>ion</strong> Blackout. It can be<br />

concluded th<strong>at</strong> there is enough stored air in the ADS relief valve accumu<br />

l<strong>at</strong>ors alone to permit the desired number of relief valve oper<strong>at</strong>ions dur<br />

ing the period in which DC power is available. In addition, the stored<br />

air in the Drywell Control Air system receivers provides an ample backup<br />

to the accumul<strong>at</strong>or supply.<br />

A fifth consider<strong>at</strong>ion concerns the steady he<strong>at</strong>up of the pressure sup<br />

pression pool w<strong>at</strong>er with no means of pool cooling available during <strong>St<strong>at</strong>ion</strong><br />

Blackout. The pressure suppression pool of approxim<strong>at</strong>ely 3785 m3 (one<br />

million gallons) of w<strong>at</strong>er is contained within a torus of 33.99 m (111.5<br />

ft) major diameter and 9.45 m (31.0 ft) minor diameter. The torus sur<br />

rounds the drywell and reactor vessel as shown in Fig. 3.1.<br />

The large he<strong>at</strong> sink afforded by the pressure suppression pool w<strong>at</strong>er<br />

can be effectively utilized during a <strong>St<strong>at</strong>ion</strong> Blackout only as long as the<br />

steam being discharged into the pool via the relief valves is condensed.<br />

If the local temper<strong>at</strong>ure of the w<strong>at</strong>er surrounding the relief valve<br />

tailpipe terminus in the pool is excessive, condens<strong>at</strong>ion oscill<strong>at</strong>ions may<br />

occur causing gross unstable vibr<strong>at</strong>ions of the torus assembly and pressuriz<strong>at</strong>ion<br />

of the torus airspace due to the escape of s<strong>at</strong>ur<strong>at</strong>ed steam from<br />

the w<strong>at</strong>er surface. This effect is discussed in detail in Appendix D. For<br />

the "T-quencher" type of discharge header which is installed <strong>at</strong> the ter<br />

minus of each relief valve tailpipe <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1, the condensa<br />

tion oscill<strong>at</strong>ions are not expected to occur if the local pool temper<strong>at</strong>ure<br />

is limited to 93.3°C (200°F) or equivalent to 87.8°C (190°F) average pool<br />

temper<strong>at</strong>ure.6<br />

The T-quencher dischargers on the tailpipes of the thirteen primary<br />

relief valves are distributed approxim<strong>at</strong>ely evenly around the torus, as<br />

shown in Fig. 3.2. This diagram is posted on the <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 con<br />

trol room panel which contains the relief valve oper<strong>at</strong>ing switches. Dur<br />

ing a <strong>St<strong>at</strong>ion</strong> Blackout, it would be incumbent on the oper<strong>at</strong>or in his ef<br />

forts to manually control reactor vessel pressure to ensure th<strong>at</strong> oppo<br />

sitely loc<strong>at</strong>ed primary relief valves are oper<strong>at</strong>ed in turn so th<strong>at</strong> the<br />

energy input to the pressure suppression pool is evenly distributed.<br />

As illustr<strong>at</strong>ed in Section 7, the average pressure suppression pool<br />

temper<strong>at</strong>ure will have reached approxim<strong>at</strong>ely 82.2°C (180°F) five hours<br />

after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout. It can be concluded th<strong>at</strong> with<br />

oper<strong>at</strong>or action to altern<strong>at</strong>e the relief valve discharges, the pressure<br />

suppression pool temper<strong>at</strong>ure will not reach the point when condens<strong>at</strong>ion


DRYWELL<br />

12<br />

Fig. 3.1 Arrangement of drywell and torus.<br />

ORNL-DWG 81-8602 ETD<br />

REACTOR VESSEL<br />

oscill<strong>at</strong>ions might occur during the first five hours of a <strong>St<strong>at</strong>ion</strong> Black<br />

out.<br />

As a rel<strong>at</strong>ed m<strong>at</strong>ter, the HPCI system is equipped with logic which<br />

will autom<strong>at</strong>ically shift the suction of the HPCI pump to the pressure sup<br />

pression pool if the indic<strong>at</strong>ed pressure suppression pool level increases<br />

to a certain point, as discussed in Appendix E. Depending on the initial<br />

w<strong>at</strong>er level in the pool, this will occur following an increase in pool<br />

volume of between 257.4 and 370.9 m3 (68,000 and 98,000 gallons), or<br />

sometime between two and four hours into the <strong>St<strong>at</strong>ion</strong> Blackout. As previ<br />

ously discussed, the HPCI system is not expected to be utilized but merely<br />

to serve as a backup to the RCIC system. However, to preserve the HPCI


259°<br />

PCV 1-19 pcv l-»<br />

PCV 1-22 KV 1-30<br />

PCV 1-31<br />

1<br />

PCV 1-34<br />

Pnl 9-3 Controls<br />

1<br />

191°<br />

13<br />

180°<br />

Fig. 3.2 <strong>Unit</strong> 1 relief valve discharges.<br />

RELIEF VALVE POSITIONS<br />

OPPOSITE VALVES<br />

PCV 1-42 PCV 1-18<br />

PCV 1-41 PCV 1-22<br />

PCV 1-34 PCV 1-4<br />

PCV 1-30 PCV 1-5<br />

PCV 1-31 PCV 1-2<br />

PCV 1-19<br />

PCV 1-180 PCV 1-179<br />

ORNL-DWG 81-8603 ETD<br />

system as a viable backup, the oper<strong>at</strong>or should take action to maintain the<br />

pump suction on the condens<strong>at</strong>e storage tank. This can be done by racking<br />

out the motor-oper<strong>at</strong>ed breakers for the suction valves, arid will prevent<br />

the excessive HPCI system lubric<strong>at</strong>ing oil temper<strong>at</strong>ures which would result<br />

from the pumping of the hot pressure suppression pool w<strong>at</strong>er.<br />

The sixth and most important consider<strong>at</strong>ion for long term stability<br />

following a <strong>St<strong>at</strong>ion</strong> Blackout is the he<strong>at</strong>up of the drywell <strong>at</strong>mosphere. The<br />

ten drywell coolers immedi<strong>at</strong>ely fail on loss of AC power, while the r<strong>at</strong>e


14<br />

of he<strong>at</strong> transfer to the drywell <strong>at</strong> th<strong>at</strong> instant from the hot [287.8°C<br />

(550°F)] reactor vessel and associ<strong>at</strong>ed piping is about 0.98 MW (3.35 x<br />

10° Btu/h). Under this impetus, the drywell temper<strong>at</strong>ure rapidly in<br />

creases. After a few minutes, the drywell temper<strong>at</strong>ure will have signifi<br />

cantly increased so th<strong>at</strong> the r<strong>at</strong>e of he<strong>at</strong> transfer from the reactor vessel<br />

is reduced while a substantial r<strong>at</strong>e of he<strong>at</strong> transfer from the drywell <strong>at</strong><br />

mosphere to the rel<strong>at</strong>ively cool drywell liner has been established, as<br />

discussed in Section 4.<br />

The design temper<strong>at</strong>ure for the drywell structure and the equipment<br />

loc<strong>at</strong>ed therein is 138.3°C (281°F). The response of this structure and of<br />

certain safety components within the drywell to higher temper<strong>at</strong>ures has<br />

been previously investig<strong>at</strong>ed7 and the results are summmarized below:<br />

It was determined th<strong>at</strong> the drywell liner will not buckle under liner<br />

temper<strong>at</strong>ures as high as 171.1°C (340°F) nor would this temper<strong>at</strong>ure produce<br />

higher than allowable stress intensity.<br />

The drywell electrical penetr<strong>at</strong>ions were purchased with a specified<br />

short term (15 min) temper<strong>at</strong>ure r<strong>at</strong>ing of 162.8°C (325°F) and a long term<br />

r<strong>at</strong>ing of 138.3°C (281°F).<br />

It was determined th<strong>at</strong> the stresses in the drywell piping penetra<br />

tions would not exceed the allowable stress intensities <strong>at</strong> a temper<strong>at</strong>ure<br />

of 171.1°C (340°F).<br />

A DC solenoid control valve used for the remote-manual oper<strong>at</strong>ion of<br />

the primary relief valves was tested <strong>at</strong> 148.9°C (300°F) for ten hours with<br />

118 actu<strong>at</strong>ions during the test period. An AC-DC solenoid control valve<br />

for the Main Steam Isol<strong>at</strong>ion valves was tested <strong>at</strong> 148.9°C (300°F) for 7<br />

hours with 83 actu<strong>at</strong>ions each on AC, DC, and the AC-DC combin<strong>at</strong>ion. The<br />

maximum temper<strong>at</strong>ure achieved during each of these solenoid tests was<br />

153.3°C (308°F).<br />

The electrical cable which feeds the safety equipment inside the drywell<br />

has a 600-V r<strong>at</strong>ing with cross-linked polyethelene insul<strong>at</strong>ion. It has<br />

seven conductors of number 12 wire with no she<strong>at</strong>h. It is estim<strong>at</strong>ed th<strong>at</strong><br />

the ten-hour temper<strong>at</strong>ure r<strong>at</strong>ing is in excess of 160.0°C (320°F).7<br />

The results of these tests and investig<strong>at</strong>ions indic<strong>at</strong>e th<strong>at</strong> it can be<br />

confidently predicted th<strong>at</strong> the primary relief valves will remain operable<br />

and the drywell penetr<strong>at</strong>ions will not fail if the drywell ambient tempera<br />

ture is prevented from exceeding 148.9°C (300°F) during the normal recov<br />

ery phase of a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

With the oper<strong>at</strong>or acting to maintain reactor vessel level by use of<br />

the RCIC system and to control vessel pressure between 7.688 and 6.309 MPa<br />

(1100 and 900 psig) by remote-manual relief valve actu<strong>at</strong>ion as previously<br />

discussed, the drywell ambient temper<strong>at</strong>ure would reach 148.9°C (300°F) in<br />

one hour (curve A of Fig. 3.3). Before this occurs, the oper<strong>at</strong>or should<br />

act to reduce the reactor vessel pressure by blowdown to the pressure sup<br />

pression pool. This will reduce the temper<strong>at</strong>ure of the s<strong>at</strong>ur<strong>at</strong>ed liquid<br />

within the reactor vessel and thereby reduce the driving potential for<br />

he<strong>at</strong> transfer into the drywell.<br />

The vessel pressure reduction would be by remote-manual actu<strong>at</strong>ion of<br />

the primary relief valves, and should proceed <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Techni<br />

cal Specific<strong>at</strong>ions limit of a r<strong>at</strong>e equivalent to a 55.6°C/h (100°F/h) de<br />

crease in s<strong>at</strong>ur<strong>at</strong>ed liquid temper<strong>at</strong>ure. The response of the drywell ambi<br />

ent temper<strong>at</strong>ure to such a reactor vessel depressuriz<strong>at</strong>ion begun <strong>at</strong> one<br />

hour after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout is shown by curve B of Fig.<br />

3.3.


DRYWELL AMBIENT TEMPERATURE (°F)<br />

03 P<br />

3 13<br />

0. (D<br />

Oh 03 13<br />

rl 00 fD<br />

rt p.<br />

(D 3<br />

03 H<br />

Hi fD<br />

Oh CO<br />

Cd P<br />

^g<br />

3 m<br />

CD fa<br />

fi<br />

H<br />

fD<br />

03 rf<br />

o<br />

o<br />

CJ<br />

CJ1<br />

o<br />

^ (D °<br />

1-t<br />

03 -<br />

rj fD<br />

£<br />

fD<br />

°<br />

3*<br />

rj 3<br />

OQ<br />

O<br />

3<br />

o<br />

(D<br />

O &)<br />

• rt<br />

cr» o<br />

ro H<br />

ro co p.<br />

H» rt<br />

I-h rt<br />

a o<br />

03 i-J o<br />

cr ro pi<br />

h X o<br />

O O rt<br />

c ro o<br />

OQ H- H<br />

CO O<br />

141 r-i B<br />

5 fB Cd On rt H- <<br />

rt 3 cr I-1 . (D rt (D<br />

fa on rt CD<br />

& _H O<br />

fo cr e o o 3 rt co<br />

vj rt *• n 03 rjH (D<br />

p --, rt (D H<br />

<<br />

fi rr<br />

/-\ fD e j> rt < B fa<br />

« rj H.<br />

fD Co (D<br />

H. [U < s3 h- H !>< 13<br />

rt oo fD o o<br />

a4 ro<br />

c o tJ 03 5 CD<br />

rj O /-n<br />

rt v< Hi Nj m a^ 0. P) rl<br />

2 5 oo fD <br />

MOO Tl rt fD (D CD ft<br />

oo CO 00<br />

pa ««• rt fi W m m<br />

3)<br />

8 V)<br />

O c C ><br />

z 33 31<br />

H<br />

— N N<br />

H±<br />

O<br />

> ><br />

_, H H<br />

o<br />

O O<br />

3 z z<br />

3 Cfl Cfl<br />

-H H<br />

> ><br />

H<br />

3) 3)<br />

><br />

-H -1<br />

3J<br />

-H Z Z<br />

a o<br />

Z<br />

O > ><br />

Tl Tl<br />

> H H<br />

m m<br />

-1<br />

3) 3)<br />

m<br />

OJ<br />

3"<br />

fD<br />

03 a<br />

03<br />

r>Hl<br />

r- |-H fD<br />

rovj pj<br />

Ui O<br />

O rt<br />

01 o P<br />

rl<br />

rt It 3<br />

O CD •<br />

rt 43<br />

fD C P<br />

M H-fl<br />

O- (D<br />

l-l<br />

crop<br />

CD 3 H<br />

ro<br />

n<br />

o><br />

oo<br />

ro<br />

|-H fB<br />

On rt<br />

0.<br />

H<br />

Oh rt<br />

i-l <<br />

MO It<br />

«H NJ<br />

H" O<br />

p<br />

Ul |-H CD<br />

CD<br />

13 rt (D<br />

M P"H<br />

pi p.<br />

rt a<br />

n> a<br />

H- fD<br />

00<br />

x-' < CO<br />

• fD<br />

CO fa<br />

CD fD<br />

a1<br />

fD<br />

P <<br />

SI 03 o<br />

M 03<br />

1—0 0<br />

r-' CD<br />

ui cr<br />

• P CD<br />

On rt)<br />

o CO<br />

O — fD<br />

oj n><br />

-tn oo a<br />

N5 •<br />

P- OJ rt<br />

o o jr<br />

O O 03<br />

*l rt<br />

s<br />

m<br />

13<br />

ro<br />

rl<br />

03<br />

rt<br />

fi<br />

rl<br />

ro<br />

ID<br />

CO<br />

CO<br />

a<br />

H<br />

H~<br />

N<br />

fD<br />

Oh<br />

H-<br />

CO TJ<br />

n<br />

13 ID<br />

rl CO<br />

(D CD<br />

CO B<br />

CD l-(<br />

a fD<br />

fD r- (S<br />

I-" ~j n<br />

Q O M<br />

33 o O<br />

O<br />

r- CO<br />

H>^-\"^j<br />

oo oj co<br />

• oj rt<br />

VO 00 fD<br />

o o B<br />

• ho rt<br />

00 rf<br />

r- fD<br />

o<br />

fa<br />

fi<br />

rl<br />

H><br />

3<br />

00<br />

>*• l-t<br />

» V,<br />

S3<br />

-»<br />

33 ro<br />

o<br />

ro cr<br />

CO 3<br />

13 O<br />

fD fD<br />

O >o<br />

H- rt<br />

Hi Hi<br />

lt ©<br />

O 3<br />

03<br />

rt p<br />

H- Hi<br />

P<br />

3 rt<br />

co -r<br />

fD<br />

a m<br />

01 |-H<br />

-T<br />

IS)<br />

O d<br />

3 3<br />

3<br />

rl rf<br />

03 33<br />

a .. fD . H-<br />

oq ro co<br />

ro a<br />

n<br />

H- rt (D<br />

to JfO<br />

_ ro p<br />

a* s<br />

^-M i>- (U<br />

rt rt<br />

o<br />

3)<br />

H-<br />

P<br />

3<br />

ro<br />

3<br />

Oh<br />

ID<br />

fa<br />

00 p.<br />

a- B<br />

00 CO<br />

3*13<br />

P<br />

«S i-J<br />

(D fD<br />

r-1<br />

(D<br />

r- I<br />

VJ


16<br />

The curves of Fig. 3.3 show th<strong>at</strong> the maximum drywell average temper<br />

<strong>at</strong>ure can be kept below 148.9°C (300°F) provided th<strong>at</strong> the oper<strong>at</strong>or takes<br />

action to depressurize within one hour following the loss of drywell cool<br />

ers concomitant with a <strong>St<strong>at</strong>ion</strong> Blackout.* A depressuriz<strong>at</strong>ion <strong>at</strong> the<br />

Technical Specific<strong>at</strong>ions limit of 55.6°C/h (100°F/h) will produce a grad<br />

ual reduction of the drywell ambient temper<strong>at</strong>ure; a rapid depressuriza<br />

tion will produce a faster drywell temper<strong>at</strong>ure reduction, but is probably<br />

not necessary. Certainly, if the oper<strong>at</strong>or perceives developing difficul<br />

ties with the in-drywell equipment such as the relief valve solenoids, he<br />

should convert an ongoing 55.6°C/h (100°F/h) depressuriz<strong>at</strong>ion into a more<br />

rapid one.<br />

Summary. Assuming no independent secondary failures of equipment,<br />

reactor vessel level control and pressure control can be maintained during<br />

a <strong>St<strong>at</strong>ion</strong> Blackout for as long as the DC power supplied by the unit b<strong>at</strong><br />

tery lasts. This is expected to be a period of from four to six hours,<br />

and this portion of the <strong>St<strong>at</strong>ion</strong> Blackout severe accident sequence is<br />

graphically displayed with commentary in Section 7. If AC power is re<br />

gained <strong>at</strong> any time during this period, a completely normal recovery would<br />

follow.<br />

If AC power is not regained, and DC power is lost, remote-manual op<br />

er<strong>at</strong>ion of the primary relief valves would no longer be possible and the<br />

reactor vessel pressure would increase to 7.722 MPa (1105 psig), the low<br />

est setpoint for autom<strong>at</strong>ic actu<strong>at</strong>ion of the relief valves. Thereafter,<br />

the reactor vessel pressure would cycle between 7.722 and 7.377 MPa (1105<br />

and 1055 psig) while the vessel level steadily decreased because injection<br />

capability would be lost as well. The sequence of events following the<br />

loss of injection capability is described in Sections 9 through 11.<br />

*If the backup HPCI system were used for injection, the average re<br />

actor vessel pressure after depressuriz<strong>at</strong>ion would have to be maintained<br />

<strong>at</strong> about 1.14 MPa (150 psig), which corresponds to an average s<strong>at</strong>ur<strong>at</strong>ed<br />

liquid temper<strong>at</strong>ure of 185°C (365°F). This is only 15°C (25°F) higher than<br />

the average temper<strong>at</strong>ure associ<strong>at</strong>ed with RCIC oper<strong>at</strong>ion and would not<br />

significantly increase the drywell temper<strong>at</strong>ures shown in Fig. 3.3.


17<br />

4. COMPUTER MODEL FOR SYSTEM BEHAVIOR<br />

PRIOR TO LOSS OF INJECTION CAPABILITY<br />

The purpose of this chapter is to describe the BWR-LACP (BWR-Loss of<br />

AC Power) computer code th<strong>at</strong> was developed to calcul<strong>at</strong>e the effects of<br />

oper<strong>at</strong>or actions prior to loss of injection capability after <strong>St<strong>at</strong>ion</strong><br />

Blackout. Topics covered include: general fe<strong>at</strong>ures, simplifying assump<br />

tions, solutions to more important modeling problems, and model valid<strong>at</strong>ion<br />

efforts.<br />

BWR-LACP is a digital computer code written specifically to predict<br />

general <strong>Browns</strong> <strong>Ferry</strong> thermal-hydraulic behavior following a <strong>St<strong>at</strong>ion</strong> Black<br />

out event (defined in Sect. 2). The code consists of the differential and<br />

algebraic equ<strong>at</strong>ions of mass and energy conserv<strong>at</strong>ion and equ<strong>at</strong>ions of st<strong>at</strong>e<br />

for the reactor vessel and containment. The code was written in the IBM<br />

CSMP (Continuous System Modeling Program)8 Language to minimize program<br />

ming and debugging time. The listing in Appendix A specifies all required<br />

input parameters.<br />

Some of the important variables calcul<strong>at</strong>ed by the BWR-LACP code in<br />

clude:<br />

1. Reactor vessel levels (above the fuel as well as in the downcomer<br />

annulus),<br />

2. Reactor vessel pressure,<br />

3. Total injected w<strong>at</strong>er volume,<br />

4. Safety-relief valve (SRV) flow r<strong>at</strong>es,<br />

5. Containment pressures and temper<strong>at</strong>ures, and<br />

6. Suppression pool w<strong>at</strong>er level and temper<strong>at</strong>ure.<br />

These variables may be calcul<strong>at</strong>ed for arbitrary time periods follow<br />

ing the loss of AC power — typically several hours. Run specific in<br />

put includes:<br />

1. Injection flow vs time or a law to represent oper<strong>at</strong>or control of re<br />

actor vessel level with injection flow.<br />

2. SRV opening(s) vs time or a law to represent oper<strong>at</strong>or control of re<br />

actor vessel pressure with SRV opening,<br />

3. Initializ<strong>at</strong>ion parameters: initial time elapsed since reactor trip,<br />

initial reactor vessel pressure and level, and initial containment<br />

pressures, temper<strong>at</strong>ures, and suppression pool level.<br />

Specific characteristics of the <strong>St<strong>at</strong>ion</strong> Blackout event allowed sim<br />

plifying assumptions to be made, or required specific assumptions for ade<br />

qu<strong>at</strong>e description of system response. These assumptions are discussed be<br />

low:<br />

1. Reactor trip <strong>at</strong> time zero: he<strong>at</strong> input from the reactor is as<br />

sumed to consist of decay he<strong>at</strong> and is calcul<strong>at</strong>ed from the ANS standard9.<br />

2. No fuel temper<strong>at</strong>ure calcul<strong>at</strong>ion: the fuel remains covered for<br />

transients considered here and 100% of the decay he<strong>at</strong> is assumed to be<br />

transferred directly to w<strong>at</strong>er.


18<br />

3. Density of steam-w<strong>at</strong>er mixture calcul<strong>at</strong>ed by drift-flux correla<br />

tion: the low steaming r<strong>at</strong>e of decay he<strong>at</strong> oper<strong>at</strong>ion requires a model,<br />

such as the drift-flux model10 th<strong>at</strong> can allow rel<strong>at</strong>ive slip between<br />

steam and w<strong>at</strong>er.<br />

4. Phase separ<strong>at</strong>ion is likely in the standpipes: the low steaming<br />

r<strong>at</strong>es of decay he<strong>at</strong> oper<strong>at</strong>ion allow phase separ<strong>at</strong>ion to occur11 if the<br />

2-phase level is below the steam separ<strong>at</strong>ors (in standpipes or core outlet<br />

plenum).<br />

5. Recircul<strong>at</strong>ion pumps trip <strong>at</strong> time zero: these pumps require AC<br />

power for oper<strong>at</strong>ion. During the loss of AC power transients, the w<strong>at</strong>er in<br />

the recircul<strong>at</strong>ion piping is tre<strong>at</strong>ed as an inactive volume.<br />

6. Steam flow through the SRV's is calcul<strong>at</strong>ed by r<strong>at</strong>ioing the flc Low<br />

<strong>at</strong> r<strong>at</strong>ed conditions:<br />

where,<br />

W =Wr ^(pP)/(pr Pr)<br />

Wr = r<strong>at</strong>ed SRV flow <strong>at</strong> pressure Pr and density pr<br />

W = SRV flow <strong>at</strong> pressure, P, and density p.<br />

This rel<strong>at</strong>ionship is rigorously true for choked flow of an ideal gas with<br />

constant Cp/Cv r<strong>at</strong>io12 and should give reasonable results for choked<br />

flow of dry steam.<br />

7. A realistic estim<strong>at</strong>e of SRV relieving capacity is calcul<strong>at</strong>ed by<br />

taking into account the ASME code rule which requires nominal valve flow<br />

to be only 90% of the flow measured <strong>at</strong> 103% of the nominal actu<strong>at</strong>ion pres<br />

sure. For the two-stage Target Rock SRV's <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong>, the resulting<br />

estim<strong>at</strong>e of actual valve capacity is:<br />

Wr = 121.2 kg/s @ 7.79 MPa<br />

(= 960,000 lb/h @ 1115.0 psig).<br />

8. Steam flowing to RCIC and HPCI turbines is calcul<strong>at</strong>ed by r<strong>at</strong>io<br />

ing the steam flowing <strong>at</strong> r<strong>at</strong>ed conditions;<br />

where,<br />

W = Wr*(P/Pr)*(AHr/AH)<br />

Wr = turbine flow required <strong>at</strong> conditions Pr and Allr<br />

(available enthalpy difference for isentropic expansion<br />

between Pr and Pexhaust) Lo PumP r<strong>at</strong>ed injection flow.<br />

W = turbine flow required <strong>at</strong> conditions P and AH (isen<br />

tropic expansion between P and Pexhaust) to PumP the same<br />

(r<strong>at</strong>ed) injection flow.


19<br />

This equ<strong>at</strong>ion predicts a. linear rel<strong>at</strong>ionship between steam pressure and<br />

turbine flow providing steam pressure is high enough to establish choked<br />

flow across the turbine nozzles. Turbine steam flow is zeroed when the<br />

turbine is tripped.<br />

Several modeling problems had to be solved in order to adequ<strong>at</strong>ely<br />

simul<strong>at</strong>e behavior of the system following loss of AC power:<br />

1. Reactor vessel steaming r<strong>at</strong>e,<br />

2. Reactor vessel n<strong>at</strong>ural circul<strong>at</strong>ion flow,<br />

3. Suppression pool w<strong>at</strong>er temper<strong>at</strong>ure(s), and<br />

4. Drywell air temper<strong>at</strong>ure.<br />

These particular problems are highlighted because of their importance in<br />

determining the overall results and to point out approxim<strong>at</strong>ions th<strong>at</strong> were<br />

made in formul<strong>at</strong>ing the solutions.<br />

Reactor vessel steaming r<strong>at</strong>e is defined here as the r<strong>at</strong>e <strong>at</strong> which<br />

steam flows from the liquid regions in the reactor vessel into the steam<br />

volume in the upper part of the vessel. When pressure is constant the<br />

steaming r<strong>at</strong>e equals steam production r<strong>at</strong>e in the reactor core which is a<br />

function of core inlet enthalpy, flow, and pressure. However, when pres<br />

sure is changing, the steaming r<strong>at</strong>e is influenced by the significant<br />

amount of w<strong>at</strong>er th<strong>at</strong> normally exists in the steam-w<strong>at</strong>er mixture above the<br />

core in the core outlet plenum, standpipes and steam separ<strong>at</strong>ors. This<br />

w<strong>at</strong>er adds to the steaming r<strong>at</strong>e when pressure is decreasing by flashing.<br />

It is assumed to subtract from the steaming r<strong>at</strong>e when pressure is increas<br />

ing by condensing part of the core steam production. In modeling this ef<br />

fect, it was assumed th<strong>at</strong> this w<strong>at</strong>er remains <strong>at</strong> s<strong>at</strong>ur<strong>at</strong>ion <strong>at</strong> all times.<br />

The net effect on the steaming r<strong>at</strong>e was calcul<strong>at</strong>ed using the following re<br />

l<strong>at</strong>ionship:<br />

where<br />

dP dhf lf M,<br />

w<br />

Wn = Wc - —- *<br />

dt dP (hK - hf)<br />

Wn = net steam production r<strong>at</strong>e<br />

Wc = core steam production r<strong>at</strong>e<br />

P = reactor vessel pressure<br />

hf = s<strong>at</strong>ur<strong>at</strong>ed fluid enthalpy<br />

hg = s<strong>at</strong>ur<strong>at</strong>ed vapor enthalpy<br />

Mj, = mass of w<strong>at</strong>er in core boiling region and above the core in<br />

outlet plenum, standpipes, and steam separ<strong>at</strong>ors.<br />

The inherent n<strong>at</strong>ural circul<strong>at</strong>ion capability of BWRs is an important<br />

fe<strong>at</strong>ure th<strong>at</strong> should be considered even in calcul<strong>at</strong>ion of thermal-hydraulic<br />

transients <strong>at</strong> decay he<strong>at</strong> level. The n<strong>at</strong>ural circul<strong>at</strong>ion flow p<strong>at</strong>h is from<br />

the area outside the standpipes and steam separ<strong>at</strong>ors (referred to here as<br />

the downcomer annulus), down through the jet pump diffusers into the lower<br />

plenum and then into the reactor. As it flows up through the core the<br />

fluid becomes s<strong>at</strong>ur<strong>at</strong>ed and begins to boil. The steam/w<strong>at</strong>er mixture flows<br />

up through the outlet plenum and standpipes to the steam separ<strong>at</strong>ors, where<br />

the w<strong>at</strong>er is returned to the downcomer annulus and the steam flows through


20<br />

the steam dryers to the steam dome. The n<strong>at</strong>ural circul<strong>at</strong>ion r<strong>at</strong>e is de<br />

pendent on a number of variables including: w<strong>at</strong>er level in the downcomer<br />

annulus, w<strong>at</strong>er-steam level above the core, core steaming r<strong>at</strong>e, and density<br />

of the w<strong>at</strong>er-steam mixture in and above the core. <strong>One</strong> phenomenon th<strong>at</strong><br />

makes the calcul<strong>at</strong>ion more difficult is th<strong>at</strong> when w<strong>at</strong>er level gets low<br />

enough the recircul<strong>at</strong>ion of w<strong>at</strong>er from the steam separ<strong>at</strong>ors ceases and<br />

w<strong>at</strong>er flows from the downcomer annulus only as required to counter-balance<br />

w<strong>at</strong>er lost by boil-off from the core.<br />

The equ<strong>at</strong>ion used to calcul<strong>at</strong>e core inlet flow is:<br />

where<br />

KfWci2 = Pdc*Ldc - Ptp * Ltp<br />

Kf = empirically determined friction coefficient<br />

wci = core inlet tiow<br />

Pdc = downcomer w<strong>at</strong>er density<br />

Ldc = downcomer w<strong>at</strong>er level (ref. to zero <strong>at</strong> bottom of active<br />

fuel)<br />

Jt = elev<strong>at</strong>ion-averaged density of w<strong>at</strong>er-steam mixture in and<br />

above core<br />

LtD = level of steam-w<strong>at</strong>er mixture above bottom of active fuel.<br />

The value of the friction coefficient, Kf, was calcul<strong>at</strong>ed from the<br />

n<strong>at</strong>ural circul<strong>at</strong>ion curve on Fig. 3.7-1 of the BFNP FSAR by forcing agree<br />

ment with the predictions of this equ<strong>at</strong>ion <strong>at</strong> the 30% thermal power point.<br />

This procedure resulted in a reasonably good approxim<strong>at</strong>ion of the flow <strong>at</strong><br />

other points, as shown on Fig. 4.1. _<br />

The r<strong>at</strong>e of recircul<strong>at</strong>ion of w<strong>at</strong>er back to the downcomer annulus is<br />

calcul<strong>at</strong>ed as a function of the w<strong>at</strong>er-steam mixture level in the steam<br />

separ<strong>at</strong>ors:<br />

where<br />

wrecir = * f


100<br />

90<br />

£ 80<br />

o<br />

Q- 70<br />

<<br />

2<br />


22<br />

proportional to the difference between reactor coolant temper<strong>at</strong>ure (Trc)<br />

and drywell <strong>at</strong>mosphere temper<strong>at</strong>ure (Tdw). Therefore,<br />

Qdw " 980*(Trc - Tdw)/(Trc - Tdw)0 .<br />

To test the validity of the 980 kW he<strong>at</strong> load, an independent calcu<br />

l<strong>at</strong>ion was performed under the following assumptions:<br />

1. Total he<strong>at</strong>ed surface area is 1115 m**2 (12,000 sq ft). This includes<br />

539 m**2 (5800 sq ft) for the reactor vessel, 372 m**2 (4000 sq ft)<br />

for the steam lines, and 204 m**2 (2200 sq ft) for other he<strong>at</strong>ed pip<br />

ing inside the drywell.<br />

2. 90% of the he<strong>at</strong>ed surface is insul<strong>at</strong>ed. This is a rough estim<strong>at</strong>e to<br />

account both for uninsul<strong>at</strong>ed piping and for imperfectly installed<br />

insul<strong>at</strong>ion.<br />

3. Total he<strong>at</strong> loss through insul<strong>at</strong>ed surfaces is 0.25 kW/m**2 (80 Btu/h<br />

sq ft). This is a good nominal estim<strong>at</strong>e for MIRROR insul<strong>at</strong>ion when<br />

total hot surface to ambient temper<strong>at</strong>ure difference is about 220°C<br />

(400°F).<br />

4. Radiant he<strong>at</strong> loss from uninsul<strong>at</strong>ed surface is figured using emmissivity<br />

=0.8 (i.e., unpolished surface)<br />

5. Convective he<strong>at</strong> loss from uninsul<strong>at</strong>ed surface figured using the rela<br />

tion Nu = 0.13 (Gr*Pr)**0.3333 (as discussed in a following para<br />

graph).<br />

The results were as follows:<br />

Qins,total " 281 kW<br />

Qunins,convective = 170 kW<br />

Qunins,radiant = 375 kW<br />

Qtotal - 826 kW<br />

This shows th<strong>at</strong> the he<strong>at</strong> losses assumed here for <strong>Unit</strong> 1 are realistic and<br />

perhaps slightly conserv<strong>at</strong>ive. The <strong>St<strong>at</strong>ion</strong> Blackout analysis presented in<br />

the <strong>Browns</strong> <strong>Ferry</strong> FSAR (response to AEC Question 14.2) assumes a much more<br />

conserv<strong>at</strong>ive he<strong>at</strong> loss of 2000 kW.<br />

In addition to he<strong>at</strong> transfer from hot surfaces, the r<strong>at</strong>e of steam es<br />

caping directly to the drywell must be known in order to calcul<strong>at</strong>e drywell<br />

pressure and temper<strong>at</strong>ure. Figure 9.2-2 of the <strong>Browns</strong> <strong>Ferry</strong> FSAR<br />

specifies a total drywell drain sump input during normal power oper<strong>at</strong>ion<br />

of 22 m**3 (5800 gallons) per day or 4 gpm as measured <strong>at</strong> the normal sump<br />

temper<strong>at</strong>ure of about 38°C (100°F). Recircul<strong>at</strong>ion pump seals and control<br />

rod drive flange seals are identified as the major source of this leakage.<br />

This 4 gpm leak r<strong>at</strong>e is believed to be realistic for <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1<br />

during a <strong>St<strong>at</strong>ion</strong> Blackout. The fraction of the leak th<strong>at</strong> flashes to steam<br />

was calcul<strong>at</strong>ed in terms of s<strong>at</strong>ur<strong>at</strong>ion properties:<br />

Xflash -


23<br />

<strong>at</strong>mosphere, to cold surfaces (such as the drywell liner). Such n<strong>at</strong>ural<br />

circul<strong>at</strong>ion probably exists in the lower part of the drywell where the<br />

main steam isol<strong>at</strong>ion valves and drywell coolers are loc<strong>at</strong>ed. However it<br />

is likely th<strong>at</strong> temper<strong>at</strong>ures in certain areas near the top of the drywell<br />

could be much hotter than the single <strong>at</strong>mosphere temper<strong>at</strong>ure this model<br />

calcul<strong>at</strong>es.<br />

He<strong>at</strong> transfer between drywell <strong>at</strong>mosphere and liner was calcul<strong>at</strong>ed<br />

using the rel<strong>at</strong>ion<br />

where<br />

Nu = 0.13*(Gr*Pr)**0.333<br />

Nu = Nusselt Number (hL/k)<br />

Gr = Grashof Number (p2ggL3AT/p:,d)<br />

Pr = Prandtl Number (u C /K) .<br />

This formula is also used for the same purpose in the MARCH and CONTEMPT-<br />

LT codes.13>1H<br />

Internal he<strong>at</strong> transfer resistance of the steel drywell liner is low<br />

rel<strong>at</strong>ive to the resistance between liner and the <strong>at</strong>mosphere. This allows<br />

the use of one temper<strong>at</strong>ure to represent the whole thickness and it also<br />

means th<strong>at</strong> the entire ~364,000 kg (800,000 lbs) of drywell metal is ef<br />

fectively available as a he<strong>at</strong> sink during drywell he<strong>at</strong>-up. The he<strong>at</strong> sink<br />

effect of the drywell liner is important because without this he<strong>at</strong> sink<br />

the drywell <strong>at</strong>mosphere would very quickly approach primary coolant tem<br />

per<strong>at</strong>ure after loss of the drywell coolers.<br />

Various code comparison activities were pursued in order to test the<br />

validity of the BWR-LACP simul<strong>at</strong>ion:<br />

1. Comparisons of BWR-LACP results to calcul<strong>at</strong>ions reported in the FSAR.<br />

2. Comparison to results computed by the RELAP-IV computer code.<br />

The first FSAR comparison was the "Loss of Auxiliary Power — All<br />

Grid Connections" transient reported on Figs. 14.5—12 and 14.5—13<br />

of the BFNP FSAR. Plant conditions assumed by the FSAR analysis include:<br />

1. Loss of all external grid connections <strong>at</strong> time = 0.<br />

2. All pumps tripped <strong>at</strong> time = 0.<br />

3. Reactor trip and main steam isol<strong>at</strong>ion <strong>at</strong> about time = 2 s.<br />

The BWR-LACP calcul<strong>at</strong>ion was started <strong>at</strong> time equals 20 s with reactor<br />

vessel level and pressure equal to those shown for t = 20 s on FSAR Figs.<br />

14.5-12 and 14.5-13. Figure 4.2 compares the code and FSAR<br />

predictions of reactor vessel pressure and core inlet flow between 20 and<br />

50 s. During this period the core inlet flow is decreasing because steam<br />

production is falling off rapidly; reactor vessel pressure is being con<br />

trolled between the assumed 7.59 MPa (1100 psia) and 7.41 (1075 psia) SRV<br />

set and reset points. Results are reasonably close. Figure 4.3 shows<br />

BWR-LACP and FSAR calcul<strong>at</strong>ions of reactor vessel level from 20 to 2200 s.<br />

During this period, the vessel level decreases slowly until the mass addi<br />

tion r<strong>at</strong>e of the 0.0378 m**3/s (600 gpm) injection flow exceeds the mass<br />

loss r<strong>at</strong>e due to steam produced by decay he<strong>at</strong>. The results show similar<br />

behavior. The FSAR minimum level is 11.76 m (463 in.) <strong>at</strong> time equals 1600<br />

s and the BWR-LACP predicted minimum level is 11.56 m (455 in.) <strong>at</strong> time<br />

equals 1200 s.


(MPa) (psi)<br />

100<br />

UJ<br />

O<br />

< 0.6 i-<br />

X<br />

o<br />

_ 75<br />

g 0.5<br />

Z3<br />

$ 0.4<br />

rr<br />

a. 50<br />

w 0.3<br />

00<br />

CO<br />

UJ<br />

> 0.2<br />

rr 25<br />

O<br />

o 0.1<br />

<<br />

UJ<br />

rr<br />

0L 0<br />

5 50<br />

O<br />

UJ<br />

CURVE A<br />

CURVE B<br />

L<br />

24<br />

ORNL-DWG 81-8605 ETD<br />

TAKEN DIRECTLY FROM FSAR<br />

FIGURE 14.5-12<br />

BWR-LACP RESULTS USING FSAR<br />

INPUT ASSUMPTIONS<br />

TAKEN DIRECTLY FROM FSAR FIGURE 14.5-12<br />

BWR-LACP RESULTS USING FSAR INPUT<br />

ASSUMPTIONS<br />

TIME (s)<br />

Fig. 4.2 Comparison of FSAR and BWR-LACP results for loss of<br />

auxiliary power transients.<br />

±<br />

50


00<br />

00<br />

(m)<br />

14<br />

13<br />

><br />

z 12<br />

I"<br />

LU 10<br />

> UJ<br />

(in.)<br />

570<br />

520<br />

470<br />

420<br />

370<br />

320<br />

I I |llll|—| I I Mill —<br />

LEVEL REFERENCED TO BOTTOM OF VESSEL<br />

DIRECTLY FROM FSAR<br />

FIGURE 14.5-13<br />

O CALCULATED BY BWR-LACP<br />

USING FSAR INPUT<br />

TOP OF ACTIVE FUEL<br />

ORNL-DWG 81-7858 ETD<br />

| I I |llll| 1 I I | Mil<br />

I I I I Mill I I I I Mill I I I I Mill I I I I INI<br />

10 5 100 2<br />

TIME (s)<br />

1000 2<br />

Fig. 4.3 Comparison of FSAR and BWR-LACP results for reactor<br />

vessel level.<br />

5 10,000<br />

ro


26<br />

Comparison of FSAR and BWR-LACP calcul<strong>at</strong>ions of drywell temper<strong>at</strong>ure<br />

was performed for the "Loss of All AC Power" results shown on Fig.<br />

Q.14.2-1 of the BFNP FSAR. Plant conditions assumed by the FSAR calcula<br />

tions include:<br />

1. Initial power = 100%.<br />

2. Loss of all AC power <strong>at</strong> time = 0.<br />

3. Drywell perfectly insul<strong>at</strong>ed on outside.<br />

4. He<strong>at</strong> capacity of interior equipment and structures is negligible.<br />

5. Energy input from primary surfaces is initially 2000 kW.<br />

6. He<strong>at</strong> transfer coefficient between <strong>at</strong>mosphere and wall is 11.36<br />

w/m**2°C (2 Btu/h ft2 °F) without steam condens<strong>at</strong>ion.<br />

7. Drywell coolers lost <strong>at</strong> time = 0 and not restarted.<br />

8. Steam leak = 0<br />

The conditions assumed for this analysis are of the same order as those<br />

assumed for the "Normal Recovery" part of the <strong>St<strong>at</strong>ion</strong> Blackout as dis<br />

cussed in this report. Comparisons of various predictions of drywell<br />

<strong>at</strong>mosphere temper<strong>at</strong>ure to the FSAR result are shown on Fig. 4.4. The drywell<br />

temper<strong>at</strong>ure climbs rapidly during the first 5 to 10 min, before he<strong>at</strong><br />


27<br />

transfer to the drywell liner is established. After the first 10 min, the<br />

temper<strong>at</strong>ure climbs much more slowly, with the metal liner acting as the<br />

he<strong>at</strong> sink. Curve 2 on Fig. 4.4 was calcul<strong>at</strong>ed using as input to the con<br />

tainment model the FSAR assumptions as listed above. The resulting curve<br />

is similarly shaped, but about 17°C (30°F) above the FSAR prediction. In<br />

order to estim<strong>at</strong>e the possible magnitude of input parameter difference,<br />

the calcul<strong>at</strong>ion was repe<strong>at</strong>ed with identical input except a 40% increase in<br />

drywell liner area. Results are shown on Curve 3 and are very close to<br />

the FSAR prediction.<br />

A boil-off transient was selected for comparison to RELAP-IV and<br />

BWR-LACP predictions. The RELAP-IV calcul<strong>at</strong>ion was prepared and run by<br />

Idaho N<strong>at</strong>ional Engineering Labor<strong>at</strong>ory. It starts <strong>at</strong> nominal full power<br />

plant conditions. During the first several seconds the reactor trips and<br />

the main steam isol<strong>at</strong>ion valves close. Initially, several SRVs are re<br />

quired to control vessel pressure, but after about 40 seconds one SRV is<br />

sufficient. Injection flow is zero throughout. The BWR-LACP calcul<strong>at</strong>ion<br />

was intialized <strong>at</strong> 30 seconds because it is programmed only for decay he<strong>at</strong><br />

oper<strong>at</strong>ion. Figure 4.5 compares the results of the calcul<strong>at</strong>ions of reactor<br />

><br />

ui<br />

(m) (in.)<br />

15 i—<br />

14<br />

13<br />

12<br />

11<br />

_i<br />

Ui<br />

OJ<br />

CO<br />

UI<br />

> 10<br />

600<br />

— 550<br />

500<br />

450<br />

400<br />

350<br />

300<br />

250<br />

500<br />

BWR-LACP<br />

O RELAP-IV RESULTS<br />

1000 1500<br />

TIME (s)<br />

ORNL-DWG 81-7859 ETD<br />

STEAM/WATER ABOVE CORE<br />

2000 2500<br />

Fig. 4.5 Comparison of RELAP-IV and BWR-LACP results for reactor<br />

vessel level.


28<br />

vessel level. The steam/w<strong>at</strong>er level above the core is shown for both<br />

codes. Results are very similar, with RELAP predicting 33 minutes and<br />

BWR-LACP predicting 30 minutes to begin uncovering active fuel. Figure<br />

4.6 shows RELAP and BWR-LACP results for reactor steam pressure control.<br />

Results are similar although RELAP predicts a longer SRV cycle (about 60<br />

seconds) than BWR-LACP (about 38 seconds).<br />

Results presented in this Section show th<strong>at</strong> the BWR-LACP code is cap<br />

able of providing reasonable predictions of overall thermal-hydraulic<br />

UJ<br />


29<br />

variables such as reactor vessel levels and pressure and containment tem<br />

per<strong>at</strong>ure for extended periods after reactor trip prior to system damage<br />

due to loss of injection capability. Fe<strong>at</strong>ures of the code th<strong>at</strong> have con<br />

tributed to its utility in the analysis of the Normal Recovery portion of<br />

<strong>St<strong>at</strong>ion</strong> Blackout include:<br />

1. The code is specifically designed for BWRs; therefore, parameter<br />

changes are straightforward and easily made.<br />

2. The code is designed for flexibility to model the plant response to<br />

different oper<strong>at</strong>or actions.<br />

3. It is locally available and has quick turnaround time.


30<br />

5. INSTRUMENTATION AVAILABLE DURING STATION BLACKOUT<br />

AND NORMAL RECOVERY<br />

For some time following a <strong>St<strong>at</strong>ion</strong> Blackout, the reactor vessel w<strong>at</strong>er<br />

level can be maintained in the normal range by oper<strong>at</strong>ion of the HPCI and/<br />

or RCIC systems, and the pressure can be maintained in any desired range<br />

by remote-manual relief valve oper<strong>at</strong>ion. Restor<strong>at</strong>ion of AC power <strong>at</strong> any<br />

time during this period of stable level and pressure control would permit<br />

complete and normal recovery without core damage. The Control Room in<br />

strument<strong>at</strong>ion available and necessary to monitor the plant st<strong>at</strong>us during<br />

the period of stable control following the inception of a <strong>St<strong>at</strong>ion</strong> Blackout<br />

is discussed in the following paragraphs.<br />

1. Electrical system st<strong>at</strong>us. The <strong>St<strong>at</strong>ion</strong> Blackout would be clearly<br />

discernible by the loss of much of the control room indic<strong>at</strong>ion and the<br />

loss of normal Control Room lighting. Emergency Control Room lighting is<br />

available. Numerous instruments would indic<strong>at</strong>e the loss of voltage, am<br />

perage, and frequency on the electrical supply and distribution boards.<br />

2. Reactor vessel w<strong>at</strong>er level. Two channels of Control Room instru<br />

ment<strong>at</strong>ion would provide indic<strong>at</strong>ion of the reactor vessel w<strong>at</strong>er level over<br />

a range between 13.41 and 14.94 m (528 and 588 in.) above the bottom of<br />

the vessel. This range includes the normal oper<strong>at</strong>ing level of 14.15 m<br />

(561 in.) and extends over the upper portion of the steam separ<strong>at</strong>ors, a<br />

distance of 4.27 to 5.79 m (14 to 19 ft) above the top of the active fuel.<br />

Mechanical Yarway indic<strong>at</strong>ion available outside of the Control Room would<br />

provide an additional range from the low point of the Control Room indica<br />

tion, 13.41 m (528 in.) above vessel zero down to a point 9.47 m (373 in.)<br />

above vessel zero, which is 0.33 m (13 in.) above the top of the active<br />

fuel in the core.<br />

The level instrument<strong>at</strong>ion derives the reactor w<strong>at</strong>er level by compar<br />

ing the head of w<strong>at</strong>er within the downcomer region of the reactor vessel to<br />

the head of w<strong>at</strong>er within a reference leg installed in the drywell. With<br />

the loss of the drywell coolers, the drywell ambient temper<strong>at</strong>ure will in<br />

crease significantly, he<strong>at</strong>ing the reference leg w<strong>at</strong>er to above-normal tem<br />

per<strong>at</strong>ures. This will reduce the density of the w<strong>at</strong>er in the reference<br />

leg, causing an error in the indic<strong>at</strong>ed w<strong>at</strong>er level, which will be too<br />

high. For example, if the drywell ambient temper<strong>at</strong>ure increases from its<br />

normal range of 57.2 to 63.6°C (135 to 150°F) to 171.1°C (340°F), the in<br />

dic<strong>at</strong>ed level can be as much as 0.76 m (30 in.) too high.15 As dis<br />

cussed in Sect. 3, the drywell ambient temper<strong>at</strong>ure is expected to reach<br />

about 148.9°C (300°F). However, the lower boundary of reactor vessel<br />

level indic<strong>at</strong>ion is 4.27 m (168 in.) above the top of the active fuel.<br />

Therefore, if the oper<strong>at</strong>or maintains the level in the indic<strong>at</strong>ing range, a<br />

0.76 m (30 in.) error is not significant as far as the goal of keeping the<br />

core covered is concerned.<br />

3. Reactor vessel pressure. Two channels of pressure instrumenta<br />

tion would provide indic<strong>at</strong>ion of reactor vessel pressure over a range of<br />

8.274 MPa (0 to 1200 psig).<br />

4. Main steamline flow. Two channels of steam flow instrument<strong>at</strong>ion<br />

with a range of 2016 kg/s (0 to 16 x 106 lbs/h) would provide verifica<br />

tion th<strong>at</strong> steam flow had ceased following Main Steam Isol<strong>at</strong>ion Valve<br />

(MSIV) closure.


31<br />

5. Feedw<strong>at</strong>er flow. <strong>One</strong> channel of flow instrument<strong>at</strong>ion with a range<br />

of 1008 kg/s (0 to 8 x 106 lbs/h) for each of the three feedw<strong>at</strong>er pumps<br />

would indic<strong>at</strong>e the decay of feedw<strong>at</strong>er flow following loss of steam to the<br />

feedw<strong>at</strong>er turbines.<br />

6. Neutron flux. The power range meters fail on loss of AC power.<br />

The source range and intermedi<strong>at</strong>e range monitors remain oper<strong>at</strong>ional, but<br />

the detectors for these systems are withdrawn from the reactor core during<br />

power oper<strong>at</strong>ion and could not be reinserted under <strong>St<strong>at</strong>ion</strong> Blackout condi<br />

tions. Nevertheless, the oper<strong>at</strong>or could verify the reactor scram which<br />

occurs when the <strong>St<strong>at</strong>ion</strong> Blackout is initi<strong>at</strong>ed by observing the decay of<br />

the indic<strong>at</strong>ed levels on these monitors.<br />

7. Control rod position indic<strong>at</strong>ion. The control rod position indi<br />

c<strong>at</strong>ion system remains oper<strong>at</strong>ional so th<strong>at</strong> the oper<strong>at</strong>or could verify th<strong>at</strong><br />

the control rods had inserted with the scram.<br />

8. Relief valve position. There is no provision for direct indica<br />

tion of the actual position of any primary relief valve, even under normal<br />

oper<strong>at</strong>ing conditions. Thus the oper<strong>at</strong>or has no indic<strong>at</strong>ion of autom<strong>at</strong>ic<br />

actu<strong>at</strong>ion of a specific relief valve other than the recorded tailpipe tem<br />

per<strong>at</strong>ures available on charts behind the control room panels, or the re<br />

lief valve acoustic monitors, all of which would be inoperable under Sta<br />

tion Blackout conditions. However, remote-manual actu<strong>at</strong>ion of a relief<br />

valve is accomplished by energizing its DC solenoid oper<strong>at</strong>or; lights on<br />

the control panel for each valve indic<strong>at</strong>e whether or not these solenoids<br />

are energized, and this capability is maintained during <strong>St<strong>at</strong>ion</strong> Blackout.<br />

9. RCIC instrument<strong>at</strong>ion and controls. The RCIC system can be oper<br />

<strong>at</strong>ed and monitored under <strong>St<strong>at</strong>ion</strong> Blackout conditions.<br />

10. HPCI instrument<strong>at</strong>ion and controls. The HPCI system can be oper<br />

<strong>at</strong>ed and monitored under <strong>St<strong>at</strong>ion</strong> Blackout conditions.<br />

11. Condens<strong>at</strong>e Storage Tank Level. The condens<strong>at</strong>e storage tank<br />

level indic<strong>at</strong>ion [range: 9.75 m (0 to 32 ft)] remains oper<strong>at</strong>ional so th<strong>at</strong><br />

the oper<strong>at</strong>or can determine the remaining amount of w<strong>at</strong>er available for re<br />

actor vessel injection via the RCIC (or HPCI) system.<br />

12. Drywell Pressure. Drywell pressure instrument<strong>at</strong>ion [range:<br />

0.55 MPa (0 to 80 psia)] remains oper<strong>at</strong>ional so th<strong>at</strong> the oper<strong>at</strong>or can mon<br />

itor the increase in drywell pressure due to the ambient temper<strong>at</strong>ure in<br />

crease following loss of the drywell coolers.<br />

13. Pressure Suppression Pool W<strong>at</strong>er Level. Indic<strong>at</strong>ion of torus<br />

level [range: —0.63 to 0.63 m (—25 to +25 in.)] remains available allow<br />

ing the oper<strong>at</strong>or to monitor the increasing pool level caused by both the<br />

relief valve blowdowns and the increasing pool temper<strong>at</strong>ure.<br />

The above instrument<strong>at</strong>ion is powered during <strong>St<strong>at</strong>ion</strong> Blackout either<br />

by DC power directly from the installed b<strong>at</strong>teries or by AC power indi<br />

rectly obtained from the b<strong>at</strong>tery systems. The sources of AC power during<br />

<strong>St<strong>at</strong>ion</strong> Blackout are the feedw<strong>at</strong>er inverter and the unit-preferred and<br />

plant-preferred systems where single-phase 120V AC power is provided by<br />

gener<strong>at</strong>ors driven by emergency b<strong>at</strong>tery-powered DC motors.<br />

It is important to note th<strong>at</strong> Control Room temper<strong>at</strong>ure instrument<strong>at</strong>ion<br />

for the drywell and the pressure suppression pool does not remain opera<br />

tional under <strong>St<strong>at</strong>ion</strong> Blackout conditions. However, the ambient tempera<br />

tures <strong>at</strong> various points in the drywell would be available <strong>at</strong> an indic<strong>at</strong>ormeter<br />

and a recorder mounted on panel 9-47, which is loc<strong>at</strong>ed on the back<br />

of the Control Room panels and is accessible from outside of the Control


32<br />

Room. Also, Using a portable self-powered potentiometer, st<strong>at</strong>ion person<br />

nel can monitor local pressure suppression chamber and drywell tempera<br />

tures which are sensed by installed thermocouple elements.<br />

Following the restor<strong>at</strong>ion of normal AC power, either by recovery of<br />

the offsite power sources or by the delayed but finally successful loading<br />

of the onsite diesel-gener<strong>at</strong>ors, the Instrument<strong>at</strong>ion and Control buses<br />

would be re-energized, restoring all normal Control Room instrument<strong>at</strong>ion<br />

for use in monitoring the normal recovery.


33<br />

6. OPERATOR ACTIONS DURING STATION BLACKOUT<br />

AND NORMAL RECOVERY<br />

In the event of a <strong>St<strong>at</strong>ion</strong> Blackout, the immedi<strong>at</strong>e result would be a<br />

turbine trip, reactor scram, and Main Steam Isol<strong>at</strong>ion Valve (MSIV) clo<br />

sure, which would all occur autom<strong>at</strong>ically with no oper<strong>at</strong>or action; the re<br />

actor would be shut down and isol<strong>at</strong>ed behind the closed MSIVs within 30<br />

seconds following the initi<strong>at</strong>ing loss of offsite power. Immedi<strong>at</strong>ely fol<br />

lowing the isol<strong>at</strong>ion, the reactor vessel pressure would increase to the<br />

setpoints of as many relief valves as are required to termin<strong>at</strong>e the pres<br />

sure increase. The affected relief valves would open to pass steam di<br />

rectly from the reactor vessel to a terminus bene<strong>at</strong>h the w<strong>at</strong>er level in<br />

the pressure suppression pool so th<strong>at</strong> the released steam is condensed.<br />

The core w<strong>at</strong>er void collapse caused by both the scram and the pres<br />

sure increase following MSIV closure would result in a rapid drop in re<br />

actor vessel w<strong>at</strong>er level to some point below the lower limit of level in<br />

dic<strong>at</strong>ion available in the Control Room under <strong>St<strong>at</strong>ion</strong> Blackout conditions<br />

[13.41 m (528 in.) above vessel zero]. Standard <strong>Browns</strong> <strong>Ferry</strong> Emergency<br />

Oper<strong>at</strong>ing Instructions for immedi<strong>at</strong>e action following reactor scram and<br />

MSIV closure call for the oper<strong>at</strong>or to manually initi<strong>at</strong>e both the HPCI and<br />

the RCIC systems. The combined injection flow of 0.353 m3/s (5600 GPM)<br />

would rapidly restore the level into the indic<strong>at</strong>ing range and the oper<strong>at</strong>or<br />

would secure the HPCI system when the indic<strong>at</strong>ed level reached a point<br />

equivalent to about 13.72 m (540 in.) above vessel zero. The level would<br />

then continue to increase due to the remaining 0.038 m /s (600 GPM) of<br />

RCIC system flow and the he<strong>at</strong>up and expansion of the injected w<strong>at</strong>er, but<br />

<strong>at</strong> a slower r<strong>at</strong>e.<br />

For pressure control, standard procedure is for the oper<strong>at</strong>or to<br />

remote-manually oper<strong>at</strong>e the primary relief valves as necessary to cycle<br />

the reactor vessel pressure between 7.69 and 6.31 MPa (1100 and 900 psig).<br />

This prevents the autom<strong>at</strong>ic actu<strong>at</strong>ion of the relief valves [lowest setpoint:<br />

7.72 MPa (1105 psig)], and since the pressure reduction following<br />

autom<strong>at</strong>ic actu<strong>at</strong>ion is only 0.34 MPa (50 psi), gre<strong>at</strong>ly reduces the total<br />

number of relief valve actu<strong>at</strong>ions. The purpose is to decrease the oppor<br />

tunity for a relief valve to stick open, and to allow the oper<strong>at</strong>or to al<br />

tern<strong>at</strong>e the relief valves which are in effect passing the decay he<strong>at</strong><br />

energy to the pressure suppression pool; this more evenly distributes the<br />

pool he<strong>at</strong>up.<br />

Throughout the period of <strong>St<strong>at</strong>ion</strong> Blackout, the oper<strong>at</strong>or would oper<strong>at</strong>e<br />

the RCIC system intermittently as necessary to maintain the reactor vessel<br />

level in the indic<strong>at</strong>ing range, i.e., between 13.41 and 14.94 m (528 and<br />

588 in.) above vessel zero. Thus, it is expected th<strong>at</strong> the oper<strong>at</strong>or would<br />

turn on the RCIC system <strong>at</strong> an indic<strong>at</strong>ed level of about 13.61 m (538 in.)<br />

and turn the system off <strong>at</strong> about 14.68 m (578 in.). The periods of RCIC<br />

system oper<strong>at</strong>ion would become less frequent as the decay he<strong>at</strong> intensity<br />

subsides during a prolonged <strong>St<strong>at</strong>ion</strong> Blackout; after the first hour, the<br />

oper<strong>at</strong>or would find it necessary to run the RCIC system for only about<br />

one-third of the time. This is illustr<strong>at</strong>ed in Sect. 7.<br />

As previously discussed, the oper<strong>at</strong>or would control reactor vessel<br />

pressure by remote-manual oper<strong>at</strong>ion of the relief valves. It is important<br />

th<strong>at</strong> the oper<strong>at</strong>or take action to begin to lower the reactor vessel pres<br />

sure to about 0.79 MPa (100 psig) within 60 min following the inception of


CO O* cr o Cu CO CO H- cr 3" rt CO "3 VO g o rt rt CO CO rt £ rt o rt TJ rt H- Oh rt CO ~J co Hi rt Oh N rt H- Ul CO X-N rt ii O CU<br />

n> c fD *< *o pJ fD pJ 3 fD cu ZT V! ro u> fD o 3d H- 3 rt l-l H- H- Hi cr CO 3 3 i-J O CO . o 11 3 tl CU H- 3 UI CU OJ ro O<br />

sf<br />

01 e< rt fD rt Oh cu CO < ro CO l-l . 3 3 fD O fD O M o ro H- tl 00 >< rt o rt o H ^< rt o O . 11 o cu g O on<br />

CO fD sS P- 11 *< n c fD fD CO rt CO U) rt CO 3 O cu (-" M 3 o 00 3d « OJ 3 o 3 B ro H- 3 H as ^ 00 Cu rt "C rt Co n M 3 O CU n Hi Tl rt fD 3 rt<br />

CO 3 fD O c rt rt H- O CO CO i-l 3 3 n rt i-i o cr O I-1 -^4 (D to fD ro i-j o rt O 3d H- o h-1 Hi CO ^^ o v-x 3d i 00 prt<br />

e i-( rH rt rt P- I—1 »< ro •—s cr fD M 3 fD rt CU H 3 TJ H- ro O CD 1* 3 H- ro 3d H ro O<br />

g §<br />

fD Hi o<br />

3 XT p. O ^ rt CO CU N3 o 3 CD CO o rt o CU CO Cl H- en cu ^H> O O 3 3 CO h-1 CO rt H- CD O 3<br />

g . p.<br />

Mi CO p- CU CO 3 cu rt l-l B O cu rt cu 3d fD rt 3d O t-t ?r 3 rt CO rt s **• . 3 Hi Oh Oj 3d rt X-N rt Hi Cu 3 O<br />

TJ p. o> rt XT CO CO rt Oh X* fD fD H- o ti r-> 3 O CL 3d cu X) fD o Cl O H- CU cl -~J rt CD fD fD 3 fD 3d 1—H cr < C 3 CO<br />

fD n ro rt O P- cr o fD B 00 o CL V< a 3 fD rt ro J-i 3 ft CO o H rt rt U3 3d o rt o CO fD fD o ro rt ro Co O M<br />

rt p. cu e g<br />

CO CO 3 fD 3 CO o \T Tl M H H i-j 3 rt O CO H- H-J cr fD fD M "~< CO H- n 1 o cr 1 M O Co<br />

CU fD cu 3 i—1<br />

1 fD I-l "3 rt fD CU 3 rt s_^ CO CO r* Cl fD s rt CO H- . rt O TJ O H- H- g s fD 3 00 fD fD O o o H- Co<br />

O<br />

H.<br />

rr 3 3 rt a. o o O s3 O I-"- fD 3 3d n h-1 H- 3d rt 11 -3 cr> O Hi CU 3 a CD TJ TJ O 3 CD CO 3 CO M O Tl o CO 00 Cu ?r<br />

c rr a. I-l rt l-l ro H- rt CO i-l cr cu Cl C M cr H- CO ro O fD 3d KJ rt cr H- fD CU TJ O rt ro fD CO H- O *-^» o ro O rt o<br />

rl o a ^< P- M<br />

rt fD 3 H- cu fD 3 rt n ro ro ro H H- CO ro i-1 CO rt n H •« ro H- Cu Oj cu ro h-1 cr M CO rt rt 3<br />

— (0 TJ o Tl cu O cu 3 O n rt O- O Hi %» CO CU h-1 S O 3 fD I-" CD fD CO H CL 3 CD H Hi Oj N—^ Oj o Co 3 CO rt<br />

i-i . fD P- 3 CO 3 rt 3 M ro l-l 3 Oh rt ti 0 g 3 ro TJ rt CO CL rt ^"N CU CD CL fD Hi < 3 fD X < p* CL CL 3d ro fD o CO h-1 CO o UI to 3 fD CO rt H- TJ o rt »* 00 H CD rt fD rt CO O 3d CD<br />

i-l CO xr O B H- fD n O 3 fD CD Cl g n H- rt CO s3 3 CL H rt X 3d rt CO rt 3d Co . ro fD Cu ro Cl Hi<br />

cu rt •->* O fD 3* o O rt TJ 1—' l-l o 3 Cu O OJ CO P CU O fD H- fD CU 3 fD CU O H- ro 3d H» CD ro sS 3 OJ o cu D rt •1 Cu P-<br />

CO O ^4 I-h Cu o CO c ro fD H- i-i 3 rt 3 rt rt fD s; rt ^ h-> 3 H < 11 3 CO H rt B H- 00 O Oh o i-1 H H- rt rt Co *< rt CO<br />

Ul O £ fD i-( i-i CU H- Hi i-i ro 3" 3d 3 ro CL M H- CU 3 Oh 3 rt H- 3 n 3 fD Hi O O ?r XT C/3<br />

%<br />

TJ !-( rt rr i-l rt cu l-l Oh H- cr H- 3 CD CO H- CO cr s "3 Co H M rt O cr g H rt O 3 I-- fD Oh ii fD fD fD rt 3<br />

o c cu 3" O rt p. ro XT rt "^ fD 3 rD 3 3 0 "< 0 rt fD cu O rt 3 fD •^xS cr 3 o H- rt O rt CL X X^s ro TJ rt ro 3 H" Co fD<br />

OJ<br />

M<br />

CO 5 3 fD i-l p* 3 3 cu c fD 3 00 i-i CD cr n rt O fD C B Ul fD 3 Cl fD fD < X rt O<br />

1—1 "^<br />

CO a. 5 On rt rt i-l H- rt o. fD ro CO rt rt o fD M g CU O CO s3 rt H H- ro H- ro 00 rt fD 00 CO H B fD n<br />

1 P- ro<br />

5.<br />

P- rr ?o < rt p. pj ft> 3 ZT . Hi CO CO c fD CO 3d S i-l rt cr H- TJ O ro H- •~< 3 O On H 3d 3 K- 3 O TJ CO fD rt H> O CD<br />

cr 3- 3<br />

h- O fD o VT, 3 1 CO ro H* CO Xi<br />

1 i-i fD fD s 3d fD 3 CO 3 rt i- « 00 < o 3 H- H CO o m fD CO ro rt fD CD<br />

i cu<br />

i—' fD ro 1—| CO CX CU O pi rt CO rt 3 o Xi m i-i rt Cu fD H CO H> rt o 3d h> ro fD o rt fD H- Tl fD H* •1 fD Oj 3d B CO<br />

fD Ui o CO e rt fD n i-l ro 1—i i-i 3 M fD rt fD rt 00<br />

H,<br />

H o 00 h"0 CO TJ fD *< Cu < '^w' X < cu 1—' H- TJ 1 co 1<br />

fD fD x ro rt c rt) O O Co V3 cr CL O g fD l-l o Co w O 3 CU • H- O CO CO rt fD<br />

o<br />

. O fD rt rt 3 fD "-< 1—' ^^<br />

rr "3 CO pj p. O. p. B I-j. i CO Hl I-1 cr V! ro CU O -3 •I fD Hi < M CL 3 VO rt fD H- rt O fD ro Cl 3 o 3d tl Co<br />

o 1—1 CO "-< a CO fD < ro ^H rt O i-1 H- CD l-l ro M cu Oh H- O CU fD H-00 3d Hi 3 CL CO . 1 o fD O CO 1 n cr<br />

CJ p. CO p.i no cr rt l-i cu 3 CD 3d CO 3 ro CO o H- fD 3d H P- H- l-l H- 3 < rt H- n < 3 s—^ ro JU W CO fD o 3 rt fD CO H- Oh S2 3d O Hi «. CO<br />

S cr cu i-i fD H v; i-i o H- o C/3 CO H- H •3 Hi fD ro CU Hi fD m . o ro 11 O TJ TJ CO CO CO 3 3 3 3 s ro<br />

p. p. H 3<br />

& O xr fD a CO o n rt •<br />

3 O fD rt fD o 3 M<br />

CO TJ o Hi o o rt h H rt H* B, O ** H- H H- cu<br />

. ^<br />

N 3 3* Dh (—i O ro TJ H-1 o C o CU 00 3 0 l-l l-l CO M < < TJ tl Tl Co O g o O H- H- O < cr 11 fD O h-1 Co 3 o<br />

fD fD P- rt O i-i cu cr M i-i o rt 00 O Co 3 V5 CD CU TJ H M ro w B 11 ti H B B fD H- fD Oj a" cu M M Oj Hi<br />

«# CO CO 3d 3 Ipy o O ^ *<br />

p.i fD fD rt l—l O fD cu X) CO cu Co to . H fD H- H- Cl rt H- fD ro o rt rt K3 Oj M 3 H r-1 h-1 B < fD H- O X<br />

O<br />

p.i £T<br />

fD n cu *rt I-h 3 3 p. P- cu O CO O 3 (D 3" o rt H M ro O *< l-l rt CO TJ rt o o H TJ 3 00 11 H- Hi ,Q cu ii CD fD n CL ro 1—'<br />

fD CO rt Cu O CO o l-l . fD Co l-t O c 3d 3d H- CO H CO rt H- . 3d fD 3 3 O fD CO rt fD 3 3 g CO fD sS 11 cu cu °- "!? o<br />

cu o n p. 3 rt 3 1—' (U c rt H- fD g 3 CO rt 3d rt 3 O O tl ro CO •^j H Hi O H CD B


p TJ Cu rt rt rt Oj cr rt CO B n Co o rt pj r1 Oj »i M rt rt CO TJ P- O co Oh P- rt O rr 3 o rt O rt r> rt CU Hi < p. Hi<br />

O 3 cr cr •I ro XT Co CO fD P.<br />

8 3 o Cu o o H fD O cr p- n •1 CO n p- P- 3 O Hi fD O CU p. 3 p. XT XT 3 O p. a O<br />

fD p- 3<br />

to •1 rt CO On o<br />

3 n<br />

ft ro<br />

3 1 rt p- fD rt pj ro ^ > rt<br />

XT ^ O 3 fD O rt O to Cu X O<br />

3 rr TJ rt O Co fD O- 3 OjOO n<br />

o 00<br />

3 p- < O Co o<br />

h rt rt<br />

CU ro 3 rj rt fD<br />

1 rt o 00 TJ to CU CO p-1 pj O rt cu CO < - ro 00 1 o CO o P- O 03 -«r m fD XT XT o cr O Co CO 00 TJ rt Oj CO p.<br />

. 3d TJ H s M XT -< -< ii XT 3 to rt M 3 rt S . o<br />

Pi<br />

S" 3 Cl O fD o . Cu fD to cu fD Pi u p- ii H fD O 3- XT a H<br />

sf fD to XT p- 3 P1 fD •<br />

3<br />

fD to rt cu CO p. cr pj P- ro XT<br />

fD pj Oh 3 CO 3 rt c 3 fD O cr CD p. to O rt CO LJ- XT<br />

rt CO 11 to CD TJ 3 rr NJ CL n CO • fD N<br />

B<br />

§ to rt ro rt ro Tj CC 3 VJ rt O Hi ro 3 3 XT rt to ro<br />

rt fD CO CU 01 . . TJ O n M rt ro ro Co fD 3 o H O Co Cl rt i. H CO 11 TJ cr 01 P- pj CO cr rt TJ rt Co co 0 hj<br />

fD fD 3 rt 3 rt tl 3d Hi H NJ o 3 p- p-> • H rt rt XT 3 O XT ro O ro fD p- 3 3 XT rl i-i fD 11 03 rt rt rt ro<br />

t-( TJ O O XT o ro * O P- TJ cr S3 P- rt co M CL CO 00 CL O fD rD 00 ro i. p. p.<br />

H* > TJ H<br />

§•<br />

i Cu Cu CO P- 1—' H fD fD 3 TJ CL o XT o n tl 01 tl P- ^< CO XT CO O 03 3 . fD pJ-O p. 03 p-<br />

fD<br />

O O Co<br />

TJ 11 rt 3 01 rt XT CO XT O i cr 3 CO Cu o 1 fD 3 cr to 3 TJ 01 CO rt CL 3 P- 3 3 fD CO rt 3 3 3 hi<br />

CO TJ ro XT Co 3 XT to B to CO rt rt fD P- O TJ rt MTJ o o < CU rt o 3 M CU H 3 rD CC 3 XT ro p. CO H 3 3* Oh ro<br />

fD CD CU P-1 rt cr •I to CO Hi UJCD TJ P- O oi oo rt XT P- o TJ cu to CL XT 3 fD 3 fD 3 CL & Hi to P- O Hi r| ro t-i fD fD<br />

H- 3 CO CO<br />

01 XT ro ro CL P* --— to tl O CO XT P- to rt 3 3 fD 3 3 fD to rt rt < TJ s3 Hi 3 3 fD rr fD *3 1—1 Co<br />

CO<br />

CU<br />

CL p" •1 to O O CO CU 3 TJ 3 O H XT 00 fD H rt .O XT ro Pi 01 CO rS P- TJ < Oj O rt CO fD Co 3<br />

P*<br />

o<br />

B<br />

cu<br />

TJ<br />

X<br />

3 g ro rr CD TJ o S3 01 *< tl H O 3 ro fD 11 PJ cr 3 K -^j to M 3 3<br />

CD < n ro CO rt CO XT CO < 3 0 Oj<br />

o O 3 p- ro Hi s~^ >«", /—N to fD O Hi rt to rt Co CO h- OjTJ ft to p- H fD cr pj Hi 3d to 3 CO Oj •r h-1<br />

CO 3 o TJ 1 00 ii S OJ CO CO r1 < 3 O Hi P- O P- fD XT rt rt . TJ «3 P- TJ M cu H ro pi n ro rt *< TJ to i—i rt Hi o 3 1 CO CL o- P- fD ro K- H pi O 1 pJ i. 3 o rt fD fD CD TJ pj 3 3 XT<br />

3 o TJ to ii ro cu rt cr 3 »• ro CD O 3 01 CO M O o 01 H O ro P1 Cu fD cr rt Oh P- TJ CD X3 p. 3 rj Co rr rt to CO<br />

g Hi o 3


36<br />

7. COMPUTER PREDICTION OF THERMAL-HYDRAULIC<br />

PARAMETERS FOR NORMAL RECOVERY<br />

7.1 Introduction<br />

The purpose of this chapter is to present the results of BWR-LACP<br />

calcul<strong>at</strong>ions (see Sect. 4) of system behavior for two different portions<br />

of the <strong>St<strong>at</strong>ion</strong> Blackout:<br />

1. Normal Recovery: DC power from the unit b<strong>at</strong>tery remains available<br />

during this period; therefore RCIC and HPCI injection flows are assumed<br />

available throughout, and<br />

2. Loss of 250 vdc B<strong>at</strong>teries: The b<strong>at</strong>teries are assumed to fail after<br />

four hours, causing failure of RCIC and HPCI injection, ultim<strong>at</strong>ely leading<br />

to uncovering of the core about eight hours after the <strong>blackout</strong>.<br />

The normal recovery portion of the <strong>St<strong>at</strong>ion</strong> Blackout is discussed in<br />

detail in Sects. 3 and 6. Oper<strong>at</strong>or actions assumed here are consistent<br />

with those sections. Results were calcul<strong>at</strong>ed to five hours* for normal<br />

recovery in order to provide some overlap with the MARCH code severe ac<br />

cident calcul<strong>at</strong>ions (see Sects. 9 and 10), which assume th<strong>at</strong> the boil-off<br />

begins after four hours from a fully pressurized condition. The Loss of<br />

250 vdc B<strong>at</strong>teries results are given in this section in order to provide an<br />

estim<strong>at</strong>e of system behavior possible after loss of dc power if the plant<br />

is depressurized during the normal recovery period.<br />

7.2 Conclusions<br />

Major conclusions drawn from the calcul<strong>at</strong>ed results are given below,<br />

succeeded by a detailed discussion of code input assumptions and transient<br />

results.<br />

7.2.1 Normal Recovery — Conclusions<br />

If power were recovered within five hours of the inception of the<br />

<strong>St<strong>at</strong>ion</strong> Blackout, a normal recovery would be possible. System parameters<br />

are within acceptable ranges after five hours:<br />

1. The 250 vdc b<strong>at</strong>teries, by assumption, last the full five hours.<br />

2. Reactor vessel level is within the normal control range, about 5.08 m<br />

(200 in.) above the top of active fuel.<br />

3. Reactor vessel pressure is being controlled <strong>at</strong> about 0.69 MPa (100<br />

psia).<br />

4. About 354 m3 (93,500 gal.) of w<strong>at</strong>er have been pumped from the Con<br />

dens<strong>at</strong>e Storage Tanks, which had an assured capacity of 511 m3<br />

(135,000 gal.) before the <strong>blackout</strong>.<br />

5. Suppression pool temper<strong>at</strong>ure is about 82°C (180°F), but this should<br />

not be a problem for the T-quencher type of SRV discharge header pip<br />

ing.<br />

6. Containment pressures are elev<strong>at</strong>ed to about 0.17 MPa (25 psia), well<br />

below the 0.53 MPa (76.5 psia) design pressure.<br />

*These results are extended to seven hours in Appendix G.


37<br />

7. Drywell <strong>at</strong>mosphere temper<strong>at</strong>ure is below the 138°C (281°F) design tem<br />

per<strong>at</strong>ure.<br />

7.2.2 Loss of 250 vdc B<strong>at</strong>teries — Conclusions<br />

The results of this transient show very clearly how fuel damage is<br />

postponed because the reactor vessel was depressurized early in the Sta-t<br />

tion Blackout:<br />

1. The repressuriz<strong>at</strong>ion time after loss of the 250 vdc b<strong>at</strong>teries is<br />

gre<strong>at</strong>er than one hour, during which time there is no significant<br />

coolant loss from the reactor vessel.<br />

2. When the boil-off does begin, it takes a much longer time to uncover<br />

fuel because of the higher starting inventory of w<strong>at</strong>er.<br />

Although fuel damage is significantly delayed, the ability to avoid<br />

ultim<strong>at</strong>e fuel damage is compromised because of the elev<strong>at</strong>ed drywell tem<br />

per<strong>at</strong>ure experienced after loss of the 250 vdc b<strong>at</strong>teries. As discussed in<br />

Sect. 3, a containment temper<strong>at</strong>ure of 149°C (300°F) would not prevent nor<br />

mal recovery. This temper<strong>at</strong>ure is reached about 40 min. after loss of the<br />

b<strong>at</strong>teries. At about four hours after the b<strong>at</strong>tery loss, the fuel is begin<br />

ning to be uncovered, and the drywell temper<strong>at</strong>ure is above 191°C (375°F).<br />

This elev<strong>at</strong>ed temper<strong>at</strong>ure may cause failure of the drywell electrical pen<br />

etr<strong>at</strong>ions and may fail the solenoid oper<strong>at</strong>ors necessary for oper<strong>at</strong>ion of<br />

the SRVs, inner isol<strong>at</strong>ion valves, and containment cooler dampers (which<br />

fail closed on loss of AC power). Even if electrical power were fully re<br />

stored <strong>at</strong> this point, considerable oper<strong>at</strong>or ingenuity would be required to<br />

effect a normal recovery if the MSIV and SRV solenoid oper<strong>at</strong>ors have<br />

failed.<br />

In addition, the chances for a normal recovery are compromised by the<br />

elev<strong>at</strong>ed suppression pool temper<strong>at</strong>ures experienced <strong>at</strong> the end of the tran<br />

sient. Condens<strong>at</strong>ion oscill<strong>at</strong>ion during SRV discharge (see Appendix D),<br />

which can damage the suppression pool pressure boundary, becomes more<br />

likely <strong>at</strong> higher pool temper<strong>at</strong>ures. Steam discharge without oscill<strong>at</strong>ion<br />

from the <strong>Browns</strong> <strong>Ferry</strong> T-quencher type discharge piping is assured up to<br />

88°C (190°F), but average pool temper<strong>at</strong>ure <strong>at</strong> the end of the Loss of 250<br />

vdc B<strong>at</strong>teries calcul<strong>at</strong>ion is above 93°C (200°F).<br />

7.3.1 Normal Recovery — Assumptions<br />

7.3 Normal Recovery<br />

Assumptions specific to programming and input prepar<strong>at</strong>ion for the<br />

normal recovery calcul<strong>at</strong>ion include:<br />

1. The calcul<strong>at</strong>ion begins 30 s following the <strong>St<strong>at</strong>ion</strong> Blackout initi<strong>at</strong>ion<br />

with the reactor tripped and the main steam isol<strong>at</strong>ion valves closed.<br />

Values for system parameters <strong>at</strong> the 30-s point are taken from the re<br />

sults reported by Sect. 14.5.4.4 of the <strong>Browns</strong> <strong>Ferry</strong> FSAR. The cal<br />

cul<strong>at</strong>ion ends <strong>at</strong> the 5 hour point.<br />

2. The RCIC system is used in an on-off mode to control vessel level be<br />

tween 13.7 m (538 in.) and 14.7 m (578 in.) above vessel zero. The


38<br />

HPCI system is actu<strong>at</strong>ed only when level is more than 0.25 m (10 in.)<br />

below the 13.4-m (528-in.) lower limit of control room indic<strong>at</strong>ion<br />

under <strong>St<strong>at</strong>ion</strong> Blackout conditions. Suction for both systems is from<br />

the condens<strong>at</strong>e storage tank (CST). The oper<strong>at</strong>ors actu<strong>at</strong>e HPCI and<br />

RCIC 1 min. after the <strong>blackout</strong>.<br />

3. Following 1 min. of autom<strong>at</strong>ic SRV actu<strong>at</strong>ion, reactor pressure is con<br />

trolled by remote-manual actu<strong>at</strong>ion of the SRVs. Control range dur<br />

ing the first hour is 7.52 MPa (1090 psia) to 6.31 MPa (915 psia).<br />

After 1 hour the reactor is depressurized to about 0.79 MPa (115<br />

psia) <strong>at</strong> a r<strong>at</strong>e consistent with the 55.6°C/h (100°F/h) cooldown r<strong>at</strong>e<br />

limit. After depressuriz<strong>at</strong>ion, pressure is controlled between 0.62<br />

MPa (90 psia) and 0.86 MPa (125 psia).<br />

Manual sequential SRV action is used to spread SRV discharge around<br />

the suppression pool and thereby avoid localized he<strong>at</strong>ing of the pool.<br />

4. The assumed reactor system leakage into the drywell is 0.0089 m /s<br />

(4 gpm).<br />

7.3.2 Normal Recovery — Results<br />

Results for normal recovery are shown on Figs. 7.1 through 7.9.<br />

Each system variable is discussed below.<br />

7.3.2.1 Reactor vessel pressure. Figure 7.1 shows reactor vessel<br />

pressure. During the first minute, reactor pressure cycles between 7.72<br />

MPa (1120 psia) and 7.38 MPa (1070 psia) on autom<strong>at</strong>ic SRV actu<strong>at</strong>ion.<br />

After 1 min. the oper<strong>at</strong>or opens one SRV to lower pressure to 6.31 MPa (915<br />

psia). Since the HPCI is running, pressure continues to decrease to below<br />

6.21 MPa (900 psia) until the HPCI is shut down. During the first hour a<br />

single SRV is cycled open and shut seven times to keep pressure in the de<br />

sired range.<br />

After one hour, the depressuriz<strong>at</strong>ion begins. Initially, intermittent<br />

oper<strong>at</strong>ion of one SRV is sufficient to meet the target depressuriz<strong>at</strong>ion<br />

r<strong>at</strong>e [i.e., 55.6°C (100°F)/h], As pressure decreases, the r<strong>at</strong>e of de<br />

crease begins to slow until finally an additional SRV is opened. For<br />

choked flow of dry steam, the mass flow r<strong>at</strong>e is linearly proportional to<br />

reactor pressure . Therefore an extra valve is required <strong>at</strong> the lower pre<br />

ssure. When depressuriz<strong>at</strong>ion is complete, the oper<strong>at</strong>or controls pressure<br />

between 0.62 and 0.86 MPa (90 and 125 psia).<br />

After depressuriz<strong>at</strong>ion, the steam flow through one SRV is nearly<br />

equal to the core steaming r<strong>at</strong>e, resulting in much slower pressure change.<br />

Under these conditions, the most rapid pressure change is caused by the<br />

RCIC system. When RCIC comes on the 600 gpm injection of cold w<strong>at</strong>er tends<br />

to lower the core steaming r<strong>at</strong>e, causing pressure to decrease. This ef<br />

fect can be seen in Fig. 7.1. At 256 min., the RCIC comes on, reducing<br />

pressure until the open SRV is shut. When the RCIC is shut off 23 min.<br />

l<strong>at</strong>er, pressure increases rapidly until the SRV is reopened.<br />

Steam flow from the reactor vessel is shown in Fig. 7.2. The large<br />

spikes are due to SRV actu<strong>at</strong>ion. Also included in the total steam flow<br />

are the smaller amounts of steam flowing to the RCIC and HPCI turbines<br />

when they are running.


UJ<br />

rr<br />

UJ<br />

cc<br />

a.<br />

S<br />

< to-<br />

Pig.<br />

pressure.<br />

150<br />

TIME (min)<br />

ORNL-DWG 81-8489 ETD<br />

7.1 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - reactor vessel<br />

300<br />

OJ


5 O<br />

co 9-<br />

LLI<br />

CO<br />

CO<br />

UJ<br />

><br />

.*> 10<br />

< 2<br />

UJ<br />

Ico<br />

uis-fi<br />

co —<br />

CO<br />

LL!<br />

><br />

M<br />

flow.<br />

o<br />

rr<br />

X<br />

o<br />

o<br />

tr<br />

I<br />

r-<br />

o<br />

30<br />

—P"<br />

60<br />

7<br />

U —r~<br />

so<br />

ORNL-DWG 81-8490 ETD<br />

LARGE SPIKES DUE TO INTERMITTENT OPERATOR ACTUATION<br />

OF A SINGLE SRV DURING DEPRESSURIZATION<br />

N<br />

150<br />

TIME (min)<br />

I—OPERATOR OPENS SECOND SRV TO<br />

SPEED DEPRESSURIZATION<br />

LLI<br />

z<br />

CD<br />

CC<br />

I-<br />

O<br />

CJ<br />

CC<br />

X<br />

C5<br />

o<br />

cr<br />

x<br />

H<br />

VESSEL IS<br />

DEPRESSURIZED<br />

FLOW THROUGH<br />

ONE SRV<br />

Fig. 7.2 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - vessel steam<br />

270 300<br />

o


41<br />

7.3.2.2 Reactor vessel level — normal recovery. Figure 7 .3 shows<br />

vessel w<strong>at</strong>er level (distance above vessel zero) in the region outside the<br />

core outlet plenum, standpipes, and steam separ<strong>at</strong>ors. This is the level<br />

measured by vessel level instrument<strong>at</strong>ion and available in the control<br />

room. As discussed in Sect. 4, there is a corresponding level of twophase<br />

mixture in and above the core. For an undamaged core in a mild<br />

transient such as <strong>St<strong>at</strong>ion</strong> Blackout, the level of steam/w<strong>at</strong>er mixture in<br />

and above the core will be higher than the downcomer level whenever down<br />

comer level is below the top of the steam separ<strong>at</strong>ors.<br />

Downcomer level is initialized <strong>at</strong> 12.7 m (500 in.) and, <strong>at</strong> first, de<br />

creases rapidly until the oper<strong>at</strong>or initi<strong>at</strong>es injection via the RCIC and<br />

HPCI systems. When level recovers to 13.7 m (540 in.), the oper<strong>at</strong>or shuts<br />

off the HPCI system, and when level reaches 14.7 m (578 in.), the RCIC<br />

injection is shut off. Level continues to increase due to the continuing<br />

he<strong>at</strong>up of the large quantity of cold w<strong>at</strong>er injected by the RCIC and HPCI<br />

systems and due to form<strong>at</strong>ion of additional voids in and above the core as<br />

the steaming r<strong>at</strong>e increases. The level peaks <strong>at</strong> 15.2 m (600 in.). This is<br />

about 0.30 m (12 in.) above the top of the range of level indic<strong>at</strong>ion<br />

available in the control room during <strong>St<strong>at</strong>ion</strong> Blackout.<br />

Control Room level indic<strong>at</strong>ion during a <strong>St<strong>at</strong>ion</strong> Blackout is limited to<br />

a range of 3.66 m (0 to 60 in.) with instrument zero corresponding to<br />

13.41 m (528 in.) above vessel zero, which is the bottom of the reactor<br />

vessel. The basic cycle of RCIC actu<strong>at</strong>ion by the oper<strong>at</strong>or when level<br />

reaches an indic<strong>at</strong>ed 0.25 m (10 in.) and shut-off when level reaches an<br />

indic<strong>at</strong>ed 1.27 m (50 in.) is repe<strong>at</strong>ed eight times on Fig. 7.3. The fine<br />

structure is caused by action of the SRVs. When the SRV opens, vessel<br />

level first swells due to increased steaming, but then begins to decrease<br />

due to inventory loss. When the SRV shuts, level <strong>at</strong> first continues to<br />

decrease due to decrease in steaming r<strong>at</strong>e, but then begins to recover due<br />

to he<strong>at</strong>up of subcooled liquid still within the downcomer.<br />

Injection flow from the CST to the reactor vessel is shown in Fig.<br />

7.4. The oper<strong>at</strong>or controls the RCIC and HPCI systems in an off-on mode in<br />

order to maintain vessel level within the desired control band as speci<br />

fied in Para. 7.3.1.2. The HPCI system is only run during the initial few<br />

minutes. The periods of RCIC system oper<strong>at</strong>ion become less frequent as the<br />

decay he<strong>at</strong> subsides with time. Total injected flow (i.e., total amount of<br />

w<strong>at</strong>er taken from the CST) is shown in Fig. 7.5. The injected total in<br />

creases rapidly <strong>at</strong> first during the brief period of combined HPCI and RCIC<br />

oper<strong>at</strong>ion; the increase is much slower during the subsequent intermittent<br />

periods of RCIC oper<strong>at</strong>ion.<br />

7.3.2.3 Suppression pool level — normal recovery. When steam flows<br />

from the reactor vessel to the suppression pool, it is condensed by the<br />

colder pool w<strong>at</strong>er. Suppression pool level increases both because of the<br />

extra mass of the condensed steam and because of the temper<strong>at</strong>ure increase<br />

of the original pool w<strong>at</strong>er. Suppression pool level is shown in Fig. 7.6,<br />

referenced to instrument zero of the torus. The torus has a 9.45 m (31<br />

ft) inside diameter and instrument zero is 0.1 m (4 in.) below the midplane.<br />

(A zero level indic<strong>at</strong>es the torus is about half filled with<br />

w<strong>at</strong>er.) The pool level is normally maintained between -0.051 and -0.152 m<br />

(—2 and —6 in.) indic<strong>at</strong>ed; an initial pool level of -0.102 m (—4 in.)<br />

was assumed for this analysis. The pool condenses steam both from the


120 150 180<br />

TIME (min)<br />

ORNL-DWG 81-8491 ETD<br />

210 240 270 300<br />

Fig. 7.3 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - reactor vessel<br />

level.<br />

ro


8<br />

8-<br />

* o. —' o<br />

u- o.<br />

o<br />

Q to<br />

UJ —^<br />

r-<br />

-? «N.<br />

5000 gpm HPCI PLUS 600 gpm RCIC<br />

TOTAL INJECTED FLOW<br />

HPCI OFF<br />

RCIC OFF<br />

30<br />

—r<br />

60<br />

—r-<br />

90 120<br />

RCIC<br />

ON OFF ON OFF<br />

{ \ { \<br />

150<br />

TIME (min)<br />

—T-<br />

180 210<br />

Fig. 7.4 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - injection flow.<br />

ORNL-DWG 81-8492 ETD<br />

240 270 300


O<br />

><br />

Q<br />

UJ<br />

r-<br />

CJ<br />

UJ<br />

<<br />

t °<br />

S-><br />

a<br />

QJ oo<br />

o<br />

><br />

Ch-<br />

ID<br />

ra<br />

UJ<br />

5°<br />

OS<br />

I- -r<br />

flow.<br />

RCIC<br />

OFF ON<br />

4=4 /<br />

30<br />

HPCI OFF<br />

RCIC IS OFF DURING PERIODS WHEN<br />

•INDICATED VESSEL LEVEL IS ABOVE"<br />

DESiRED LOWER LIMIT<br />

/<br />

INJECTION BY COMBINED HPCI<br />

AND RCIC SYSTEMS<br />

T<br />

60 90 120 150<br />

TIME (min)<br />

OFF-<br />

RCIC<br />

ORNL-DWG 81-8493 ETD<br />

180 210 240 270 300<br />

Fig. 7.5 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - total injected<br />

4>


o<br />

X<br />

E<br />

^<br />

c<br />

_J<br />

UJ<br />

_l ><br />

UJ UJ<br />

>


46<br />

SRVs and the RCIC and HPCI turbine exhaust. The effect of RCIC turbine<br />

exhaust shows up in Fig. 7.6 as a very slow background r<strong>at</strong>e of increase<br />

against the dominant effect of the SRVs.<br />

7.3.2.4 Suppression chamber temper<strong>at</strong>ures — normal recovery. Sup<br />

pression chamber temper<strong>at</strong>ures are shown in Fig. 7.7. For all practical<br />

purposes, the average pool temper<strong>at</strong>ure responds solely to condens<strong>at</strong>ion of<br />

reactor vessel steam. Therefore, this curve has almost the same shape as<br />

the pool level curve. The pool <strong>at</strong>mosphere can be influenced by mass and<br />

he<strong>at</strong> transfer from the pool w<strong>at</strong>er and by mass transfer from the drywell<br />

<strong>at</strong>mosphere.<br />

During the first 30 min. the suppression chamber <strong>at</strong>mospheric tempera<br />

ture increases rapidly because of mixing with the inflow of hotter gases<br />

from the expanding drywell <strong>at</strong>mosphere. Drywell temper<strong>at</strong>ure (Fig. 7.8) in<br />

creases rapidly <strong>at</strong> first due to loss of the drywell coolers. As a result,<br />

the drywell <strong>at</strong>mosphere expands into the suppression chamber <strong>at</strong>mosphere<br />

through the pool w<strong>at</strong>er via the eight vent pipes, the single ring header,<br />

and the 96 downcomer pipes.<br />

In the long term, mass transfer from the drywell ceases and the sup<br />

pression chamber temper<strong>at</strong>ure continues to increase due to he<strong>at</strong> transfer<br />

and evapor<strong>at</strong>ion from the suppression pool surface.<br />

7.3.2.5 Containment pressures — normal recovery. The suppression<br />

chamber and drywell pressures are shown in Fig. 7.9. The drywell and sup<br />

pression chamber <strong>at</strong>mospheres are coupled in the following manner:<br />

1. When suppression chamber pressure exceeds drywell pressure by 0.00345<br />

MPa (0.5 psi), the vacuum breaker valves will open and allow flow of<br />

suppression chamber <strong>at</strong>mosphere into the drywell.<br />

2. When drywell pressure exceeds suppression chamber pressure by more<br />

than about 0.0121 MPa (1.75 psi), this will clear the 1.22 m (4 ft)<br />

of w<strong>at</strong>er from the downcomer pipes and allow drywell <strong>at</strong>mosphere to<br />

bubble up through the pool w<strong>at</strong>er into the suppression chamber.<br />

Immedi<strong>at</strong>ely after the <strong>St<strong>at</strong>ion</strong> Blackout, drywell pressure increases<br />

rapidly due to the concurrent rapid he<strong>at</strong>up of the drywell <strong>at</strong>mosphere.<br />

Even after the drywell <strong>at</strong>mosphere reaches its peak temper<strong>at</strong>ure and starts<br />

down, the drywell pressure continues to increase under the influence of<br />

the assumed 0.0089 m3/s (4 gpm) leak of hot reactor coolant, some of<br />

which flashes to steam. Throughout the first 2 hours, conditions in the<br />

drywell bring the suppression chamber pressure up <strong>at</strong> about the same r<strong>at</strong>e<br />

by expansion (via the downcomers) into the suppression chamber. After the<br />

first two hours, suppression chamber pressure is increasing faster than<br />

dict<strong>at</strong>ed by the drywell because of increasing r<strong>at</strong>es of he<strong>at</strong> transfer and<br />

evapor<strong>at</strong>ion from the overhe<strong>at</strong>ed suppression pool. After about 190 min.<br />

the pressure is high enough to open the vacuum breakers and cause expan<br />

sion of suppression chamber <strong>at</strong>mosphere back into the drywell.<br />

7.3.2.6 Drywell temper<strong>at</strong>ure — normal recovery. Drywell <strong>at</strong>mosphere<br />

temper<strong>at</strong>ure response is shown in Fig. 7.8. The initial r<strong>at</strong>e of increase<br />

is very rapid because the drywell coolers are lost <strong>at</strong> time zero, and about<br />

half of the 100% power drywell he<strong>at</strong> load is assumed to remain. The r<strong>at</strong>e<br />

of increase becomes much slower when drywell temper<strong>at</strong>ure is high enough


SUPPRESSION CHAMBER TEMPERATURES (°C)<br />

110<br />

l<br />

50 60 70 80 90 100<br />

_l_ _i_ _1_ _1_<br />

40<br />

I<br />

30 L_<br />

SUPPRESSION CHAMBER TEMPERATURES (°F)<br />

130 150 170 190 210<br />

O<br />

-U<br />

z<br />

r-<br />

I<br />

o<br />

S<br />

o<br />

(O<br />

oi<br />

m<br />

H<br />

O<br />

L*i


O<br />

o__<br />

UJ<br />

cr<br />

<<br />

rr<br />

UJ<br />

o.<br />

UJ<br />

t-<br />

UJ<br />

rr<br />

UJ<br />

x<br />

o.<br />

co<br />

O<br />

< -<br />

UJ<br />

><br />

rr<br />

a<br />

o<br />

uv<br />

o<br />

•«r<br />

8r-><br />

r— DEPRESSURIZATION<br />

u. BEGINS<br />

1<br />

UJ<br />

rr i DRYWELL DESIGN TEMPERATURE<br />

P o /<br />

< M<br />

cr<br />

UJ /<br />

a.<br />

5<br />

UJ<br />

H<br />

UJ 0 >-<br />

UJ <br />

I<br />

a.<br />

CO<br />

O<br />

r-<br />

UJ<br />

><br />

cr<br />

Q<br />

o<br />

^ LO-jo ui uii j vvi_i_u<br />

cc;uLcri5<br />

DEPRESSURIZATION—^<br />

COMPLETED<br />

2- i<br />

30 60 90 120 150 180<br />

TIME (min)<br />

210 240<br />

Fig. 7.8 Normal recovery after st<strong>at</strong>ion <strong>blackout</strong> - drywell<br />

temper<strong>at</strong>ures.<br />

ORNL-DWG 81-8496 ETD<br />

270 300<br />

00


a.<br />

o<br />

o<br />

to<br />

LLI<br />

rr<br />

—^<br />

co<br />

CO<br />

UJ<br />


50<br />

to establish n<strong>at</strong>ural convection he<strong>at</strong> transfer to the drywell liner (see<br />

discussion in Sect. 4). Drywell temper<strong>at</strong>ure begins decreasing after about<br />

60 min. because a reactor coolant system (RCS) depressuriz<strong>at</strong>ion is begun<br />

<strong>at</strong> this point. The depressuriz<strong>at</strong>ion reduces s<strong>at</strong>ur<strong>at</strong>ion temper<strong>at</strong>ure within<br />

the RCS, hence surface temper<strong>at</strong>ures of the reactor vessel and piping.<br />

7.4 Loss of 250 vdc B<strong>at</strong>teries<br />

7.4.1 Loss of 250 vdc B<strong>at</strong>teries — Assumptions<br />

Assumptions specific to programming and input prepar<strong>at</strong>ion for the<br />

Loss of 250 vdc B<strong>at</strong>teries calcul<strong>at</strong>ion include:<br />

1. When the b<strong>at</strong>teries are lost, injection capability is lost; in addi<br />

tion, the SRVs can be opened only by autom<strong>at</strong>ic actu<strong>at</strong>ion.<br />

2. Under autom<strong>at</strong>ic actu<strong>at</strong>ion, the lowest set SRV will open <strong>at</strong> about 7.72<br />

MPa (1120 psia) and close <strong>at</strong> about 7.38 MPa (1070 psia).<br />

3. The calcul<strong>at</strong>ion begins 4 h after the <strong>St<strong>at</strong>ion</strong> Blackout and proceeds to<br />

about 8 h.<br />

4. Initial values of system parameters, except reactor vessel level, are<br />

equal to those calcul<strong>at</strong>ed <strong>at</strong> the 4 h point in the normal recovery re<br />

sults (see Figs. 7.1 through 7.9). Reactor vessel level is assumed<br />

to begin <strong>at</strong> 14.2 m (558 in.), the midpoint of the control range as<br />

sumed for the normal recovery calcul<strong>at</strong>ion.<br />

7.4.2 Loss of 250 vdc B<strong>at</strong>teries — Results<br />

Results for the Loss of 250 vdc B<strong>at</strong>teries case are shown in Figs.<br />

7.10 through 7.16. Each system variable is discussed below.<br />

7.4.2.1 Reactor vessel pressure. Reactor vessel pressure is shown<br />

in Fig. 7.10. During the first 90 min., pressure climbs slowly from the<br />

0.86 MPa (125 psia) initial value to the 7.72 MPa (1120 psia) actu<strong>at</strong>ion<br />

point of the lowest set SRV. The r<strong>at</strong>e of increase is slow because the de<br />

cay he<strong>at</strong> after 4 hours is small compared to the thermal inertia of liquid<br />

w<strong>at</strong>er within the vessel.<br />

After repressuriz<strong>at</strong>ion, the pressure is controlled between 7.72 MPa<br />

(1120 psia) and 7.38 MPa (1070 psia) by one SRV, actu<strong>at</strong>ing autom<strong>at</strong>ically.<br />

As shown in Fig. 7.11, no steam flows from the vessel until pressure re<br />

aches the SRV autom<strong>at</strong>ic actu<strong>at</strong>ion setpoint.<br />

7.4.2.2 Reactor vessel level. Reactor vessel level is shown in Fig.<br />

7.12. No injection is provided <strong>at</strong> any time in this transient, since DC<br />

power is assumed lost.<br />

The initial response of level is a brief but rapid decrease caused by<br />

closing of the previously open SRV <strong>at</strong> time zero. Within several minutes<br />

level begins slowly rising and peaks <strong>at</strong> about 15.88 m (625 in.). Level<br />

swells during repressuriz<strong>at</strong>ion because the large mass of w<strong>at</strong>er in the ves<br />

sel is he<strong>at</strong>ed from about 165°C (330°F) to about 288°C (550°F) with about a<br />

25% increase in specific volume, and there is no coolant loss (other than<br />

the assumed leakage) during repressuriz<strong>at</strong>ion.


360 390 420<br />

TIME (min)<br />

Fig. 7.10 Loss of 250 VDC b<strong>at</strong>teries - reactor vessel pressure.<br />

ORNL-DWG 81-8498 ETD<br />

ij.


i. o. =<br />

•? 5<br />

o o<br />

_l _l<br />

LL o<br />

(O<br />

?<br />

u.<br />

S<br />

< < —<br />

11J LU<br />

1-<br />

CO<br />

in<br />

H<br />

co<br />

in<br />

in-<br />

_1 _l o<br />

UI LU o<br />

'<br />

"0 CO *<br />

CO<br />

CO<br />

LU<br />

><br />

JT<br />

LU<br />

><br />

NO STEAM FLOW FROM<br />

VESSEL DUE TO LOSS<br />

OF RCIC TURBINE AND<br />

REMOTE-MANUAL SRV<br />

CAPABILITY<br />

240 270<br />

—I—<br />

300<br />

AUTOMATIC ACTUATION OF<br />

LOWEST SET SRV<br />

330 360 390 420<br />

TIME (min)<br />

450<br />

ORNL-DWG 81-8499 ETD<br />

CALCULATIONS<br />

STOPPED<br />

Fig. 7.11 Loss of 250 VDC b<strong>at</strong>teries - vessel steam flow.<br />

480 51C 540<br />

ro


240 270 300 330 360 390 420<br />

TIME (min)<br />

Fig. 7.12 Loss of 250 VDC b<strong>at</strong>teries - vessel level.<br />

ORNL-DWG 81-8500 ETD<br />

450 480 510 540<br />

OJ


54<br />

After repressuriz<strong>at</strong>ion, the SRVs begin to discharge steam so level<br />

decreases throughout the remainder of the transient. Fuel is beginning to<br />

be uncovered <strong>at</strong> the end of the transient.<br />

7.4.2.3 Suppression pool level. The suppression pool level is shown<br />

in Fig. 7.13. During the first 90 min., there is no SRV discharge, so<br />

pool level is constant. After SRV discharge resumes, the pool level be<br />

gins increasing steadily.<br />

7.4.2.4 Suppression chamber temper<strong>at</strong>ures. Figure 7.14 shows sup<br />

pression pool and suppression chamber <strong>at</strong>mosphere temper<strong>at</strong>ure. Pool tem<br />

per<strong>at</strong>ure, like pool level, is constant for the first 90 min. and then be<br />

gins a steady increase. Atmosphere temper<strong>at</strong>ure continues to rise during<br />

the first hour due to he<strong>at</strong> transfer and evapor<strong>at</strong>ion from the pool sur<br />

face. Atmosphere temper<strong>at</strong>ure rise acceler<strong>at</strong>es slightly between the first<br />

and second hours due to an influx from the expanding drywell <strong>at</strong>mosphere.<br />

After about 2 hours, the mass interchange ceases, and the suppression<br />

chamber <strong>at</strong>mosphere temper<strong>at</strong>ure is responding solely to the increasing pool<br />

temper<strong>at</strong>ure.<br />

7.4.2.5 Containment pressures. Figure 7.15 shows containment pre<br />

ssures. During the first 90 min., drywell pressure increases rapidly due<br />

to he<strong>at</strong>up of the drywell <strong>at</strong>mosphere during repressuriz<strong>at</strong>ion. This brings<br />

drywell pressure from slightly below suppression chamber pressure to about<br />

0.0125 MPa (1.8 psi) above, allowing some drywell <strong>at</strong>mosphere to expand<br />

into the suppression chamber. After about 2 hours, the drywell and sup<br />

pression chamber pressures are increasing independently <strong>at</strong> about the same<br />

r<strong>at</strong>e, with little mass interchange.<br />

7.4.2.6 Drywell <strong>at</strong>mosphere temper<strong>at</strong>ure. Drywell <strong>at</strong>mosphere tempera<br />

ture is shown in Fig. 7.16. During the repressuriz<strong>at</strong>ion, the coolant tem<br />

per<strong>at</strong>ure within the reactor vessel increases by over 111 C° (200 F°),<br />

thereby increasing the drywell he<strong>at</strong> source. Atmosphere temper<strong>at</strong>ure rises<br />

to new quasi-equilibrium values, with increased n<strong>at</strong>ural circul<strong>at</strong>ion he<strong>at</strong><br />

transfer from the <strong>at</strong>mosphere to the drywell liner. After repressuriza<br />

tion, the coolant temper<strong>at</strong>ure becomes approxim<strong>at</strong>ely constant, and the tem<br />

per<strong>at</strong>ure of the drywell <strong>at</strong>mosphere rises more slowly <strong>at</strong> a r<strong>at</strong>e limited by<br />

the thermal inertia of the liner.


o<br />

X<br />

o<br />

o<br />

a.<br />

z<br />

o<br />

LU<br />

cc<br />

a.<br />

a.<br />

3<br />

to<br />

.= o<br />

-I<br />

UJ<br />

><br />

LU<br />

_l<br />

_l<br />

o<br />

0D_<br />

O to<br />

rs. ^<br />

Z<br />

o<br />

to<br />

t/><br />

LU<br />

CC<br />

a.<br />

0- o,.<br />

3 <br />

CO<br />

OJi<br />

i<br />

"'<br />

i—- NO DISCHARGE<br />

INTO POOL ^<br />

\— INTERMITTENT SRV DISCHARGE<br />

INTO POOL BEGINS WHEN VESSEL<br />

PRESSURE REACHES SETPOINT<br />

OF LOWEST SET SRV<br />

240 270 300 330 360 390 420 450<br />

TIME (min)<br />

Fig. 7.13 Loss of 250 VDC b<strong>at</strong>teries - suppression pool level.<br />

ORNL-DWG 81-8501 ETD<br />

460 510 540<br />

UI<br />

Ln


to<br />

UJ<br />

rr<br />

5 LU<br />

I— O<br />

rr<br />

LU<br />

m<br />

< <<br />

X t^- I<br />

o O<br />

z z<br />

o o<br />

8<br />

to<br />

o_ (O<br />

UJ UJ<br />

cc rr<br />

Q_ Q.<br />

CL. a.<br />

D D<br />

CO to<br />

o_<br />

•—CONTINUED HEATUP BY HEAT<br />

AND MASS TRANSFER FROM<br />

HOTTER POOL<br />

8- 240 270 300 330 360 390 420<br />

-POOL TEMPERATURE INCREASES WHEN<br />

SRV DISCHARGE RESUMES<br />

HEATUP ACCELERATES DUE TO INFLUX<br />

"OF HOTTER DRYWELL ATMOSPHERE<br />

VIA DOWNCOMERS<br />

TIME (min)<br />

450 480<br />

Fig. 7.14 Loss of 250 VDC b<strong>at</strong>teries - suppression chamber<br />

temper<strong>at</strong>ures.<br />

ORNL-DWG 81-8502 ETD<br />

510 540<br />

Ln<br />

ON


Fig. 7.15 Loss of 250 VDC b<strong>at</strong>teries - containment pressures.<br />

ORNL-DWG 81-8503 ETD<br />

510 540<br />

Ui<br />

--J


o<br />

o__<br />

UJ<br />

cc<br />

o<br />

o-<br />

(N<br />

ATMOSPHE100 1<br />

07<br />

o_<br />

UJ<br />

cc<br />

^H<br />

o<br />

in<br />

to<br />

SRV DISCHARGE BEGINS<br />

SLOWER INCREASE BECAUSE REACTOR<br />

VESSEL TEMPERATURE APPROXIMATELY<br />

CONSTANT __j^<br />

1— lt>-<br />

< —<br />

CC<br />

UJ<br />

0.<br />

<br />

cc<br />

o<br />

o<br />

o<br />

\—DR<br />

VWELL TE VIPERATU RE INCRE/ \SES<br />

AS REACTOR VESSEL COOLANT<br />

TEI\ /IPERATUR E INCREASES<br />

240 270 300 330 360 390 420<br />

TIME (min)<br />

DRYWELL DESIGN TEMPERATURE<br />

450 480<br />

Fig. 7.16 Loss of 250 VDC b<strong>at</strong>teries - drywell <strong>at</strong>mosphere<br />

temper<strong>at</strong>ure.<br />

ORNL-DWG 81-8504 ETD<br />

510 540<br />

en<br />

oo


59<br />

8. FAILURES LEADING TO A SEVERE ACCIDENT<br />

As discussed in Sect. 3, control can be maintained over reactor ves<br />

sel pressure and w<strong>at</strong>er level <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 for a significant<br />

period of time during a <strong>St<strong>at</strong>ion</strong> Blackout provided the installed equipment<br />

oper<strong>at</strong>es as designed and the oper<strong>at</strong>or takes the required actions. The<br />

first objective of this Section is to briefly discuss the other sequences<br />

which might occur given significant secondary independent equipment fail<br />

ures or improper oper<strong>at</strong>or actions. Subsequently, the equipment failures<br />

which have the potential to directly convert the rel<strong>at</strong>ively stable period<br />

of level and pressure control of the isol<strong>at</strong>ed reactor vessel during the<br />

early stages of a <strong>St<strong>at</strong>ion</strong> Blackout into a Severe Accident will be dis<br />

cussed in detail.<br />

The several sequences which are considered most probable in a <strong>St<strong>at</strong>ion</strong><br />

Blackout during the period in which DC power remains available are dis<br />

played in the "event tree" of Fig. 8.1. Each of these sequences is dis<br />

cussed below.<br />

Sequence 1; Following the complete loss of AC power, the oper<strong>at</strong>or<br />

takes remote-manual control of the RCIC system and maintains the reactor<br />

vessel w<strong>at</strong>er level within the limits of the available Control Room indica<br />

tion. Since the RCIC System is being used for level control, the st<strong>at</strong>us<br />

of the HPCI system is not a factor in this sequence. The oper<strong>at</strong>or also<br />

controls the reactor vessel pressure by remote-manual oper<strong>at</strong>ion of the<br />

primary relief valves and takes action to begin depressuriz<strong>at</strong>ion of the<br />

reactor vessel within one hour; this lowers the temper<strong>at</strong>ure of the s<strong>at</strong>u<br />

r<strong>at</strong>ed liquid within the vessel and thereby decreases the driving potential<br />

for he<strong>at</strong> transfer into the drywell <strong>at</strong>mosphere. As a result of this de<br />

pressuriz<strong>at</strong>ion, the maximum average ambient temper<strong>at</strong>ure in the drywell is<br />

limited to 148.9°C (300°F), as discussed in Sect. 3. The oper<strong>at</strong>or will be<br />

able to maintain reactor vessel level and pressure control for as long as<br />

DC power is available from the <strong>Unit</strong> B<strong>at</strong>tery. This is considered to be the<br />

most realistic sequence should a <strong>St<strong>at</strong>ion</strong> Blackout occur, and served as the<br />

basis for the plots of thermohydraulic parameters as functions of time<br />

which were presented in Sect. 7. This sequence will also serve as the<br />

starting point for the degraded accident behavior discussed in Section 9<br />

in which the <strong>St<strong>at</strong>ion</strong> Blackout develops into a Severe Accident when DC<br />

power is lost so th<strong>at</strong> cooling w<strong>at</strong>er can no longer be injected into the re<br />

actor vessel.<br />

Sequence 2; This sequence differs from Sequence 1 only in th<strong>at</strong> the<br />

oper<strong>at</strong>or does not act to depressurize the reactor vessel. The average<br />

ambient drywell temper<strong>at</strong>ure continues to increase beyond the one-hour<br />

point, reaching 176.7°C (350°F) about four hours after the inception of<br />

the <strong>St<strong>at</strong>ion</strong> Blackout (cf. Curve A of Fig. 3.3). This excessive tempera<br />

ture existing over a period of several hours can cause serious damage to<br />

the equipment loc<strong>at</strong>ed within the drywell and a breaching of the primary<br />

containment due to failure of the drywell electrical penetr<strong>at</strong>ion assembly<br />

seals. If the DC solenoid oper<strong>at</strong>ors for the primary relief valves fail<br />

because of the excessive temper<strong>at</strong>ure, the oper<strong>at</strong>or will lose remote-manual<br />

relief valve control. If the solenoid oper<strong>at</strong>ors for the inboard Main<br />

Steam Isol<strong>at</strong>ion Valves also fail, the oper<strong>at</strong>or will be unable to depres<br />

surize the reactor vessel through the primary relief valves even after AC


COMPLETE LOSS<br />

OF AC POWER<br />

OPERATOR ACTION<br />

TO CONTROL LEVEL<br />

AND RCIC OPERABLE<br />

HPCI OPERABLE<br />

OPERATOR ACTION<br />

TO DEPRESSURIZE<br />

WITHIN 1 h<br />

ORNL-DWG 81-1544A ETD<br />

HPCI SUCTION SHIFTS TO PSP AT<br />

PSP LEVEL = +7"<br />

Fig. 8.1 Event tree for initial phase of a st<strong>at</strong>ion <strong>blackout</strong> in<br />

which DC power remains available.<br />

©<br />

©<br />

©<br />

©<br />

©<br />

©<br />

©<br />

©<br />

ON<br />

o


61<br />

power is restored. There is no reason to accept these risks to the drywell<br />

integrity and installed equipment; the oper<strong>at</strong>or should take action to<br />

depressurize, as in Sequence 1.<br />

Sequence 3; Either the RCIC system is inoperable or the oper<strong>at</strong>or<br />

does not choose to employ it for long-term reactor vessel level control.<br />

The HPCI System is operable, and either autom<strong>at</strong>ically functions as neces<br />

sary to cycle the reactor vessel level between 12.1 and 14.8 m (476 and<br />

582 in.) above vessel zero, or is remote-manually controlled by the oper<br />

<strong>at</strong>or to maintain the w<strong>at</strong>er level within the indic<strong>at</strong>ing range, 13.4 to 14.9<br />

m (528 to 588 in.). The oper<strong>at</strong>or controls the reactor vessel pressure by<br />

remote-manual oper<strong>at</strong>ion of the relief valves and takes action to begin depressur<strong>at</strong>ion<br />

within one hour. Up to this point, this sequence is similar<br />

to Sequence 1, except th<strong>at</strong> the injection of condens<strong>at</strong>e storage tank w<strong>at</strong>er<br />

into the reactor vessel is by the HPCI System instead of the RCIC System.<br />

When the indic<strong>at</strong>ed w<strong>at</strong>er level in the pressure suppression pool in<br />

creases to 0.18 m (+7 in.), the HPCI pump suction is autom<strong>at</strong>ically shifted<br />

from the condens<strong>at</strong>e storage tank to the pressure suppression pool. De<br />

pending on the initial suppression pool level, the necessary amount of<br />

w<strong>at</strong>er to cause this shift will have been transferred from the reactor ves<br />

sel via the primary relief valves <strong>at</strong> some time between two and four hours<br />

after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout. Since the lubric<strong>at</strong>ing oil for<br />

the HPCI turbine is cooled by the w<strong>at</strong>er being pumped, and the average sup<br />

pression pool temper<strong>at</strong>ure will be about 71.1°C (160°F) <strong>at</strong> this point, an<br />

early failure of the HPCI system is thre<strong>at</strong>ened.<br />

Sequence 4; This sequence is the same as Sequence 3, except th<strong>at</strong> the<br />

oper<strong>at</strong>or has recognized the difficulties with the elev<strong>at</strong>ed suppression<br />

pool temper<strong>at</strong>ure and has taken action to prevent the shift in HPCI pump<br />

suction. The oper<strong>at</strong>or will be able to maintain reactor vessel level and<br />

pressure control for as long as DC power remains available from the <strong>Unit</strong><br />

B<strong>at</strong>tery. The continuing increase in suppression pool level will not cause<br />

any significant problems during the remaining period in which DC power<br />

would remain available.<br />

It should be noted th<strong>at</strong> pressure suppression pool temper<strong>at</strong>ure instru<br />

ment<strong>at</strong>ion would be inoperable during a <strong>St<strong>at</strong>ion</strong> Blackout. Oper<strong>at</strong>or train<br />

ing and the <strong>St<strong>at</strong>ion</strong> Blackout Emergency Oper<strong>at</strong>ing Instruction (which does<br />

not now exist) must provide for oper<strong>at</strong>or understanding of the need to pre<br />

vent a shift of the HPCI pump suction to the overhe<strong>at</strong>ed pressure suppres<br />

sion pool.<br />

Sequence 5: This sequence represents the case of <strong>St<strong>at</strong>ion</strong> Blackout<br />

with no oper<strong>at</strong>or action and no secondary independent equipment failures.<br />

The HPCI System autom<strong>at</strong>ically cycles the reactor vessel w<strong>at</strong>er level be<br />

tween the HPCI system initi<strong>at</strong>ion point of 12.1 m (476 in.) and the HPCI<br />

turbine trip point of 14.8 m (582 in.) above vessel zero. Over the long<br />

term, one primary relief valve would repe<strong>at</strong>edly oper<strong>at</strong>e as necessary to<br />

maintain the reactor vessel pressure between about 7.722 and 7.377 MPa<br />

(1105 and 1055 psig).<br />

There are three problem areas with this case of no oper<strong>at</strong>or action:<br />

1. the difficulties with high drywell ambient temper<strong>at</strong>ure as discussed in<br />

connection with Sequence 2,<br />

2. the increased probability of loss of injection capability after the<br />

undesirable shift of the HPCI pump suction to the overhe<strong>at</strong>ed pressure<br />

suppression pool as discussed in connection with Sequence 3, and


62<br />

3. the decrease in suppression pool effectiveness caused by the highly<br />

localized he<strong>at</strong>ing of the pool w<strong>at</strong>er surrounding the discharge of the<br />

one repe<strong>at</strong>edly oper<strong>at</strong>ing relief valve. The possible consequences are<br />

discussed in Appendix D.<br />

Sequence 6: This sequence differs from Sequence 5 only in th<strong>at</strong> the<br />

HPCI pump suction is maintained on the condens<strong>at</strong>e storage tank, either by<br />

oper<strong>at</strong>or action, or by fortuitous failure of the pertinent HPCI system<br />

logic. This reduces the probability of HPCI system failure due to inade<br />

qu<strong>at</strong>e lube oil cooling during the period of <strong>St<strong>at</strong>ion</strong> Blackout in which DC<br />

power is still available. The difficulties with high drywell ambient tem<br />

per<strong>at</strong>ure and localized suppression pool he<strong>at</strong>ing as discussed in connec<br />

tion with Sequence 5 remain.<br />

Sequence 7: The RCIC system is not available because of equipment<br />

failure, or lack of oper<strong>at</strong>or action. The HPCI system has failed because<br />

of a system malfunction. The represents the worst case of loss of injec<br />

tion capability while DC power remains available. A boiloff of the ini<br />

tial reactor vessel w<strong>at</strong>er inventory begins immedi<strong>at</strong>ely after the complete<br />

loss of AC power, leading to a rel<strong>at</strong>ively quick core uncovery and subse<br />

quent meltdown. In this sequence, the core uncovery is hastened by a de<br />

pressuriz<strong>at</strong>ion of the reactor vessel either by means of a stuck-open re<br />

lief valve or because of inappropri<strong>at</strong>e oper<strong>at</strong>or action; the depressuriza<br />

tion increases the r<strong>at</strong>e of loss of the irreplaceable reactor vessel w<strong>at</strong>er<br />

inventory.<br />

Sequence 8: This sequence is the same as Sequence 7, except th<strong>at</strong><br />

there is no reactor vessel depressuriz<strong>at</strong>ion. The uncovery of the core<br />

would begin about one-half hour after the loss of AC power. The plant re<br />

sponse to Sequences 7 and 8 will be discussed further in Section 9.<br />

The preceding discussion of altern<strong>at</strong>e sequences again shows th<strong>at</strong> a<br />

<strong>St<strong>at</strong>ion</strong> Blackout <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant will not evolve into a<br />

Severe Accident as long as reactor vessel w<strong>at</strong>er injection capability is<br />

maintained. The remainder of this section contains a discussion of the<br />

methods by which this injection capability might be lost. There are three<br />

main areas of concern for the viability of the injection systems: <strong>St<strong>at</strong>ion</strong><br />

Blackout induced direct failure of the HPCI and RCIC systems, a stuck-open<br />

relief valve which might reduce reactor vessel pressure below th<strong>at</strong> neces<br />

sary for HPCI and RCIC turbine oper<strong>at</strong>ion, and the ultim<strong>at</strong>e loss of DC<br />

power. Each of these will be discussed in turn.<br />

8.1 Induced Failure of the HPCI and RCIC Systems<br />

The design and the principles of oper<strong>at</strong>ion of the HPCI and RCIC sys<br />

tems are discussed in Appendices E and F, respectively. Each of these<br />

systems has the capacity to provide the necessary reactor vessel w<strong>at</strong>er<br />

level control during a <strong>St<strong>at</strong>ion</strong> Blackout; both must fail to cause a total<br />

loss of injection capability.<br />

The failure modes considered in this Section will be limited to those<br />

induced by the conditions of a <strong>St<strong>at</strong>ion</strong> Blackout. Independent secondary<br />

failures, whose occurrence during a <strong>St<strong>at</strong>ion</strong> Blackout would be purely coin<br />

cidental, have been considered in other studies16 and will not be dis<br />

cussed here.


63<br />

The first thre<strong>at</strong> to the continued oper<strong>at</strong>ion of the HPCI and RCIC sys<br />

tems under <strong>St<strong>at</strong>ion</strong> Blackout conditions is due to the loss of the Reactor<br />

Building cooling and ventil<strong>at</strong>ion systems. The major components of the<br />

HPCI and RCIC systems are loc<strong>at</strong>ed in the basement of the Reactor Building,<br />

where the average temper<strong>at</strong>ures during a <strong>St<strong>at</strong>ion</strong> Blackout would be signif<br />

icantly affected by the temper<strong>at</strong>ure of the pressure suppression pool. The<br />

HPCI and RCIC systems are designed for continuous oper<strong>at</strong>ion <strong>at</strong> an ambient<br />

temper<strong>at</strong>ure of 64.4°C (148°F). As was shown in Section 7, the average<br />

pressure suppression pool temper<strong>at</strong>ure would reach 71.1°C (160°F) after<br />

about three hours under <strong>St<strong>at</strong>ion</strong> Blackout conditions. However, it is ex<br />

pected th<strong>at</strong> the ambient temper<strong>at</strong>ure in the vicinity of the HPCI and RCIC<br />

systems would significantly lag the increasing suppression pool tempera<br />

ture; it is estim<strong>at</strong>ed th<strong>at</strong> the design temper<strong>at</strong>ure of 64.4°C (148°F) would<br />

not be exceeded for <strong>at</strong> least four hours. In any event, exceeding the de<br />

sign ambient temper<strong>at</strong>ure would not assure failure of the HPCI and RCIC<br />

systems.<br />

A more probable cause of HPCI or RCIC system failure is the autom<strong>at</strong>ic<br />

isol<strong>at</strong>ion of these systems due to the tripping of the temper<strong>at</strong>ure sensing<br />

circuits designed to detect steam leaks in the system piping. As des<br />

cribed in Appendices E and F, each of these systems has a set of four trip<br />

logics with four temper<strong>at</strong>ure sensors per logic. The 16 sensors are physi<br />

cally arranged in four groups placed near the HPCI or RCIC equipment, with<br />

the four sensors in each group arranged in a one-out-of-two taken twice<br />

trip logic. If the trip setpoint of 93.3°C (200°F) is reached, an auto<br />

m<strong>at</strong>ic closure signal is sent to the RCIC or HPCI primary containment in<br />

board and outboard steam supply valves, and the system turbine is tripped.<br />

Since the inboard steam supply valve for each of these systems is ACmotor-oper<strong>at</strong>ed,<br />

it would not close, but the system would be effectively<br />

isol<strong>at</strong>ed due to closure of the outboard (DC-motor-oper<strong>at</strong>ed) steam supply<br />

valve.<br />

As shown in Section 7, it is expected th<strong>at</strong> the RCIC turbine would be<br />

oper<strong>at</strong>ed only intermittently during a <strong>St<strong>at</strong>ion</strong> Blackout, while the HPCI<br />

system would serve only as a backup in the event of RCIC system failure.<br />

Also, the RCIC equipment is not loc<strong>at</strong>ed in a closely confined space, and<br />

some n<strong>at</strong>ural convection within the reactor building will certainly occur.<br />

Nevertheless, it is conceivable th<strong>at</strong> the local temper<strong>at</strong>ure in the vicinity<br />

of the steam leak detection sensors could reach 93.3°C (200°F) during RCIC<br />

system oper<strong>at</strong>ion after the average space temper<strong>at</strong>ure has increased to over<br />

60°C (140CF). If this occurs, the resulting RCIC system isol<strong>at</strong>ion signal<br />

can be overriden in the auxiliary instrument<strong>at</strong>ion room and the steam sup<br />

ply valves reopened and the turbine trip reset. Thereafter, the HPCI sys<br />

tem and the RCIC system, which are loc<strong>at</strong>ed on opposite sides of the sup<br />

pression pool torus, might be altern<strong>at</strong>ely used for reactor vesssel level<br />

control so as to reduce the he<strong>at</strong>up in the vicinity of the RCIC system.*<br />

Thus, the tripping of the temper<strong>at</strong>ure sensing circuits is not expected to<br />

lead to a total loss of injection capability.<br />

*The HPCI room has not been designed to permit n<strong>at</strong>ural circul<strong>at</strong>ion<br />

and the HPCI system has much more surface area for he<strong>at</strong> transfer Into its<br />

surrounding space. Therefore, it is expected th<strong>at</strong> the he<strong>at</strong>up associ<strong>at</strong>ed<br />

with HPCI oper<strong>at</strong>ion would be more severe than th<strong>at</strong> associ<strong>at</strong>ed with RCIC<br />

oper<strong>at</strong>ion.


64<br />

Another challenge to the viability of the HPCI and RCIC systems would<br />

be posed by the loss of control air pressure during a prolonged <strong>St<strong>at</strong>ion</strong><br />

Blackout. The plant control air system is supplied from three air receiv<br />

ers with a combined capacity of 22.60 m3 (798.0 ft3). Under <strong>St<strong>at</strong>ion</strong><br />

Blackout conditions, the air compressors which normally run intermittently<br />

as necessary to maintain the receiver pressure in the range of 0.66 to<br />

0.86 MPa (80 to 105 psig) would be inoperable; the stored inventory of<br />

pressurized air would gradually be lost due to valve oper<strong>at</strong>ions and leak<br />

age.<br />

Control air is used in the HPCI and RCIC systems to oper<strong>at</strong>e the steam<br />

supply line drain isol<strong>at</strong>ion valves. In each of these systems, the two<br />

primary containment isol<strong>at</strong>ion valves in the steam line to the turbine are<br />

normally open so th<strong>at</strong> the steam supply piping is kept <strong>at</strong> elev<strong>at</strong>ed tempera<br />

tures; this permits rapid turbine startup on demand. The w<strong>at</strong>er formed by<br />

the steam which condenses in this line when the turbine is not oper<strong>at</strong>ing<br />

is removed to the main condenser via a thermost<strong>at</strong>ic steam trap. The two<br />

air-oper<strong>at</strong>ed drain isol<strong>at</strong>ion valves close to prevent the flow of w<strong>at</strong>er<br />

from the steam trap to the main condenser when the primary containment is<br />

to be isol<strong>at</strong>ed; the closing signal is autom<strong>at</strong>ically gener<strong>at</strong>ed on low re<br />

actor w<strong>at</strong>er level [12.10m (476.5 in.) above vessel zero].<br />

The steam supply line drain isol<strong>at</strong>ion valves fail closed on loss of<br />

control air, which would eventually occur during a prolonged <strong>St<strong>at</strong>ion</strong><br />

Blackout. This should not cause serious difficulties for the RCIC system<br />

which would be run intermittantly so th<strong>at</strong> the accumul<strong>at</strong>ion of w<strong>at</strong>er in the<br />

steam supply piping between runs would not be excessive. However, a sub<br />

stantial amount of w<strong>at</strong>er would collect in the HPCI steam supply piping if<br />

this system is not oper<strong>at</strong>ed over a long period following the loss of con<br />

trol air pressure. Subsequent initi<strong>at</strong>ion of the HPCI system might cause<br />

turbine damage. However, it should be noted th<strong>at</strong> the HPCI and RCIC tur<br />

bines are two-stage, non-condensing Terry turbines, which are of very rug<br />

ged construction and are designed for use under emergency conditions, and<br />

the oper<strong>at</strong>or could take action to run the HPCI turbine for short periods<br />

to clear the lines of w<strong>at</strong>er as necessary. Thus the loss of control air<br />

during a prolonged <strong>St<strong>at</strong>ion</strong> Blackout should not lead to a total loss of in<br />

jection capability.<br />

A third challenge to the viability of the w<strong>at</strong>er injection systems<br />

should affect the HPCI system only. This challenge would occur because of<br />

the HPCI system logic which provides for an autom<strong>at</strong>ic shifting of the HPCI<br />

pump suction from the condens<strong>at</strong>e storage tank to the pressure suppression<br />

pool when the indic<strong>at</strong>ed pressure suppression pool level reaches 0.18 m (+7<br />

in.). As previously discussed, this would occur between two and four<br />

hours after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout, when the pressure sup<br />

pression pool temper<strong>at</strong>ure has increased to about 71.1°C (160°F). Since<br />

the turbine lubric<strong>at</strong>ing oil is cooled by the w<strong>at</strong>er being pumped, and the<br />

oil cooler is designed for a maximum inlet w<strong>at</strong>er temper<strong>at</strong>ure of 60.0°C<br />

(140°F), the oil would become overhe<strong>at</strong>ed, possibly leading to failure of<br />

the turbine bearings. This can be avoided if the oper<strong>at</strong>or takes action to<br />

maintain suction on the condens<strong>at</strong>e storage tank for any HPCI system oper<br />

<strong>at</strong>ion. There is an ample supply of condens<strong>at</strong>e storage tank w<strong>at</strong>er avail<br />

able for injection, and the continuing increase in pressure suppression<br />

pool level will in no way thre<strong>at</strong>en the continued oper<strong>at</strong>ion of the


p- rt o rt rt p- co rr O CO CD h- ft n TO O O 1 H H 00 5 H CO 1 P- CC Pi O Pi s CO Hi .o C JO P" O Cfl rt t* Pi P-<br />

3 XT TJ XT XT 3 G ro fu ro Xi CO XT (0 rt |"d *o ro P> CO H ro ro M ro co hfl 3 Hi C p. C H C 1 o O Hi rt cr o G 3* TO P- G O 00 rt to o cr p. • o. •- •< rt ro M h cr ro P- c ro 3 TO ro M H ro p- o<br />

tj 1 o •.. oj TO (0 3 *- B 0 CO CO rt 3d 3 PJ o Oj o pi V£> PI cr p. O O P1 O cr rt p. CO cr ro 3<br />

ro xr co co CO 3d 3 \~s rt 3 rt 3 O ro •-< H G i Co c r-> P- H OJ H p. pj >a pi Xi Oj H ro ro ro 3 Cfl P"0 p- ro •<br />

i-l O 00 rt rt B O O 00 rt . ro o o 00 o ro H ro r-> pj < 3 ro . 3 ro<br />

to pj to ro B L-l. rt 3 Hi TO<br />

* S<br />

h- c to ro G O § o ro 3d M XT m ro cr O Hi O to P- pi CO CO to pi oj rt ro H cr pi cr Xi CO ro CO o S ro Hi -<<br />

o i p- o. n i-i 3 o » ro VS . H X) o TO 3 n O rt<br />

n o O rt 3 •-< PI ro o o H w o rt TTXi TO ro TO<br />

Cl 3 pr ro G CD rt P- to rt pj ro 00 rt ro M 1- rt O P> G rt rt rt rt ro rt p. O v o rt<br />

co tj i-i 1 o i-i rt r-l Xi I-1 G 3 n cr o. o G o. P- P- o rt a h p. p. H- o cr a cr P- o G TO rt ro<br />

ro rt ro O CD 3 TO XT to H o n o 00 pj ro p- p) H TO Hi O H /-n XT Oj cr rt to O 1 H pi C O 3 rt C o TO B<br />

«; i-i c co Tj rt to CO o -,3 3 rt SJ CD cr ro G rt cr ro Pi p- H- O 3 p. rt H rt 3 1 O Hi CO<br />

XT P- i-i o ro ro tj PI O XI ro co o rt O CC P> o < a. TO P- < O rt O 3 (D p" 3 < cr ro CO O rt o<br />

ro O 3 rt 3 to p- rt o rt o r-l ro XT H « rt CL c ro P- 3 o ro O • ro TO pi O rt ro ro Oj rt O P1 o p. rt Hi Cu<br />

3 Oj CO O B oo a o r-l o ro o ro G rt TO p- 3 00 3 CO o K rt Hi CO TO XT CO pi 3 O XT G<br />

i-i i-i • co ro r-l rt H Hi rt C M H to TO 3 00 CD ro CO *i XT H^- o ro p- TO ?o rt to 3 o O. 3 to P- H<br />

rt CO O ro p- c ii P- CO Hi p* H CO rt ro ro v—- P- 00 rt Hi rt 3 ro n o Pi 7? P- 3 p.<br />

3d XT Xi < M CO 00 O CO < O rt ro ro ro co hi cr 3d h-1 rt rt P- H P1 ro XT o cr ro p- M o zT O rt rt rH O 3<br />

£ rt CO ro cr ro rt o CO pi • XT P> o Oh O rt CO to ro P"0 TO i-d rt TO Pi to P1 rt O CO ro<br />

pd 3 XT TO mi ro i-l CO P1 ro ro rt a- S XT Hi rt TO p- H O Pi rt ro pj ro p- >a pi oo<br />

H P- 1 3 Co CO pi rt<br />

o ro ro p- p- ro . ro < O o po p- ro Oh o cr ro ro TJ O H PI o 3 c 3 g* CO rt P- TO 3 TO cr<br />

M H- M < 3 CD >£> rt M rt h-s xa to H rt O rt rt H S ro o o Hi CO H O ^^ P- B € p- ro Oh ro rt V! 3 O ro ro<br />

O 3 pd Co 00 G O h m p cr m xr O TO s CO p- x> o e ro pr TO CO H < P- Hi TO H 3 3 o. ?S vo ro h C O G ro o ro H ro Oj h O. rt<br />

cl ro ro > & < to TO rt G a" a. rt Co CO rt 3 P- o cr • ro O OJ ro O H Hi h ro X ro cr P-<br />

CO X) Oj rt v: ro rt B ro 00 CD p- co ro oo P1 XT 00 H ro Co O rQ M rr » w 7? * cr H o n X) p- O ro 3<br />

G. B Cu TO (0 GO 3 TO 3" ro p- 3 co ro < to "3 c p- TO Hi G o 3 cr co pi 1 XT p- < ro Hi rt to 3 TO Hi<br />

fD rt rt CO 3* CO rt ^*. ro TO rQ 3 rt o ro P- H O* Xi p- h3 1 c o O to 3 pi o D G < «<br />

O xi rr O zT to to P- TO CO 3 rt C rt O co Hi rt zn oo ro to o to rt -a rt pi O H XT Xi rt ro p- rt rt Hi rt rt tj PI p- cr<br />

r-t i-t to O (I H O i H 3* ro O XT 0! CO rt . TO Oj p- P- S C G to ro XT TO < P- XT pi ro cr tj 3 n pro<br />

ro i-t rt G rr 3 ^ ro ro 3 rt O o 3 3 pi 3 H B ro 1 /-^ 00 o 3 ro ro < to p- o. P- H H- o<br />

» TO 3 XT rt xi o> rt O ro CO to Xi to On a" rt O ro o c o. 3 On rt rt ro ro ro pi o H o TO CO rt rt a<br />

CO I-i CO Xi P- rt co V TO M H o P- OJVJ O 3 P1 Cfl Hi M G TO ro xr -a cr M 3 o rt ro G H- O V! o<br />

ro o B XT TO ro o rt p- ro o o 3 - Oj c ro o rt H •o • 13 ro h ro P- O o- rt ro P1 0- o S<br />

hS (IP- ro p- c J-T TJ O ro ro cd x> 3 B rr rt Cd ro o. o H P- CO TO ro TO ro c H p- 3 o ro TO 3 Pi O TJ<br />

XT P- O 3 3 r-l O SXl X h> co ro rt *! coCT cr M o ro rt O 3 o P-OO < ro H!00 p- o rt Hi to ro rt Hi o<br />

ro 3 3 rt .o ro C N-' Xi G 1 H p-—. ro ro P> H o- . rt Hi 00 ro H Pi m ro cr < 3 P- o. (1 TJ P- «<br />

3 O rt 00 rr rt o I-1 < H P> O 00 TO O ro cr 3-w Pi 3 CO < ro TO Co rt rt O ro rt ro<br />

H P- SI XT cr • Pd i-n CO pi ro rt h-> • O p- ?r ft) p- H> p- rt Co rt ro 3 rt ro o p. M P- p> ro p. ro rt TO c p- P- to Pi 3d p1 ro O •a rt H Hi M O z ro M P-<br />

M O. < XT TO (T> rt 11 TO 3 3 TO Co 3 p. CO Oj o H . i H rt O rt rt ro TO TO s H ro ro Co rt O H O 3<br />

o c ro ro ><br />

On


CL<br />

s<br />

LU<br />

cr<br />

w ^<br />

to<br />

LU<br />

CC<br />

o.<br />

S<br />

< „<br />

o<br />

o.<br />

o<br />

o<br />

01<br />

o<br />

— o<br />

F<br />

oo<br />

LU<br />

c 8-<br />

3 S<br />

LU<br />

rr o<br />

<<br />

IT)<br />

r- 8-<br />

(fl §<br />

o<br />

M<br />

O<br />

r\i<br />

L<br />

\<br />

n<br />

CICO N r~H<br />

'<br />

\<br />

o<br />

o-<br />

-RCIC OFF<br />

i L<br />

"-RCIC OFF<br />

1<br />

rR CICON<br />

30 60 90 120 150 180<br />

TIME (min)<br />

ORNL-DWG 81-8505 ETD<br />

210 240 270<br />

Fig. 8.2 Reactor vessel pressure response to a stuck-open relief<br />

valve during a st<strong>at</strong>ion <strong>blackout</strong>.<br />

300<br />

en


S<br />

8<br />

5<br />

o<br />

CO-<br />

Q co J<br />

UJ -H<br />

I-<br />

? CM<br />

E<br />

a<br />

o><br />

O -I o<br />

O<br />

o<br />

o.<br />

5600 gpm COMBINED HPCI AND RCIC INJECTION<br />

T"<br />

30<br />

HPCI OFF<br />

60<br />

RCIC<br />

OFF ON<br />

/ V<br />

-1—<br />

90<br />

—p-<br />

120<br />

-600 gpm RCIC INJECTION FLOW<br />

T —T"<br />

150 180<br />

TIME (min)<br />

Fig. 8.3 Reactor vessel w<strong>at</strong>er injection with a stuck-open relief<br />

valve during a st<strong>at</strong>ion <strong>blackout</strong>.<br />

—r-<br />

210<br />

ORNL-DWG 81-8506 ETD<br />

—r—<br />

240<br />

—r—<br />

270<br />

300


9 i-J 0) Cfl TJ iH u tj<br />

B tJi 3 O 4-1<br />

CO cfl O. 4-1 o •H Cfl rH /-N<br />

cu cu o •H u u O 4-1<br />

CO « 4-1 4H 4-J CU CU I-l CO<br />

cfl co co B O cfl Oh O. 4-1 O<br />

cu cu cu In o C rH<br />

I-l CO rH 4-J TO cu CO o<br />

a ca cu co >-i Oh tH CO u to<br />

cu cu co >*> 3 o X tH •H<br />

TJ In CO CO O 4-1 rH<br />

O CU X G 0 CU u<br />

CU CU > rH tH oo S > s O 33 4J cu H >> o. ><br />

CO rH 4J h xi co rH rH<br />

0) 3 CJ TJ 4J TJ CU CJ cfl<br />

U O cfl CU 3 TJ CJ co Q ><br />

0.rH tH CU<br />

CCJ 4-1 CU 4-1 X o Cfl 4-1 •H<br />

CU cfl 00 C »-i CO cO O. 4.) u<br />

0) 4-1 1 CJ W<br />

0) >i > (U cfl 4-J 0) CO in a o G<br />

00 cfl cfl In TO U CO \0 1 4-1<br />

TO X &n o 4H o o 3 cu IH l-l 4-1 PQ rH ^ £ q H-J 3 cu cu CU 3 XI rH >1 3 cu U rH cO<br />

-5 •H CJ CN TO 3 o XI G o CU 9 a CO 4-1 CO CJ 4J Oh 0 o 4-1 O rH 3<br />

9 T3 CU CO u CJ •H CO CO CO cu o. cfl X! cfl 4J 01 "3 •H<br />

O iH a<br />

. 4-1 XI TO 4-1 CU •H cj o 1 U TO cfl TJ •H >> 3 rH X o 3 4J In O 9 3<br />

I-i u 4-1 rH H •H 4-1 CU 3 CO 3 cu •H o CU TJ rH CO O rH 4-1 4J CO 4-1 •H a> CO cfl In<br />

03 cfl 3 o B rH XI OJ o XI 4-> 4-1 CN 4H Cfl PQ 4J cu CO •H cfl 9 Oj CU CO 01<br />

1 cu > CO O H a cu a 4-1 •H CO rH cu o rH m c -h 9 3 m In XI o In cfl 3 4-1<br />

CU TJ a 1 . c > OjX! 3 4J U rH 3 o 01 O TJ cu cu 01 4-1 A **<br />

XI cfl o. o 4-1 cfl 1 •H 4-1 TO 4H 3 CO cfl Q. o > XI -H 4-1 9 CO o 0) 4-1 o rH<br />

S s<br />

4-> CU tH vO 3 In O . 3 cfl o cj •H 1 4-1 4-1 CO iH 9 O o o cu 4-1 3 3 Tj cfl<br />

l-l rH xi 1—1 o 4-1 CN 4-1 cr « 00 IH CO in 4J Q 4-1 o 3 a 3 o. Ph TO 4-1 o cu 4-1 3<br />

TJ 3<br />

cu 4J cr-* M 1—1 3 cu a cu o o •H cd m 4-1 X 3 CU >-. iH 4H<br />

o rH l-l cfl C cfl M 4-> 4-1 CJ o c 3 rH CO X In CO XI •H O Q 4-1 •H In B cj TO<br />

a<br />

cfl<br />

O. TO 01 G 3 rH cfl CJ 3 CO cfl 1-4 iH In O CU 4J >> CJ 4-1 In 1 cd •H cd cj<br />

3 cfl<br />

a cj o o PQ l-l cfl cfl >i 4-1 TJ cu u cu CJ > cfl X » CO TO cfl 4-1 > 3 CU<br />

CJ cu tH 4-1 4J O rH rH TO CO CU 9 3 9 < 1 4-1 >> iH CU 01 3 o cr i_> a" 3 4n Xi<br />

Q 4J O 4_l c G 4-1 PQ Oh TJ O Q o o oo Mfl >> XI o m cu d CU O TO cfl +J<br />

CO CN 3 cu o cfl 3 CU •H o. a 4-1 m 3 TJ CU In 4J 4-1 CJ CM T3 In •H CO<br />

4-J >1 rH Xi XI •H rH I-l c 3 O XI > rH CN H cu 4J 4J 01 cfl 1 cfl In CO CO<br />

B cfl<br />

rH CO •H 4J 4-1 o. cu o O -H 4-1 o 4H • cu o u CU 4-> T-I 4-1 4-1 0) >1 O In cu<br />

XI<br />

o cfl l-l cfl 9 •H a 4J 1-4 O CO > > rJ 3 4-1 cd 3 4-> >1 cfl > In 01 4H cu CU X 05<br />

> 9<br />

>1 4-1 o 4-> G O 4J a cj 3 Oh TJ •H 1 o TJ X 3 cfl <br />

1<br />

CO 3<br />

U MH CO 4J to o o. cfl o cu 3 CU cfl In O •"-) o X •H 4-J Cfl cu >1 o trH<br />

o cu o •H 4-1 CJ 4-1 cfl CO cj O TJ CN cfl CO 4-1 - cu rH 3 > CXI rH rH Oj >i 00 In<br />

ui 4J -d tH cfl B cu CO o •H 1-4 rH rH a cu CO X 4-1 •H o rH Oj TO TH o<br />

M<br />

CN 4-1 CO cu o > CU u 3 cu •H cu 4-1 4-> 3 X -Sri "3 TO<br />

Cl, (_; CO 4H<br />

cfl 4-1 J TJ 9 00 CJ -H cfl T3 O. Jri CO O I-i TJ CU 01 In rH •H Cfl cfl CJ 3 3 3 (H TO CU o<br />

,3<br />

4H X CO cu o c u 3 CJ 4-1 CO o •H XI X! cu X 3 4H rH O. CO cfl 9 TO TO TJ Tj TJ<br />

CU<br />

o •H 4-1 a. tH U T3 00 rH CU o •H 4J > H H 4-1 •H 3 O Oh cfl rH o ^ cu In 4-J<br />

CJ CO cfl S-l o c O I-i rH 3 cfl O o 4-1 CO CJ PQ cj u —1 >1 3 X cd cd In s<br />

CO Q C •H rH 3 4H >-, •H 3 iH CJ 3 a l-l cfl CO u >, u •H • PQ •• 4J cfl 4-1 3 tH In .<br />

CO o CJ o XI rH l-l •H 4H CO o. . . X o CU 3 O c 3 O0T3 4-J iH CJ 00 4H xi CU TO<br />

o 4J CJ o u I-i o. 3 I-l >1 Cfl CJ 4J —1 O. X cd o o o CU cu<br />

rS CJ M cu o W X 4-J<br />

l_J rH CO 4J TJ CU O. T3 CO CN CU l-l Q o cu . 4-1 4-1 U •H •H -H 4J X cd TO 0) 4H 0) 4-1 rH<br />

o a CO c CU 9 xi TJ O 4-1 1-4 TO CO TO 00 •H TO O O CU 4-1 4-1 CO 4-1 4-1 Oh 0) rH Cd 4-1 u o o<br />

> cu cfl o TO O TO 4-1 cfl O 3 cu a 4-i rH 3 iH C 4J s CJ co u 3 cd •H X co 3 ><br />

C"> 1 4J a 3 Oj cu o O. Cu CU iH cfl m cu 3 cfl 3 O cu 4-1 Q CO In CO u In cfl cu In 0)<br />

. O CO cu TJ CO rH CU a 4-1 3 O rH 4-1 •H O- •r-l CO XI o CU cu rH TJ > X o<br />

s<br />

00 u~l >i X cu cu CO rH XI o CO co 3 TJ 4J X 0) M a 3 4-J X 4H TJ >1 4-1 •H 01 01 9 4-1 -H<br />

CN CO 4J TJ Xi CU 3 l-l a *-' CJ 3 >1 rH CO CO X O In rH •H -3 rH 01 •H In 4-1 cfl In o CM<br />

•H TJ O o 5) 3 co 3 3 m h 4-1 In CU O 0) o CO > cu cfl > 01 0) On MH<br />

4J XI T3 > 4-1 •H 9 4J 4-> * CU o •H O CU . 4-1 9 U . 4H oo > TO •H o U X cd 0) X o 4H<br />

x cj c o o > cfl TO S XI u<br />

9 3 3 m CN O 4J XI o 3 cu TO In 4-1 3 4J<br />

o<br />

00 CO cfl u 3 O TJ I-l >i o 4-1 M &2 CU -H o • 4J O- C o. o o a cfl o. cd 4-1 CO iH X 3<br />

•H W Oj M 3 cu CO o CU In 00 00 •H O cd CO rH m o X 0Q •H In 00 3 3 cu<br />

M<br />

cu<br />

TJ Oh CO 3 l-l A cu 4-1 CU t: 1 TJ X^<br />

In CO O CN a<br />

§B ° § : 3 01 3 iH cu o 00<br />

In CO rH cu X) 1-4 X 4-1 O CU u cu CJ CU 00 o In CU 3 3 00 CU X TJ cfl<br />

cu • cu a 3 a co 00 CU CO cu 4-1 cfl 4-1 O 4J cO rH TJ cd rH O. CO X 00 4J In 4-1 4-1 rH 4-1<br />

l-l 4-1 00 cu o CU 3 1 1-4 3 TJ xi m 4-1 4J CO cu X CU 00 In In cu iH TO g CU tH o rH<br />

2<br />

cfl S l-l 4-1 3 4-1 O l-l IH O l-l 4-1 o cfl O iH cfl 3 3 cd cd rH Cfl tH TO >. 9 X X 3 TO o o<br />

cfl cfl TO TO -H o CU iH o o O 4H XI B rH >iH O iH O o, cd rH i 0) CO IH V 4-1 3 CO CJ ><br />

CU rH .3 >iTJ ;>. 4J 4J 4H 4-1 CJ Q X >iX 4-1 00 O. 0) TJ<br />

U 0-i CJ CO G CO o o CU CO cu XI TJ 4-1 TJ CU 3 4H rH 00 O G O- 4-1 3<br />

cu cfl c a 1-4 CJ 1-4 CJ 4-1 3 •H CU In TJ •H O CL C 3 4-1 •H 3 TO 0) o<br />

XI M >1 >» CJ 3 O. tH cfl rH CO 3 IH Cfl CU O. 9 •H In CO r>ix •H<br />

H cfl M l-l TO a 4h TJ 3 TO w o 3 m •H TJ a 3 o TJ < 3 CO EH 4-><br />

cu cu cu TJ cu 4J 3 4-1 > TO CU CO rH cu cu co -o cu T3 X 3<br />

rH 4-) 4-1 l-l 4J rH l-l c a 3 1 3 X 4H TJ Oh 4-1 4J 4J CJ CJ M X<br />

CJ 4-1 4-1 cfl rH O 1-4 co a cu O O CJ cu eg Oj TO TO In 3 01 M TH CJ •H<br />

3 cfl cfl O O l-l cu rH O > m in cd U O 3 •H >i O XI In 3 X cu In<br />

55 XI Xi XI > 4-1 4-1 o. cj cu CN 4-1 cu an CO rH TO 14H CO a CJ 5 cc 4-J


69<br />

Table 8.1 <strong>Unit</strong> preferred system loads<br />

1. Containment Isol<strong>at</strong>ion panel<br />

2. Feedw<strong>at</strong>er Control panels<br />

3. Reactor Manual Control panel<br />

4. Drywell Ventil<strong>at</strong>ion and Reactor Building Closed<br />

Cooling W<strong>at</strong>er System Control panel<br />

5. Feedpump Turbine Control panels<br />

6. Rod Position Inform<strong>at</strong>ion System<br />

7. EHC Control <strong>Unit</strong><br />

8. <strong>Unit</strong> Computer and Rodworth Minimizer panels<br />

9. Reactor W<strong>at</strong>er Cleanup panel<br />

Table 8.2 Major unit 250-volt DC loads<br />

1. Turbine Building Distribution Board<br />

2. 480-volt Shutdown Board Control Power<br />

3. Emergency DC Lighting<br />

4. <strong>Unit</strong> Preferred AC Motor-Gener<strong>at</strong>or<br />

5. Circuit Breaker Board 9-9 (Feedpump Turbine<br />

Controls)<br />

6. Reactor Motor-Oper<strong>at</strong>ed Valve Boards<br />

a) Primary Relief Valve DC Solenoids<br />

b) Main Steam Isol<strong>at</strong>ion Valve DC Solenoids<br />

c) Recircul<strong>at</strong>ion Motor-Gener<strong>at</strong>or Set Emergency Oil<br />

Pumps<br />

d) Backup Scram Valves<br />

e) RHR Shutdown Isol<strong>at</strong>ion Valves<br />

f) Engineered Safeguards Logic Power Supplies<br />

g) HPCI System Controls, Valves, and Auxiliaries<br />

h) RCIC System Controls, Valves, and Auxiliaries


70<br />

"The engineered safeguards systems th<strong>at</strong> are sup<br />

plied from the 250 volt DC system shall be designed to<br />

oper<strong>at</strong>e <strong>at</strong> a minimum of 200 volts."<br />

It has previously been estim<strong>at</strong>ed5 th<strong>at</strong> under the less severe con<br />

ditions of a <strong>St<strong>at</strong>ion</strong> Blackout, with all unit b<strong>at</strong>teries avaiable, and as<br />

suming prudent actions by a well-trained oper<strong>at</strong>or to conserve b<strong>at</strong>tery po<br />

tential by minimizing DC loads, the necessary 250 volt DC power for HPCI<br />

or RCIC system oper<strong>at</strong>ion would remain available during the first four to<br />

six hours of a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

In summary, it is reasonable to expect th<strong>at</strong> control can be maintained<br />

over reactor vessel pressure and w<strong>at</strong>er level <strong>at</strong> each of the <strong>Browns</strong> <strong>Ferry</strong><br />

<strong>Unit</strong>s during a <strong>St<strong>at</strong>ion</strong> Blackout for as long as the 250 volt DC power re<br />

mains available. This period will depend on the oper<strong>at</strong>or's ability to<br />

conserve the unit b<strong>at</strong>tery potential by minimizing the DC loads, but is ex<br />

pected to last from four to six hours.* During this period the oper<strong>at</strong>or<br />

may have to take other actions to maintain the operability of the HPCI and<br />

RCIC systems as -Hscussed in subsection 8.1.<br />

*A b<strong>at</strong>tery life of seven hours is considered in Appendix G.


71<br />

9.0 ACCIDENT SEQUENCES RESULTING IN CORE MELTDOWN<br />

9.1 Introduction<br />

This section deals with the various accident sequences which might<br />

occur during a complete <strong>St<strong>at</strong>ion</strong> Blackout (CSB) <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear<br />

Plant which can lead to core meltdown.18 Event trees are presented for<br />

wh<strong>at</strong> are considered to be the six most probable sequences. The character<br />

istics and event timing for each of these sequences were determined by use<br />

of the MARCH code, and include consider<strong>at</strong>ion of the oper<strong>at</strong>or's role in re<br />

actor vessel pressure and level control. The progression of core damage<br />

and containment failure following core uncovery will be discussed in this<br />

section; an event tree for oper<strong>at</strong>or key actions in mitig<strong>at</strong>ing the accident<br />

progression will be discussed in Sect. 10.<br />

Of the sequences modelled by MARCH and presented in this section, the<br />

sequence TB'* is deemed to be most represent<strong>at</strong>ive of the events which<br />

would occur after core uncovery following a four-hour period during which<br />

the availability of DC power permitted reactor vessel level and pressure<br />

control. For this analysis, it is assumed th<strong>at</strong> no independent secondary<br />

equipment failures occur, and this sequence was chosen to serve as the<br />

basis for the fission product transport analysis discussed in Volume 2 of<br />

this report.<br />

9.2 Accident Phenomenology<br />

9.2.1 Accident Progression Resulting in Core Melt<br />

Upon a loss of offsite and onsite AC power, a number of reactor<br />

safety systems respond immedi<strong>at</strong>ely and autom<strong>at</strong>ically. First of all, a<br />

full load rejection (i.e., fast closure of the turbine control valves) oc<br />

curs, followed by the tripping of the recircul<strong>at</strong>ion pumps and the main<br />

condenser cooling w<strong>at</strong>er pumps. With the load rejection, the scram pilot<br />

valve solenoids are deenergized and the control rods start to move toward<br />

the fully inserted position. The main steam isol<strong>at</strong>ion valves (MSIVs) be<br />

gin to close, resulting in a rapid reactor vessel pressure increase. The<br />

se events are closely followed by a main turbine trip (i.e., closure of<br />

the turbine stop valves) and the tripping of the feedw<strong>at</strong>er turbines.<br />

After the autom<strong>at</strong>ic actions described above, core flow is provided by<br />

n<strong>at</strong>ural circul<strong>at</strong>ion and excess reactor vessel pressure is relieved by<br />

steam blowdown through the safety/relief valves (SRVs) into the pressure<br />

suppression pool. If any SRV fails to reclose after actu<strong>at</strong>ion, the reac<br />

tor vessel will continue to depressurize with an accompanying loss of<br />

*The nomencl<strong>at</strong>ure TB' follows th<strong>at</strong> used in the Reactor Safety<br />

Study,19 where T denotes a transient event and B' denotes failure to<br />

recover either offsite or onsite AC power within about 1 to 4 hours. In<br />

effect, TB' is a loss of decay he<strong>at</strong> removal (TW) sequence with the loss<br />

of both offsite and onsite AC power as an initi<strong>at</strong>ing event.


72<br />

w<strong>at</strong>er inventory similar to th<strong>at</strong> occurring in a small break LOCA. Accord<br />

ing to the Reactor Safety Study,ly the probability of a stuck-open re<br />

lief valve (SORV) event is estim<strong>at</strong>ed to be 0.10 with an error spread of 3.<br />

However, this estim<strong>at</strong>e was based upon consider<strong>at</strong>ion of three-stage SRVs<br />

such as those originally installed <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> site, with the<br />

two-stage relief valves of improved design which have a recently been in<br />

stalled <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Plant, the probability of a SORV event is sub<br />

stantially reduced and is estim<strong>at</strong>ed to be less than 10-z. The occur<br />

rence of a sequence involving a SORV, design<strong>at</strong>ed sequence TPB', is in<br />

cluded in the event trees of this section.<br />

The reactor vessel w<strong>at</strong>er level decreases rapidly during the initial<br />

moments of a <strong>St<strong>at</strong>ion</strong> Blackout due both to the void collapse caused by the<br />

increased pressure and to the w<strong>at</strong>er inventory lost through the SRVs. When<br />

the w<strong>at</strong>er level sensed by the wide range detector reaches the low w<strong>at</strong>er<br />

level setpoint (Level 2), the DC-powered HPCI and RCIC systems are auto<br />

m<strong>at</strong>ically initi<strong>at</strong>ed, with their turbine-driven pumps supplied by steam<br />

gener<strong>at</strong>ed by the decay he<strong>at</strong>. The HPCI and RCIC systems are assumed to re<br />

main oper<strong>at</strong>ional until the unit b<strong>at</strong>tery is exhausted <strong>at</strong> four hours into<br />

the <strong>St<strong>at</strong>ion</strong> Blackout. Following the loss of these injection systems, the<br />

reactor vessel level decreases until the core is uncovered about one hour<br />

l<strong>at</strong>er. Subsequently, the core begins to melt.<br />

The failure probability for HPCI has been estim<strong>at</strong>ed19 to be 9.8 x 10~2<br />

with an error spread of 3 and for RCIC has been estim<strong>at</strong>ed to be 8 x 10~2<br />

with an error spread of 3. The overall failure probability of both HPCI<br />

and RCIC to provide makeup w<strong>at</strong>er during the sequence TB', is design<strong>at</strong>ed<br />

TUB' and has been estim<strong>at</strong>ed19 to be 2 x 10-3 with an error spread of about<br />

4. The failure of both HPCI and RCIC together with a SORV occurrence is<br />

design<strong>at</strong>ed TUPB'.* Sequences TUB' and TUPB' have been included in the<br />

event trees of this section.<br />

9.2.2 Containment Failure Modes<br />

Any sequence resulting in core melt will eventually lead to contain<br />

ment failure if electrical power is not restored before the reactor vessel<br />

fails. According to the Reactor Safety Study,19 BWR containment failure<br />

could occur in the following c<strong>at</strong>egories:<br />

a — Containment failure due to steam explosion in vessel,<br />

0 — Containment failure due to steam explosion in containment,<br />

Y — Containment failure due to overpressure - release through reactor<br />

building,<br />

Y' — Containment failure due to overpressure-release direct to <strong>at</strong>mos<br />

phere,<br />

j — Containment isol<strong>at</strong>ion failure in drywell,<br />

e — Containment isol<strong>at</strong>ion failure in wetwell,<br />

5 — Containment leakage gre<strong>at</strong>er than 2400 volume percent per day.<br />

Containment failure by overpressuriz<strong>at</strong>ion was considered to be the<br />

dominant failure mode for a BWR inerted containment in the Reactor Safety<br />

*TUB' and TUPB' are in effect TQUV and TPQUV sequences with the<br />

loss of both offsite and onsite AC power as an initi<strong>at</strong>ing event.


lU S rMU<br />

TJ CU CU TJ u<br />

Xi B CU 3 3<br />

4-1 iH 3 4-1 CO<br />

CO rH 4-1 TO TO<br />

TJ<br />

o-> B<br />

rH Cd<br />

TJ Cfl<br />

rH TJ Mn<br />

CU 01<br />

•H TJ «<br />

>» iH<br />

> cu<br />

cu o<br />

X U tH<br />

4-> O.^<br />

TJ O<br />

CU<br />

4-> U<br />

Cfl 0)<br />

rH >1<br />

3 Cfl<br />

4-1 rH<br />

TO<br />

O U<br />

Oh 01<br />

B<br />

TO B<br />

Cfl tH<br />

9<br />

cu<br />

4J X<br />

3 M<br />

3<br />

S rH<br />

CO iH<br />

o. cu<br />

m<br />

cu<br />

Oj<br />

TO<br />

3<br />

4-> TJ<br />

rH B<br />

3 Cfl<br />

4H<br />

4-1<br />

CU<br />

a<br />

3<br />

TO<br />

CO<br />

Cfl<br />

B<br />

4-1 iH<br />

m<br />

CU TJ<br />

cd<br />

9 4J<br />

3<br />

cu cu<br />

XI TJ<br />

00 cu<br />

•H In<br />

x B<br />

rH CU<br />

3 CU<br />

CO X<br />

CU<br />

In >,<br />

rH<br />

CO rH<br />

CU Cfl<br />

TJ rj<br />

2 •H<br />

a In<br />

O<br />

CU 4-1<br />

In TO<br />

3 iH<br />

• rH XI<br />

r—i tH<br />

/-n cd cu<br />

CO 4H ><br />

•H CO<br />

CO In Xi<br />

Oj CU<br />

XI 4-1<br />

in 4J b<br />

r-. o oj<br />

- §<br />

X) tH<br />

B cd<br />

Cd 4-1<br />

3 cd<br />

•H iH r4<br />

o cd<br />

O. 4-> XI<br />

TJ fi CU<br />

BO,-*!<br />

cO cj cfl<br />

4-1 OJ<br />

TO CO rH<br />

CO<br />

0) O 0J<br />

XI U X<br />

00 4-1<br />

TJ<br />

B<br />

cd<br />

-H 3<br />

00 In •H<br />

CJ cd co<br />

C O Mn 01<br />

TO<br />

X * cd<br />

O TJ 01<br />

4-1 CU 3 rH<br />

X<br />

CU J 2<br />

3 r-s<br />

3 rH m cu<br />

•H rH oi xi<br />

4-1 CO XI 4-1<br />

3 3 4-1<br />

O -H o a<br />

B O Mn o<br />

01<br />

0) In<br />

> TJ O XI 4H<br />

01 H 4J 4-1<br />

u a<br />

TO<br />

O. O XI 0 01<br />

3 3 O CJ<br />

B<br />

« oi<br />

MH 3<br />

M Cr<br />

TJ 4J<br />

OJ<br />

CO<br />

CO<br />

m<br />

S<br />

cu _ o<br />

Oh O o<br />

4-1<br />

c<br />

§ -a<br />

MH 4-J Cd<br />

O B O<br />

CU iH<br />

M MH 4-1<br />

a<br />

O TJ<br />

cd<br />

O >i 3<br />

•H X O<br />

oo 3<br />

O cu<br />

rH U >,<br />

O 3 4-1<br />

•H rH T-I<br />

TJ -H ><br />

cd cd in<br />

m oi x<br />

><br />

CJ TO<br />

O<br />

0)<br />

TJ M<br />

rH CU<br />

3 9<br />

g<br />

In<br />

3<br />

CJ<br />

cu<br />

co<br />

TO<br />

cu<br />

In<br />

4-1<br />

in cd co<br />

4-1 •<br />

3 -i<br />

• o<br />

X! CJ B<br />

4-> CU<br />

oo i<br />

TJ fd XI<br />

rH 3<br />

3 TJ<br />

O 4-1 CU<br />

<br />

B<br />

• co<br />

cu cd u<br />

U iH<br />

0) rH X<br />

X tH 4-1<br />

Oh Cd<br />

TO MH TJ<br />

O 3<br />

a TJ Cd<br />

4-1 iH<br />

cfl 3 •><br />

O 00<br />

3 3<br />

u<br />

OJ<br />

%<br />

>»<br />

u<br />

TJ<br />

cu oi<br />

In rl<br />

xi xi<br />

4-1 CO<br />

Cd TO<br />

In 01<br />

01 U<br />

Oj O.<br />

a<br />

TO 4-1<br />

B 3<br />

O cd<br />

•H B<br />

4-1 iH<br />

u a<br />

0 o<br />

o-tj<br />

o<br />

In CU<br />

O.XI<br />

4-1<br />

CU<br />

In TO<br />

3 CO<br />

rH<br />

iH XI<br />

cd CU<br />

MH iH<br />

MH<br />

XI iH<br />

01 4J<br />

XI B<br />

CJ cu<br />

Cfl TJ<br />

CU iH<br />

In<br />

„ 3<br />

o. cu<br />

3 01<br />

•W X<br />

cfl<br />

O) TO<br />

X! cd<br />

X<br />

rH<br />

O 3<br />

O O<br />

O-T-l<br />

•U<br />

B cd<br />

O In<br />

iH O<br />

CO iH<br />

CO In<br />

OJ OJ<br />

In 4-1<br />

O- 01<br />

O.TJ<br />

3<br />

CO rH<br />

td<br />

r*. cu<br />

x co<br />

cu cu<br />

0) ><br />

4-1 CU<br />

CO rH<br />

3 cu cd<br />

O U Pj<br />

TO 3 S<br />

cd rH<br />

CU iH rH<br />

U cd CM<br />

cu<br />

X!<br />

O 4J cd<br />

4-i m<br />

TJ 4-1<br />

TJ 0) rH<br />

cd > -H<br />

01 0) MH<br />

rH .rl<br />

rH CU<br />

4-1 CU XI<br />

I<br />

CU B XI<br />

00 O rH 4J 4-1<br />

O 3 •• rH B O<br />

o<br />

CO CU CU 00<br />

cd TO 3<br />

CJ U<br />

cu cu<br />

cu cu<br />

cj a 10 tl WT)<br />

B CU 4-1 oi otj<br />

B 3 TO M CJ B<br />

• cu cr >,<br />

cd<br />

a S 0) TO TO 00 00<br />

CU B TO<br />

B BO<br />

4J iH<br />

•H iHCM<br />

TO Cd<br />

3 3 "To<br />

rS 4J 3 CU O O 4J 01<br />

CO S q a rH rH B O<br />

o .M 4-1<br />

cd TJ<br />

4J O CJ Cfl . O<br />

B cfl CU In Mn 4H O,<br />

cu rH rH In CU<br />

a cd 0Q 4-> 3 cu B<br />

O XI o u<br />

Cd 4-1 B co Oh 4-1 iH iH O<br />

CU iH o cd<br />

tl) N O<br />

In B iH &0 CJ In O<br />

4J iH 4J i 4H O.XI<br />

TO XI 4J X MH X 4J .8*<br />

CO 00 co x) O TJ CU<br />

TO<br />

00 tH B cu 4J 3 3<br />

X cu cd<br />

a * b o o<br />

>1 XI 4J<br />

cd 3 •H T-I<br />

X 00 4J TO<br />

01 >* O 4-1 CO<br />

TJ 3<br />

O 4-J rH X a o<br />

B -H In CU a CO 0) TO Cd rH<br />

cfl > O XI cu to M In O.<br />

4J rH XI iH cd tH..<br />

cu cu X<br />

CO O<br />

4-1 TJ rH > 4-1 CU<br />

> 4J XI<br />

B cd 3<br />

CU B B O MH CO 3 XI<br />

X tH cd tH O iH •* %<br />

4-1<br />

cu >n 3 cu<br />

^ -5<br />

TO m 3 01 01 3 rHCM O 4-1<br />

MH 0J o CJ In TJ X < Oj TO<br />

O XI Oh b B 3 OOM 3<br />

B -h OJ III 01 H Q o<br />

. a •H 3 co In X 2; TO 4J<br />

4-1<br />

cr cu 3<br />

B<br />

iH CU 0» >> CU U.<br />

CU CO o cu<br />

CJ In X TJ OjiH X •H 3<br />

CO 3 3<br />

4J TO TJ<br />

OhiH O 4-1<br />

4H O Cd o<br />

cd iH 4-1 CO<br />

4-1 H CU<br />

CJ Cfl<br />

4-1 TO O. In<br />

MH TJ TO Cd C TJ 4-1 X 3<br />

B B iH O 01 C B 0) rH<br />

O •» 3 .3 CO 4-1 3 CU •H<br />

•H m O 4J cd g O S 4-1 Cd<br />

4-1 cu<br />

cu<br />

C MH<br />

Oh > B 01 3<br />

CU<br />

In CU S -H rH tj<br />

rH 4-1<br />

O 9 CU X<br />

O fi<br />

CO O 01 TJ cd cu<br />

•H 01<br />

x W X 0) In m cj x a<br />

cd<br />

In OJ 3-<br />

CU CU OnrH<br />

> TJ OH ><br />

Cfl iH fi Cd rH<br />

X) CO<br />

3 O<br />

B<br />

§<br />

B<br />

•H<br />

cd<br />

4-1<br />

B<br />

• o<br />

> CJ<br />

TJ<br />

3 OJ<br />

4-> XI<br />

TO H<br />

§ cd<br />

N<br />

r>» in<br />

rH In<br />

XI 3<br />

00 TO<br />

•H TO<br />

CU<br />

In<br />

O.<br />

U<br />

OJ<br />

><br />

O<br />

•2 °<br />

a tj<br />

01 4-1<br />

TO rH<br />

CO 01<br />

cd e<br />

01 01<br />

3<br />

TO Cd MH 01 CJ<br />

c§<br />

XI<br />

3 O<br />

4J X!<br />

Cfl<br />

01<br />

00 X X)<br />

-i In<br />

co<br />

. 01<br />

3<br />

On Oh O rH O<br />

O 01<br />

m TO Oh 3<br />

3 O<br />

rH TO<br />

iH CO<br />

Cd iH<br />

MH TJ<br />

H OJ<br />

n3<br />

4J<br />

CO<br />

r- fi<br />

01<br />

x:<br />

X XI<br />

CJ o<br />

OJ<br />

CO rl<br />

B<br />

o<br />

CJ<br />

4-1<br />

cd<br />

0 o<br />

X)<br />

CU<br />

In<br />

01<br />

TJ<br />

•H<br />

CO<br />

3<br />

O<br />

CJ<br />

/"N Tj<br />

< r-j<br />

On 3<br />

W O<br />

w 3<br />

In<br />

O<br />

XI<br />

TO<br />

cu<br />

3<br />

•H<br />

TO U<br />

rH X3<br />

cd cj<br />

cu o<br />

TO O<br />

In 3<br />

O<br />

MH TJ<br />

B<br />

•> cd<br />

TO cd<br />

OJ MH<br />

O<br />

In MH<br />

O O<br />

Mn<br />

01<br />

0) CO<br />

. co cd<br />

TO<br />

cd o<br />

Oj<br />

01 01<br />

TO T3<br />

3<br />

01<br />

X<br />

TO<br />

CO<br />

01<br />

In<br />

O.<br />

Oj<br />

3<br />

TO<br />

4-1 01<br />

O XI<br />

Cd 4-1<br />

In<br />

MH fi<br />

•H<br />

01<br />

00 TJ<br />

m cu<br />

Cfl 4-1<br />

o<br />

XI<br />

TO<br />

o<br />

m<br />

PQ<br />

TJ<br />

cu<br />

CO<br />

3<br />

. cd<br />

CJ<br />

XI<br />

4-1<br />

cu<br />

TJ<br />

X<br />

0 01<br />

4-i m<br />

o<br />

01 MH<br />

3 oi<br />

tj x<br />

•H Cfl<br />

1<br />

X<br />

00 0)<br />

dX •cl 4-><br />

01 TJ<br />

> 0><br />

•H 00<br />

TO In<br />

to cd<br />

OJ x<br />

CJ CJ<br />

X co<br />

0) iH<br />

TJ<br />

X<br />

cj cu<br />

•H m<br />

XI cd<br />

3<br />

co<br />

B cu<br />

•H rH<br />

X<br />

TO T-I<br />

0) TO<br />

CJ C<br />

C CU<br />

01 TJ<br />

3 B<br />

cr o<br />

01 CJ<br />

TO<br />

fl) B<br />

3 Oi<br />

a<br />

01 01<br />

X 00<br />

4-> B<br />

•H<br />

•> Oh<br />

oi a<br />

a -h<br />

•H<br />

4J 4-1<br />

01<br />

MH Tl<br />

O<br />

a<br />

TJ Cd<br />

o cu<br />

•H 4-1<br />

In TO<br />

CU<br />

O. 4h<br />

O<br />

CJ 4n<br />

O<br />

rH TJ<br />

rH B<br />

> cy<br />

rH Pi<br />

01<br />

4-1 01<br />

cd x:<br />

a 4-><br />

•H<br />

X fi<br />

0 iH<br />

m<br />

Oh OJ<br />

Oj In<br />

cd 3<br />

rH<br />

01 iH<br />

In cd<br />

3 MH<br />

TO<br />

TO 4-1<br />

CU 3<br />

In OI<br />

Oh a fi<br />

CO iH<br />

cd<br />

4-1 4-1<br />

cd c<br />

o<br />

m u<br />

3<br />

CJ In<br />

CJ O<br />

O MH<br />

3 01<br />

cd W fi<br />

MH tH<br />

01 Cfl<br />

4J X 4J<br />

C 4-i B<br />

CU O<br />

a oo o<br />

fi 3<br />

H H CJ<br />

cd co X<br />

4-13 4-1<br />

n cfl<br />

3 4J<br />

•H<br />

TO<br />

TJ CO<br />

01 01<br />

In rH<br />

3<br />

U 01<br />

CJ X<br />

O<br />

TJ<br />

CU rH<br />

M 3<br />

cd cd<br />

4-1 TO<br />

B<br />

4-1 OJ<br />

X TJ<br />

00 B<br />

•H O<br />

a a<br />

X 4-1<br />

•H -H<br />

TJ fi<br />

B -H<br />

CU<br />

o. cu<br />

c*x<br />

< 4-1<br />

rH < CU<br />

3 -- c<br />

-H Oh 0<br />

3 01<br />

4-1 TO<br />

0) O<br />

3 XI<br />

4-1<br />

CU<br />

X! 3<br />

U g<br />

cd cd<br />

x<br />

H<br />

CJ<br />

iH<br />

U<br />

4-1<br />

CJ<br />

CU<br />

O 3<br />

O !H,<br />

cu<br />

co xi<br />

4-1 4-1<br />

3<br />

3 O<br />

0 4-1<br />

a s<br />

cd iH<br />

B<br />

o<br />

rH iH Q cd<br />

0)<br />

X<br />

0) O<br />

XI 4-J •<br />

H rH<br />

CO rH<br />

rH Cd<br />

• cd 3<br />

cu cu<br />

In CO 4J<br />

in a<br />

TJ<br />

In 0><br />

13 §<br />

TO CO<br />

rH 0><br />

00 TJ<br />

S3<br />

cu I m<br />

I X cu en<br />

0) 4J In rH<br />

X O.V-T<br />

I<br />

3<br />

O<br />

CJ<br />

X4<br />

3 o<br />

•H<br />

cu<br />

X<br />

TO<br />

CO<br />

c<br />

cd<br />

cu<br />

4-1 a<br />

4H 0)<br />

o -o<br />

Q<br />

I<br />

cd<br />

u<br />

4-1<br />

cu<br />

B<br />

01<br />

Oh<br />

TJ<br />

a CU<br />

O<br />

rH U<br />

rH MH<br />

cu I<br />

xi cd<br />

cu<br />

00<br />

JS<br />

cd<br />

CU<br />

rH m<br />

rH 0)<br />

01 X<br />

CO<br />

CJ iH<br />

•H rH<br />

00 01<br />

I<br />

m<br />

h I<br />

OJ 0)<br />

4-1 T3<br />

T-)<br />

B OJ<br />

0) CO<br />

cu cd<br />

X O)<br />

rH<br />

01 OJ<br />

> u<br />

cd<br />

XI 4J<br />

o<br />

TJ fi<br />

rH<br />

3 01<br />

O u<br />

9 O<br />

MH<br />

TO 01<br />

4-> U<br />

CJ CU<br />

3 X!<br />

XI 4J<br />

O<br />

In tj<br />

Oh 0<br />

cd<br />

B<br />

O rH<br />

•H O<br />

TO O<br />

TO O.<br />

•H<br />

MH B<br />

O<br />

I XI<br />

OJ rH<br />

TJ 3<br />

o<br />

rS 3<br />

X<br />

00<br />

01 B<br />

U tH<br />

xi -u<br />

rH Cd<br />

iH 01<br />

co xi<br />

Mn In<br />

CU<br />

><br />

B o<br />

OJ<br />

a o<br />

B 4-><br />

•H<br />

cd 01<br />

4-1 3<br />

B TJ<br />

O<br />

U CO<br />

rH<br />

MH Cd<br />

O OJ<br />

TO<br />

cu<br />

TJ fi<br />

2 a -H °<br />

4-1<br />

TJ CO<br />

OJ In<br />

4-> 4-1<br />

cfl 01<br />

m<br />

O<br />

x r>*<br />

4-1 4-1<br />

01<br />

TO Mn<br />

to cd<br />

oi co<br />

3 CO<br />

2 TJ<br />

3<br />

CO<br />

c<br />

o<br />

OCT)<br />

TJ<br />

01<br />

In<br />

(U<br />

TJ<br />

In<br />

cd<br />

TO<br />

CO<br />

CU<br />

CJ<br />

CU<br />

fi


74<br />

9.3 Event Trees<br />

9.3.1 Event Trees for Accident Sequences Resulting in Core Melt<br />

It has been concluded in this study th<strong>at</strong> the sequence of events dur<br />

ing a prolonged complete <strong>St<strong>at</strong>ion</strong> Blackout (CSB) <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nu<br />

clear Plant (BFNP) would most probably be described by one of the follow<br />

ing titles:<br />

1. CSB + HPCI/RCIC (TB')<br />

2. CSB + HPCI/RCIC + SORV (TPB')<br />

3. CSB + Manual RCIC & SRV (TyB')<br />

4. CSB + Manual RCIC & SRV + SORV (TVPB")<br />

5. CSB + No HPCI/RCIC (TUB')<br />

6. CSB + No HPCI/RCIC + SORV (TUPB')<br />

As indic<strong>at</strong>ed in this listing, a stuck-open relief valve (SORV) corresponds<br />

to a small break LOCA. The terminology "Manual RCIC & SRV" refers to the<br />

assumption th<strong>at</strong> the oper<strong>at</strong>or controls level and pressure by remote-manual<br />

oper<strong>at</strong>ion of the RCIC system and the relief valves, respectively. The<br />

phrase "No HPCI/RCIC" means th<strong>at</strong> both of these w<strong>at</strong>er-injection systems are<br />

assumed to be unavailable due to mechanical failure.<br />

The event tree identifying these six accident sequences is shown in<br />

Fig. 9.1. Sequence No. 1, traced by the dotted line in this figure, is<br />

the sequence TB' which involves no independent secondary equipment fail<br />

ures and was selected as the basis for the fission product transport anal<br />

ysis discussed in Volume 2. Other possible but much less likely sequences<br />

such as failure of reactor scram are shown on Fig. 9.1 but were not con<br />

sidered in this study.<br />

9.3.2 Core Damage Event Tree<br />

Without restor<strong>at</strong>ion of offsite or onsite AC power and with the con<br />

sequent inevitable loss of DC power, any of the numbered sequences shown<br />

on Fig. 9.1 will lead to core uncovery and subsequent core melting, reac<br />

tor vessel failure, and corium-concrete interaction. A tree for the<br />

events subsequent to core uncovery is shown in Fig. 9.2, with the p<strong>at</strong>h<br />

used for the fission product transport analysis of Vol. 2 identified by a<br />

dotted line.<br />

9.3.3 Containment Event Tree<br />

A containment event tree for the occurrences following core melt is<br />

given in Fig. 9.3. The particular p<strong>at</strong>h which has been chosen for the fis<br />

sion product transport studies is again indic<strong>at</strong>ed by the dotted line p<strong>at</strong>h.<br />

It should be noted th<strong>at</strong> if AC power is restored after core, melt, but<br />

before a failure of the reactor vessel occurs, the low-pressure Emergency<br />

Core Cooling Systems (ECCS) would function and a breach of the containment<br />

in the drywell or wetwell areas may be averted.


INITIATING EVENT<br />

LOSS OF OFFSITE<br />

AND ONSITE<br />

ac POWER<br />

YES<br />

A<br />

V<br />

NO<br />

SYSTEM<br />

AUTOMATIC<br />

RESPONSES<br />

r-<br />

I<br />

STUCK OPEN<br />

RELIEF VALVE<br />

HPCI AND<br />

RCIC<br />

OPERABLE<br />

MANUAL SRV<br />

DEPRESSURIZATION<br />

WITHIN 15 min.<br />

LOSS OF dc POWER -<br />

HPCI/RCIC INOPERABLE<br />

ORNL-DWG 81-8164A ETD<br />

SEQUENCE CONSEQUENCE<br />

•© ITVPB') CORE MELT<br />

POTENTIAL DELAYED<br />

CORE DAMAGE<br />

(?) (TPB'l CORE MELT<br />

POTENTIAL DELAYED<br />

CORE DAMAGE<br />

.(6) (TUPB) CORE MELT<br />

•(5)


INITIATING EVENT -<br />

CORE UNCOVERY<br />

YES<br />

REACTOR VESSEL<br />

DEPRESSURIZED<br />

dc POWER RESTORED<br />

BEFORE EXTENSIVE<br />

CORE DAMAGE -<br />

HPCI/RCIC OPERABLE<br />

OFFSITE ac POWER RESTORED<br />

BEFORE EXTENSIVE<br />

CORE DAMAGE-<br />

LOW PRESSURE ECCS<br />

OPERABLE<br />

dc POWER RESTORED<br />

AFTER SIGNIFICANT<br />

CORE MELT, BUT<br />

BEFORE VESSEL<br />

FAILURE -<br />

HPCI/RCIC OPERABLE<br />

OFFSITE ac POWER RESTORED<br />

AFTER SIGNIFICANT<br />

CORE MELT, BUT<br />

BEFORE VESSEL<br />

FAILURE-<br />

LP ECCS OPERABLE<br />

Fig. 9.2 Core damage event tree.<br />

ORNL-DWG 81-8200 ETD<br />

OFFSITE ac POWER RESTORED AFTER VESSEL<br />

FAILURE - LP ECCS OPERABLE<br />

SLIGHT CORE DAMAGE,<br />

LITTLE OR NO CORE MELT<br />

CORE MELT, DEBRIS<br />

CONTAINED IN VESSEL<br />

CORE MELT, RPV<br />

FAILURE, NO CONCRETE<br />

ATTACK<br />

CORE MELT, RPV<br />

FAILURE, AND CONCRETE<br />

ATTACK<br />

SLIGHT CORE DAMAGE,<br />

LITTLE OR NO CORE MELT<br />

CORE MELT, DEBRIS<br />

CONTAINED IN VESSEL<br />

CORE MELT, RPV<br />

FAILURE, NO CONCRETE<br />

ATTACK<br />

CORE MELT, RPV<br />

FAILURE, AND CONCRETE<br />

ATTACK<br />

C*


INITIATING EVENT<br />

-CORE MELT<br />

YES<br />

A<br />

LARGE AMPLITUDE<br />

CONOENSTION<br />

OSCILLATIONS IN<br />

WETWELL<br />

T-QUENCHER<br />

FAILURE<br />

WETWELL<br />

RUPTURE<br />

FAILURE<br />

VESSEL<br />

FAILURE<br />

77<br />

DRYWELL DRYWELL<br />

EPA VENTING EPA FAILURE<br />

DRYWELL<br />

RUPTURE<br />

FAILURE<br />

Fig. 9.3 Containment event tree.<br />

ORNL-DWG 81-0201 ETD<br />

HIGH RELEASE (WETWELL FAILUREl<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

SOME RELEASE (DRYWELL VENTINGI<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

NO CONTAINMENT FAILURE<br />

NO VESSEL FAILURE. NO CONTAINMENT<br />

FAILURE<br />

HIGH RELEASE (WETWELL FAILUREl<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

SOME RELEASE (ORYWELL VENTING I<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

NO CONTAINMENT FAILURE<br />

NO VESSEL FAILURE, NO CONTAINMENT<br />

FAILURE<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

SOME RELEASE (DRYWELL VENTINGI<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

NO CONTAINMENT FAILURE<br />

NO VESSEL FAILURE. NO CONTAINMENT<br />

FAILURE<br />

VERY HIGH RELEASE IDRYWELL FAILUREl<br />

SOME RELEASE (DRYWELL VENTINGI<br />

VERY HIGH RELEASE (DRYWELL FAILUREl<br />

NO CONTAINMENT FAILURE<br />

— NO VESSEL FAILURE, NO CONTAINMENT<br />

FAILURE


9.4.1 MARCH computer code<br />

78<br />

9.4 Accident Sequences<br />

Detailed calcul<strong>at</strong>ions for the accident sequences have been performed<br />

with the MARCH computer code , version 1.4B. This version is based on<br />

version 1.4 <strong>at</strong> Brookhaven N<strong>at</strong>ional Labor<strong>at</strong>ory, but contains a different<br />

subroutine ANSQ for the decay he<strong>at</strong> power calcul<strong>at</strong>ions and modific<strong>at</strong>ions to<br />

the subroutine HEAD which were necessary to improve the prediction of ves<br />

sel failure time. 18<br />

In the MARCH code, the fission product decay he<strong>at</strong> source term is<br />

based on ANS Standard ANS-5.1 (1973)za which does not account for the<br />

decay of U-239 or Np-239. The new standard ANS-5.1 (1979) zl* provides<br />

decay parameters for U-239 and Np-239, but does not account for the decay<br />

power gener<strong>at</strong>ed from these or the numerous other heavy nuclides (actinides)<br />

which exist in power reactors. The new subroutine ANSQ used in<br />

this study (Cf. Appendix B) is based on the actinide decay he<strong>at</strong> source in<br />

a BWR following a depletion of 34,000 MWd/t. The actinide he<strong>at</strong>ing calcu<br />

l<strong>at</strong>ions Zb were performed using the EPRI-CINDER code and include all sig<br />

nificant actinides from Tl-208 through Cm-246. Furthermore, the initial<br />

fission energy release from the fuel is assumed to last 3 seconds r<strong>at</strong>her<br />

than 5 seconds as used originally in the MARCH code. This has been found<br />

to yield better agreement with test d<strong>at</strong>a in implementing the REDY code <strong>at</strong><br />

GE.2b<br />

A comparison of MARCH calcul<strong>at</strong>ions for the sequence TB " as per<br />

formed by versions 1.4 and 1.4B are given in Figs. 9.4 through 9.11 for<br />

the time- dependence of (1) the maximum core temper<strong>at</strong>ure, (2) the w<strong>at</strong>ersteam<br />

mixture level, (3) the containment wall temper<strong>at</strong>ure, and (4) the<br />

containment volumetric leak r<strong>at</strong>e. It should be noted th<strong>at</strong> the times pre<br />

dicted by version 1.4B for core uncovery and core melt are less by approx<br />

im<strong>at</strong>ely 18 and 26%, respectively, and th<strong>at</strong> the maximum containment wall<br />

temper<strong>at</strong>ure is increased by more than 120%. Other comparisons have shown<br />

th<strong>at</strong> the 1.4B version produces results in better agreement with the core<br />

uncovery time calcul<strong>at</strong>ed by the RELAP4/Mod 7 Code for the sequence TUB "<br />

<strong>at</strong> INEL. 2/<br />

9.4.2 Accident progression sign<strong>at</strong>ures<br />

This section contains the accident progression sign<strong>at</strong>ures for the<br />

six most probable sequences following complete st<strong>at</strong>ion <strong>blackout</strong> (CSB).<br />

The early part of the plant transient characteristics follow th<strong>at</strong> con<br />

tained in the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant Final Safety Analysis Report.<br />

All other accident sign<strong>at</strong>ures have been based on the results calcul<strong>at</strong>ed by<br />

the MARCH computer code.13<br />

9.4.2.1 CSB + HPCI (TB'). The accident progression sign<strong>at</strong>ure for<br />

the sequence TB' is given in Table 9.1. This sequence has been chosen<br />

for the fission product transport studies presented in Volume 2.<br />

9.4.2.2 CSB + HPCI + SORV (TPB'). The accident progression signa<br />

ture for the sequence TPB' is given in Table 9.2. The SORV event has<br />

the same effect as a small break LOCA, ensuring th<strong>at</strong> the reactor vessel


3000.0<br />

2500.0-<br />

3 2000.0<br />

\-<br />

<<br />

cc<br />

H 1500.0<br />

UJ<br />

cc<br />

o<br />

o<br />

I 1000.0<br />

<<br />

2<br />

500.0-<br />

0.0<br />

0.0<br />

DECREASE FOLLOWING SCRAM<br />

50.0<br />

CORE UNCOVERY BEGINS<br />

CORE MELTING BEGINS<br />

dc POWER LOST<br />

1 —I 1 I<br />

100.0 150.0 200.0 250.0 300.0<br />

TIME (min)<br />

Fig. 9.4 Maximum core temper<strong>at</strong>ure (MARCH/MOD 1.4B).<br />

ORNL-DWG 81-8515 ETD<br />

I<br />

350.0 400.0


3000.0<br />

2500.0-<br />

LU<br />

3 2000.0<br />

<<br />

rr<br />

LU<br />

a.<br />

2<br />

h 1500.0<br />

UJ<br />

cc<br />

O o<br />

<<br />

1000.0<br />

500.0-<br />

0.0<br />

0.0<br />

DECREASE FOLLOWING SCRAM<br />

dc POWER LOST<br />

CORE UNCOVERY BEGINS<br />

CORE MELTING BEGINS<br />

T T 1 T T<br />

50.0 100.0 150.0 200.0 250.0 300.0<br />

TIME (min)<br />

Fig. 9.5 Maximum core temper<strong>at</strong>ure (MARCH/MOD 1.4)<br />

ORNL-DWG 81-8516 ETD<br />

350.0 400.0 450.0 500.0<br />

os<br />

o


12.0<br />

10.0<br />

3 8.0-<br />

><br />

UJ<br />

_J<br />

UJ<br />

cc<br />

6.0<br />

9 4.0-<br />

2<br />

<<br />

UJ<br />

k i<br />

tr<br />

UJ<br />

h-<br />

<<br />

2.0-<br />

0.0-<br />

-2.0-<br />

-4.0<br />

0.0 50.0<br />

T T<br />

100.0 150.0<br />

1<br />

200.0<br />

TIME (min)<br />

Fig. 9.6 W<strong>at</strong>er-steam mixture level (MARCH/MOD 1.4B)<br />

LOSS OF dc POWER<br />

BOILOFF BEGINS<br />

ORNL-DWG 81-8517 ETD<br />

CORE SLUMPS-<br />

—I 1 1<br />

250.0 300.0 350.0 400.0<br />

oo


12.0-1<br />

10.0<br />

1 8.0-<br />

><br />

UJ<br />

_l<br />

UJ<br />

cc<br />

6.0-<br />

r-<br />

* 4.0<br />

<<br />

UJ<br />

fc 2.0<br />

i<br />

cc<br />

UJ<br />

<<br />

5 0.0<br />

-2.0-<br />

LOSS OF dc POWER<br />

BOILOFF BEGINS<br />

-4.0 | | 1 I i 1 1 r<br />

T T<br />

0.0 50.0 100.0 150.0 200.0 250.0<br />

TIME (min)<br />

300.0 350.0 400.0 450.0 500.0<br />

Fig. 9.7 W<strong>at</strong>er-steam mixture level (MARCH/MOD 1.4)<br />

ORNL-DWG 81-8518 ETD<br />

CORE SLUMPS-<br />

oo<br />

t-o


1400.0<br />

— 1200.0<br />

«—<br />

Q<br />

O<br />

Z<br />

UJ<br />

cc 1000.0<br />

D<br />

r-<br />

<<br />

CC<br />

UJ<br />

O.<br />

2<br />

UJ 800.0<br />

r-<br />

-1<br />

_l<br />

<<br />

5<br />

r-<br />

Z<br />

UJ<br />

2 Z<br />

600.0<br />

<<br />

H<br />

Z<br />

o 400.0<br />

o<br />

200.0-<br />

0.0<br />

VESSEL BOTTOM HEAD FAILS<br />

T<br />

T 1 1<br />

100.0 200.0 300.0 400.0 500.0 600.0<br />

TIME (min)<br />

GROSS EPA FAILURE<br />

EPA VENTING<br />

I I<br />

700.0 800.0<br />

Fig. 9.8 Containment wall temper<strong>at</strong>ure (MARCH/MOD 1.4B).<br />

ORNL-DWG 81-8519 ETD<br />

—I 1^ 1<br />

900.0 1000.0 1100.0<br />

oo


600.0 -r<br />

£ 550.0-<br />

o<br />

o<br />

z<br />

cc 500.0-<br />

D<br />

r-<br />

< CC<br />

UJ<br />

a.<br />

uj 450.0<br />

<<br />

z 400.0<br />

UJ<br />

2<br />

z<br />

< r-<br />

o 350.0-<br />

VESSEL BOTTOM HEAD FAILS<br />

300.0 H 1 1 1 I 1 I i i 1 1 r<br />

0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1000.0 1100.0 1200.0<br />

TIME (min)<br />

Fig. 9.9 Containment wall temper<strong>at</strong>ure (MARCH/MOD 1.4)<br />

ORNL-DWG 81-8520 ETD<br />

HEATUP DURING<br />

CORIUM-CONCRETE<br />

REACTION<br />

oo


400.0<br />

350.0-<br />

"E 300.0-<br />

<<br />

QC<br />

*<br />

<<br />

UJ<br />

-1<br />

250.0<br />

o 200.0<br />

CC<br />

r-<br />

UJ<br />

2 Z><br />

_l<br />

o<br />

><br />

1-<br />

o<br />

o<br />

150.0<br />

100.0<br />

50.0-<br />

0.0-<br />

0.0 100.0 200.0 300.0 400.0 500.0 600.0<br />

TIME (min)<br />

Fig. 9.10 Containment leak r<strong>at</strong>e (MARCH/MOD 1.4B)<br />

ORNL-DWG 81-8521 ETD<br />

700.0 800.0 900.0 1000.0 1100.0<br />

00


E<br />

UJ<br />

400.0-1<br />

350.0-<br />

300.0<br />

r-<br />

<<br />

CC 250.0<br />

< LU<br />

_l<br />

o 200.0<br />

cc<br />

K-<br />

LU<br />

2<br />

-J<br />

O<br />

><br />

1-<br />

o o<br />

150.0<br />

100.0<br />

50.0-<br />

0.0 -J<br />

0.0 100.0<br />

ORNL-DWG 81-8522 ETD<br />

200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1000.0 1100.0 1200.0<br />

TIME (min)<br />

Fig. 9.11 Containment leak r<strong>at</strong>e (MARCH/MOD 1.4).<br />

oo<br />

o>


87<br />

Table 9.1<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + HPCI/RCIC<br />

(TB')<br />

Time<br />

(sec) Event<br />

0.0 Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure = 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure = 35°C (95°F)<br />

0.2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0.2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0.2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0.3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0.5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

1.0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

1.0 Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2.0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.


88<br />

Time<br />

(sec) Event<br />

3.0 Turbine trips off (turbine stop valves fully closed).<br />

3.5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5*0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Seven (7) out of thirteen (13) S/RVs start to open in<br />

response to pressure rise above the setpoint.<br />

5.2 W<strong>at</strong>er-steam mixture level recovers 0.51 m (20 in.)<br />

from the previous momentary 1.02 m (40-in.) drop.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 7 S/RVs are completely closed.<br />

15.7 Four out of 13 S/RVs start to open.<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

21.0 Narrow range (NR) sensed w<strong>at</strong>er level reaches low alarm<br />

(Level 4), i.e., 5.98 m (235.50 in.) above Level 0, or<br />

5.00 m (196.44 in.) above TAF.<br />

22.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure rises<br />

to 35.13°C (95.24°F) in response to the first S/RV<br />

pops.<br />

29.0 All 4 S/RVs are completely closed.


89<br />

Time<br />

(sec) Event<br />

29.7 Two out of 13 S/RVs start to open.<br />

47.0 All 2 S/RVs are completely closed.<br />

47.7 <strong>One</strong> out of 13 S/RVs starts to open.<br />

56.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxi<br />

m<strong>at</strong>ely 35.3°C (95.54°F).<br />

56.0 NR sensed w<strong>at</strong>er level reaches low level alarm (Level<br />

3), i.e., 5.50 m (216.00 in.) above Level 0, or 4.50 m<br />

(176.94 in.) above TAF.<br />

90.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxi<br />

m<strong>at</strong>ely 35.4°C (95.72°F).<br />

101.0 The S/RV is completely closed. The same S/RV contin<br />

ues to cycle on and off on setpoints throughout the<br />

subsequent cyclings of HPCI and RCIC injections.<br />

625 Wide range sensed w<strong>at</strong>er level reaches low w<strong>at</strong>er level<br />

setpoint (Level 2), i.e., 4.18 m (164.50 in.) above<br />

Level 0 <strong>at</strong> 2/3 core height, or 2.96 m (116.50 in.)<br />

above TAF.<br />

625 HPCI and RCIC systems are autom<strong>at</strong>ically turned on.<br />

The HPCI and RCIC turbine pumps are driven by steam<br />

gener<strong>at</strong>ed by decay he<strong>at</strong>. System auxiliaries are<br />

powered by the 250 V dc system.<br />

655 HPCI and RCIC flows enter the reactor pressure vessel<br />

<strong>at</strong> 315 Jt/s (5000 gpm) and 38 £/s (600 gpm), re<br />

spectively, drawing w<strong>at</strong>er from the condens<strong>at</strong>e storage<br />

tank.<br />

12.5 min. Narrow range sensed w<strong>at</strong>er level reaches Level 8 setpoint,<br />

i.e., 6.86 m (270.00 in.) above Level 0, or<br />

5.64 m (222.00 in.) above TAF.


Time<br />

(sec)<br />

12,>5 min.<br />

20 min.<br />

26..5 min.<br />

HPCI and RCIC trip off.<br />

90<br />

Event<br />

Drywell and wetwell temper<strong>at</strong>ures exceed 70°C (158°F) and<br />

42°C (108°F), respectively.<br />

Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint and<br />

HPCI autom<strong>at</strong>ically restarts. (RCIC does not autom<strong>at</strong>ically<br />

restart.)<br />

27.0 min. HPCI flow enters the RPV.<br />

29.0 min. Narrow range sensed w<strong>at</strong>er level reaches Level 8 setpoint and<br />

HPCI trips off again. The HPCI system, driven by steam gen<br />

er<strong>at</strong>ed by decay he<strong>at</strong>, turns on and off autom<strong>at</strong>ically between<br />

sensed Levels 2 and 8 until the b<strong>at</strong>teries run out.<br />

80 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell<br />

pressure exceeds 13.8 KPa (2.0 psi). The HPCI/ RCIC systems<br />

are not isol<strong>at</strong>ed.<br />

240 min. The HPCI pump stops when the b<strong>at</strong>teries run out.<br />

260 min. Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint.<br />

Drywell and wetwell temper<strong>at</strong>ures are 85°C (185°F) and 87°C<br />

(188°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 27.82 3.68 * 103 7.68 * 107 4.37 x 106<br />

Hydrogen 0 0 0 0<br />

302 min. Core uncovery time. Steam-w<strong>at</strong>er mixture level is <strong>at</strong> 3.58 m<br />

(11.73 ft) above bottom of the core.<br />

320 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 485°C (904°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 101°C<br />

(213°F) and 0.21 MPa (31 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 18.75 2.48 x io3 5.40 * 107 3.07 x io6<br />

Hydrogen 6.65 x io"7 8.80 x i(f5 3.34 1.90 x io"1


91<br />

Time<br />

(sec) Event<br />

340 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 821°C (1509°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 103°C<br />

(218°F) and 0.23 MPa (33 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 11.75 1.56 x 103 3.76 x IO7 2.14 x ify*<br />

Hydrogen 1.52 x io"3 2.00 x io"1 1.10 x io*1 6.25 x io2<br />

355 min. Core melting starts.<br />

389 min. W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

390 min. Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

392 min. The corium slumps down to vessel bottom.<br />

394 min. Debris starts to melt through the bottom head.<br />

426 min. Vessel bottom head fails, resulting in a pressure increase<br />

of 0.34 MPa (49 psia).<br />

426.04 min. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 1433°C (2611°F) initial<br />

ly. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are 1.05<br />

x IO7 and 1.95 x io' w<strong>at</strong>ts, respectively.<br />

503.27 min. Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 204°C (400°F) and start<br />

to vent through the primary containment <strong>at</strong> a leak r<strong>at</strong>e of<br />

118 SL/s (250 ft3/min).<br />

513.59 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s (lb/min) (w) (Btu/min)<br />

Steam 4.61 610 1.59 x io5 9052<br />

Hydrogen 0.11 15 0 0<br />

C02 1.01 133<br />

CO 2.35 311<br />

The leak r<strong>at</strong>e through the drywell penetr<strong>at</strong>ion seals is<br />

-3.04 x io1* jt/s (6.44 x 104* ft3/min).


92<br />

Time<br />

(sec) Event<br />

613 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (~14.7 psia)<br />

and temper<strong>at</strong>ures are 661°C (~1222°F) and 98°C (~209°F),<br />

respectively. The leak r<strong>at</strong>e through the containment failed<br />

area is ~2.96 x 101* A/s (~6.27 x io** ft3/min).<br />

695 min. Drywell and wetwell temper<strong>at</strong>ures are 623°C (1154°F) and 97°C<br />

(207°F), respectively. The leak r<strong>at</strong>e through the contain<br />

ment failed area is ~6.47 x io1* i/s (~1.37 x io5<br />

ft3/min).<br />

1028 min. Drywell and wetwell temper<strong>at</strong>ures are 614°C (~1138°F) and<br />

97°C (~207°F), respectively. The leak r<strong>at</strong>e through the<br />

containment failed area is ~1.34 x io3 l/s (~2.83 x<br />

IO3 ft3/min).


93<br />

Table 9.2<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + HPCI/RCIC + SORV (Small Break LOCA)<br />

(TPB')<br />

Time<br />

(sec) Event<br />

0.0 Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure - 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure - 35°C (95°F)<br />

0.2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0.2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0.2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0.3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0.5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

1.0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

1.0 Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2.0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.


94<br />

Time<br />

(sec) Event<br />

3.0 Turbine trips off (turbine stop valves fully closed).<br />

3.5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5.0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Seven (7) out of thirteen (13) S/RVs start to open in<br />

response to pressure rise above the setpoint.<br />

5.2 W<strong>at</strong>er-steam mixture level recovers 0.51 m (20 in.)<br />

from the previous momentary 1.02 m (40-in.) drop.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 6 S/RVs are completely closed. <strong>One</strong> S/RV is stuck<br />

open (SORV); this has the same effect as a small break<br />

LOCA of equivalent break area of 0.015 m2 (0.1583<br />

ft2).<br />

15.7 Four out of 13 S/RVs start to open.<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

21.0 Narrow range (NR) sensed w<strong>at</strong>er level reaches low alarm<br />

(Level 4), i.e., 5.98 m (235.50 in.) above Level 0, or<br />

5.00 m (196.44 in.) above TAF.


95<br />

Time<br />

(sec) Event<br />

22.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure rises<br />

to 35.13°C (95.24°F) in response to the first S/RV<br />

pops.<br />

29.0 All 4 S/RVs are completely closed.<br />

29.7 Two out of 13 S/RVs start to open.<br />

47.0 All 2 S/RVs are completely closed.<br />

47.7 <strong>One</strong> out of 13 S/RVs starts to open.<br />

56.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxi<br />

m<strong>at</strong>ely 35.3°C (95.54°F).<br />

56.0 NR sensed w<strong>at</strong>er level reaches low level alarm (Level<br />

3), i.e., 5.50 m (216.00 in.) above Level 0, or 4.50 m<br />

(176.94 in.) above TAF.<br />

90.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxi<br />

m<strong>at</strong>ely 35.4°C (95.72°F).<br />

101.0 The S/RV is completely closed. The same S/RV contin<br />

ues to cycle on and off on setpoints throughout the<br />

subsequent cyclings of HPCI and RCIC injections.<br />

625 Wide range sensed w<strong>at</strong>er level reaches low w<strong>at</strong>er level<br />

setpoint (Level 2), i.e., 4.18 m (164.50 in.) above<br />

Level 0 <strong>at</strong> 2/3 core height, or 2.96 m (116.50 in.)<br />

above TAF.<br />

625 HPCI and RCIC systems are autom<strong>at</strong>ically turned on.<br />

The HPCI and RCIC turbine pumps are driven by steam<br />

gener<strong>at</strong>ed by decay he<strong>at</strong>. System auxiliaries are<br />

powered by the 250 V dc system.<br />

655 HPCI and RCIC flows enter the reactor pressure vessel<br />

<strong>at</strong> 315 l/s (5000 gpm) and 38 l/s (600 gpm), re<br />

spectively, drawing w<strong>at</strong>er from the condens<strong>at</strong>e storage<br />

tank.<br />

12.5 min. Narrow range sensed w<strong>at</strong>er level reaches Level 8 setpoint,<br />

i.e., 6.86 m (270.00 in.) above Level 0, or<br />

5.64 m (222.00 in.) above TAF.<br />

12.5 min. HPCI and RCIC trip off.


96<br />

Time<br />

(sec) Event<br />

20 min. Drywell and wetwell temper<strong>at</strong>ures exceed 70°C (158°F) and<br />

50°C (122°F), respectively.<br />

Mass and energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 35.04 4.63 x io3 9.87 x io7 5.61 x io6<br />

Hydrogen 0 0 0 0<br />

25.5 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell pres<br />

sure exceeds 13.8 KPa (2.0 psi). The HPCI/ RCIC systems are<br />

not isol<strong>at</strong>ed.<br />

26.5 min. Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint and<br />

HPCI autom<strong>at</strong>ically restarts. (RCIC does not autom<strong>at</strong>ically<br />

restart.)<br />

27.0 min. HPCI flow enters the RPV.<br />

29.0 min. Narrow range sensed w<strong>at</strong>er level reaches Level 8 setpoint and<br />

HPCI trips off again. The HPCI system, driven by steam gen<br />

er<strong>at</strong>ed by decay he<strong>at</strong>, turns on and off autom<strong>at</strong>ically between<br />

sensed Levels 2 and 8 until the b<strong>at</strong>teries run out.<br />

240 min. The HPCI pump stops when the b<strong>at</strong>teries run out.<br />

261 min. Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint.<br />

Drywell and wetwell temper<strong>at</strong>ures are 100°C (212°F) and 96°C<br />

(205°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 10.45 1.38 x io3 2.92 x io7 1.66 x io6<br />

Hydrogen 0 0 0 0<br />

315.07 min. Core uncovery time. Steam-w<strong>at</strong>er mixture level is <strong>at</strong> 3.53 m<br />

(11.58 ft) above bottom of the core.<br />

321.5 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 211°C (412°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 106°C<br />

(223°F) and 0.24 MPa (35 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 22.66 3.00 x io3 6.33 x io7 3.60 x io6<br />

Hydrogen 0 0 0 0


97<br />

Time<br />

(sec) Event<br />

384 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 1046°C (1915°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 1148C<br />

(237°F) and 0.28 MPa (41 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 2.46 325.0 8.30 x io6 4.72 x IO5<br />

Hydrogen 0.021 2.78 1.14 x io5 8.19 x io3<br />

387.77 min. Core melting starts.<br />

418.77 min. W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

420.77 min. Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

421.67 min. The corium slumps down to vessel bottom.<br />

422.12 min. Debris starts to melt through the bottom head.<br />

515.18 min. Vessel bottom head fails, resulting in a pressure increase<br />

of 0.34 MPa (49 psia).<br />

515.20 min. Debris starts to boil w<strong>at</strong>er from containment floor.<br />

515.20 min. Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 204°C (400°F) and start<br />

to vent through the primary containment <strong>at</strong> a leak r<strong>at</strong>e of<br />

105 i/a (222 ft3/min).<br />

515.21 min. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 1771°C (3219°F) initial<br />

ly. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are 1.01<br />

x IO7 and 1.86 x IO7 w<strong>at</strong>ts, respectively.<br />

579.24 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s (lb/min) (w) (Btu/min)<br />

Steam 0.63 83.33 1.59 x io5 9052<br />

Hydrogen 0.22 29.10 0 0<br />

C02 2.08 275.13<br />

CO 4.63 612.44<br />

The leak r<strong>at</strong>e through the drywell penetr<strong>at</strong>ion seals is<br />

~2.53 x 105 i/s (5.35 x IO5 ft3/min).


98<br />

Time<br />

(sec) Event<br />

681.88 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (~14.7 psia)<br />

and temper<strong>at</strong>ures are 674°C (~1245°F) and 98°C (~209°F),<br />

respectively. The leak r<strong>at</strong>e through the containment failed<br />

area is ~3.61 x IO4 n/s (-7.65 x 10^ ft3/min).<br />

810 min. Drywell and wetwell temper<strong>at</strong>ures are 1006°C (1843°F) and<br />

97°C (207°F), respectively. The leak r<strong>at</strong>e through the<br />

containment failed area is ~3.10 x io1* SL/s (~6.57 x<br />

IO4 ft3/min).<br />

1128 min. Drywell and wetwell temper<strong>at</strong>ures are 591°C (~1095°F) and<br />

97°C (~207°F), respectively. The leak r<strong>at</strong>e through the<br />

containment failed area is ~1.27 x io3 X./s (~2.70 x<br />

103 ft3/min).


99<br />

is depressurized during core uncovery and melt. However, the pressure re<br />

mains high enough so th<strong>at</strong> the HPCI turbine can be oper<strong>at</strong>ed for as long as<br />

the b<strong>at</strong>tery lasts. Compared with the sequence TB', the SORV results in<br />

a ~30 min. delay in the core melt, ~90 min. delay in vessel failure, and<br />

~65 min. delay in the containment failure.<br />

9.4.2.3 CSB + Manual RCIC & SRV (TVB'). The accident progression<br />

sign<strong>at</strong>ure for the sequence TVB' is given in Table 9.3. In this sequ<br />

ence, it is assumed th<strong>at</strong> the HPCI system is inoperable. The oper<strong>at</strong>or remote-manually<br />

opens one SRV after 15 minutes of <strong>St<strong>at</strong>ion</strong> Blackout to de<br />

pressurize the vessel in order to lower the vessel temper<strong>at</strong>ure and to pre<br />

pare for use of the low pressure ECCS injection systems upon restor<strong>at</strong>ion<br />

of AC power. At the same time, the oper<strong>at</strong>or <strong>at</strong>tempts to maintain a con<br />

stant vessel w<strong>at</strong>er level by manually controlling the RCIC injection. It<br />

is noted th<strong>at</strong> the fluid loss through the SRV causes the core to become<br />

momentarily uncovered, but it refloods immedi<strong>at</strong>ely with the continued RCIC<br />

w<strong>at</strong>er injection. This short period of core uncovery is believed not to<br />

cause any core damage <strong>at</strong> th<strong>at</strong> stage.<br />

9.4.2.4 CSB + Manual RCIC & SRV + SORV (T„PB"). The accident pro<br />

gression sign<strong>at</strong>ure for the sequence TVPB' is given in Table 9.4. In<br />

this sequence, it is assumed th<strong>at</strong> an SORV event occurs <strong>at</strong> the beginning of<br />

the transient, and the oper<strong>at</strong>or remote-manually opens a SRV which causes<br />

the reactor vessel to depressurize <strong>at</strong> a faster r<strong>at</strong>e. Compared with the<br />

sequence TVB', the two sequences have produced very similar results<br />

with respect to the times of core melt, vessel failure, and containment<br />

failure.<br />

9.4.2.5 CSB + No HPCI/RCIC (TUB"). The accident progression signa<br />

ture for the sequence TUB' is given in Table 9.5. The events of this<br />

sequence as calcul<strong>at</strong>ed by MARCH have been compared with results from the<br />

RELAP4/MOD7 code2/ up to the time of core uncovery. With the modifica<br />

tions incorpor<strong>at</strong>ed in MARCH version 1.4B, the core uncovery times pre<br />

dicted by the two codes are in agreement.<br />

9.4.2.6 CSB + No HPCI/RCIC & SORV (TUPB"). The accident progression<br />

sign<strong>at</strong>ure for the sequence TUPB' is given in Table 9.6. This is the<br />

severest of the six <strong>St<strong>at</strong>ion</strong> Blackout sign<strong>at</strong>ures studied, and includes a<br />

prediction of core uncovery <strong>at</strong> 17 minutes after the initi<strong>at</strong>ing loss of AC<br />

power. The mitig<strong>at</strong>ing action which might be taken by the oper<strong>at</strong>or in re<br />

sponse to this and the other accident progression sign<strong>at</strong>ures will be dis<br />

cussed in Section 10.<br />

9.4.2.7 Summary of key events. A comparison of the predicted times<br />

to key events following core uncovery for each of the six sequences as<br />

calcul<strong>at</strong>ed by MARCH version 1.4B is given in Table 9.7.<br />

9.4.2.8 Key results for sequence TB '. Key results from the MARCH<br />

calcul<strong>at</strong>ions for the sequence TB1 which is used as the base case for the<br />

fission product transport calcul<strong>at</strong>ions in Volume 2 are presented in Figs.<br />

9.12 through 9.21.


100<br />

Table 9.3<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + Manual RCIC & SRV<br />

(TVB-)<br />

Time<br />

(sec) Event<br />

0.0 Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure - 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure - 35°C (95°F)<br />

0.2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0.2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0.2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0.3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0.5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

1.0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

1.0 Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2.0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.


101<br />

Time<br />

(sec) Event<br />

3.0 Turbine trips off (turbine stop valves fully closed).<br />

3.5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5.0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Seven (7) out of thirteen (13) S/RVs start to open in<br />

response to pressure rise above the setpoint.<br />

5.2 W<strong>at</strong>er-steam mixture level recovers 0.51 m (20 in.)<br />

from the previous momentary 1.02 m (40-in.) drop.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 6 S/RVs are completely closed. <strong>One</strong> S/RV is stuck<br />

open (SORV); this has the same effect as a small break<br />

LOCAL of equivalent break area of 0.015 m2 (0.1583<br />

ft2).<br />

15.7 Four out of 13 S/RVs start to open.<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

21.0 Narrow range (NR) sensed w<strong>at</strong>er level reaches low alarm<br />

(Level 4), i.e., 5.98 m (235.50 in.) above Level 0, or<br />

5.00 m (196.44 in.) above TAF.<br />

22.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure rises<br />

to 35.13°C (95.24°F) in response to the first S/RV<br />

pops.


102<br />

Time<br />

(sec) Event<br />

29.0 All 4 S/RVs are completely closed.<br />

29.7 Two out of 13 S/RVs start to open.<br />

47.0 All 2 S/RVs are completely closed.<br />

47.7 <strong>One</strong> out of 13 S/RVs starts to open.<br />

56.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.3°C (95.54°F).<br />

56.0 NR sensed w<strong>at</strong>er level reaches low level alarm (Level 3),<br />

i.e., 5.50 m (216.00 in.) above Level 0, or 4.50 m (176.94<br />

in.) above TAF.<br />

90.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.4°C (95.72°F).<br />

101.0 The S/RV is completely closed. The same S/RV continues to<br />

cycle on and off on setpoints throughout the subsequent RCIC<br />

injections.<br />

625 Wide range sensed w<strong>at</strong>er level reaches low w<strong>at</strong>er level setpoint<br />

(Level 2), i.e., 4.18 m (164.50 in.) above Level 0 <strong>at</strong><br />

2/3 core height, or 2.96 m (116.50 in.) above TAF.<br />

625 Oper<strong>at</strong>or manually controls RCIC injection to maintain con<br />

stant vessel w<strong>at</strong>er level. The RCIC turbine pump is driven<br />

by steam gener<strong>at</strong>ed by decay he<strong>at</strong>. System auxiliaries are<br />

powered by the 250 V dc system.<br />

655 RCIC flows enter the reactor pressure vessel <strong>at</strong> 38 H/s<br />

(600 gpm) drawing w<strong>at</strong>er from the condens<strong>at</strong>e storage tank.<br />

15 min. Oper<strong>at</strong>or manually opens one SRV to depressurize the vessel.<br />

20 min. Drywell and wetwell temper<strong>at</strong>ures exceed 76°C (169°F) and<br />

50°C (122°F), respectively. Mass and energy addition r<strong>at</strong>es<br />

into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 829.75 1.10 x 105 2.32 x IO8 1.32 x IO7<br />

Hydrogen 0 0 0 0


103<br />

Time<br />

(sec) Event<br />

21.14 min. Core uncovery time.<br />

22.0 min. Core refloods.<br />

30 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell<br />

pressure exceeds 13.8 KPa (2.0 psi). The RCIC system is not<br />

isol<strong>at</strong>ed.<br />

240 min. The RCIC pump stops when the b<strong>at</strong>teries run out.<br />

266.3 min. Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint.<br />

Drywell and wetwell temper<strong>at</strong>ures are 99°C (210°F) and 100°C<br />

(212°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 19.16 2.53 x IO3 5.20 x IO7 2.96 x io6<br />

Hydrogen 0 0 0 0<br />

347 min. Core uncovers again.<br />

366 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 491°C (916°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 113°C<br />

(236°F) and 0.28 MPa (40 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 9.26 1.22 x 103 2.97 x IO7 1.69 x io6<br />

Hydrogen 4.09 x io"5 5.41 x io"3 222.28 12.64<br />

386 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 855°C (1571°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 115°C<br />

(239°F) and 0.29 MPa (41 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 5.05 6.68 x io2 1.81 x IO7 1.03 x IO6<br />

Hydrogen 1.68 x IO-2 2.23 1.35 x IO5 7.70 x 103


Time<br />

(sec)<br />

395.3 min.<br />

449.3 min.<br />

451,.2 min.<br />

452 min.<br />

452.,9 min.<br />

539..3 min.<br />

539.,3 min.<br />

539.,3 min.<br />

Core melting starts.<br />

104<br />

Event<br />

W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

The corium slumps down to vessel bottom.<br />

Debris starts to melt through the bottom head.<br />

Vessel bottom head fails, resulting in a pressure increase<br />

of 0.0047 MPa (0.68 psia).<br />

Debris starts to boil w<strong>at</strong>er from containment floor.<br />

Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 204°C (400°F) and start<br />

to vent through the primary containment <strong>at</strong> a leak r<strong>at</strong>e of<br />

118 Z/s (250 ft3/min).<br />

539.3 m^n. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 1750°C (3182°F) initial<br />

ly. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are 9.99<br />

x 10° and 1.84 x io7 w<strong>at</strong>ts, respectively.<br />

601.05 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s (lb/min) (w) (Btu/min)<br />

Steam 4.70 621.51 1.59 x io5 9052<br />

Hydrogen 0.14 18.27 0 0<br />

C02 1.29 170.23<br />

CO 2.88 381.21<br />

The leak r<strong>at</strong>e through the drywell penetr<strong>at</strong>ion seals is<br />

-5.33 x io* X,/s (1.13 x io5 ft3/min).<br />

718.8 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (-14.7 psia)<br />

and temper<strong>at</strong>ures are 700°C ( 1293°F) and 98°C (~209°F),<br />

respectively. The leak r<strong>at</strong>e through the containment failed<br />

area is -5.18 x io4 l/s (-1.10 x io5 ft3/min).


105<br />

Time<br />

(sec) Event<br />

821.5 min. Drywell and wetwell temper<strong>at</strong>ures are 737°C (1359°F) and 93°C<br />

(199°F), respectively. The leak r<strong>at</strong>e through the contain<br />

ment failed area is -4.23 x io4* Jl/s (-8.96 x io1*<br />

ft3/min).<br />

1127.5 min. Drywell and wetwell temper<strong>at</strong>ures are 468°C (~875°F) and<br />

86°C (~188°F), respectively. The leak r<strong>at</strong>e through the<br />

containment failed area is -4.79 x io1* SL/b (-1.02 x<br />

IO1* ft3/min).


0.0<br />

106<br />

Table 9.4<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + Manual RCIC & SRV + SORV (Small Break LOCA)<br />

(TVPB')<br />

Time<br />

(sec) Event<br />

Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure - 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure = 35°C (95°F)<br />

°«2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0.2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0*2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0.3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0.5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

1*0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

1«° Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2*0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.


107<br />

Time<br />

(sec) Event<br />

3.0 Turbine trips off (turbine stop valves fully closed).<br />

3.5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5.0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Oper<strong>at</strong>or manually opens one S/RV to depressurize the<br />

vessel.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 6 S/RVs are completely closed. <strong>One</strong> S/RV is stuck<br />

open (SORV). This has the same effect as a small<br />

break LOCA of equivalent break area of 0.0147 m<br />

(0.1583 ft2).<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

30 Oper<strong>at</strong>or manually controls RCIC injection to maintain<br />

constant vessel w<strong>at</strong>er level. The RCIC turbine pump is<br />

driven by steam gener<strong>at</strong>ed by decay he<strong>at</strong>. System<br />

auxiliaries are powered by the 250 V dc system.<br />

60 RCIC flows enter the reactor pressure vessel <strong>at</strong> 38<br />

l/s (600 gpm) drawing w<strong>at</strong>er from the condens<strong>at</strong>e<br />

storage tank.


108<br />

Time<br />

(sec) Event<br />

10.52 min. Core uncovery time. Steam-w<strong>at</strong>er mixture level is <strong>at</strong> 3.56 m<br />

(11.68 ft) above bottom of the core.<br />

11.52 min. Core refloods.<br />

20 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell<br />

pressure exceeds 13.8 KPa (2.0 psi). The RCIC system is<br />

not isol<strong>at</strong>ed.<br />

240 min. The RCIC pump stops when the b<strong>at</strong>teries run out.<br />

270 min. Wide range sensed w<strong>at</strong>er level reaches Level 2 setpoint.<br />

Drywell and wetwell temper<strong>at</strong>ures are 100°C (212°F) and 102°C<br />

(216°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 19.50 2.58 x io3 5.29 x io7 3.01 x io6<br />

Hydrogen 0 0 0 0<br />

337 min. Core uncovers again.<br />

356 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 313°C (595°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 113°C<br />

(236°F) and 0.28 MPa (40 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 12.25 1.62 x io3 3.64 x io7 2.07 x io6<br />

Hydrogen 3.05 x io~8 4.03 x io~6 0.115 6.53 x io"3<br />

376.4 min. Average gas temper<strong>at</strong>ure <strong>at</strong> top of core is 650°C (1202°F).<br />

Drywell and wetwell temper<strong>at</strong>ures and pressures are 115°C<br />

(239°F) and 0.29 MPa (41 psia), respectively. Mass and<br />

energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 7.20 9.52 x io2 2.43 x io7 1.38 x io6<br />

Hydrogen 1.60 x io~3 0.21 1.07 x up 6.09 x io2


109<br />

Time<br />

(sec) Event<br />

396.36 min. Core melting starts.<br />

450.4 min. W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

452.3 min. Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

453.1 min. The corium slumps down to vessel bottom.<br />

454. min. Debris starts to melt through the bottom head.<br />

542.5 min. Vessel bottom head fails, resulting in a pressure increase<br />

of 0.005 MPa (0.7 psia).<br />

542.5 min. Debris starts to boil w<strong>at</strong>er from containment floor.<br />

542.5 min. Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 240°C (400°F) and start<br />

to vent through the primary containment <strong>at</strong> a leak r<strong>at</strong>e of<br />

104 i/s (221 ft3/min).<br />

542.5 min. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 1766°C (3210°F) initial<br />

ly. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are 1.00<br />

x IO7 and 1.83 x io' w<strong>at</strong>ts, respectively.<br />

596.4 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Steam<br />

Hydrogen<br />

co2<br />

CO<br />

Mass<br />

(kg/s<br />

7.69<br />

0.038<br />

2.58<br />

0.80<br />

R<strong>at</strong>e<br />

(lb/min)<br />

1017<br />

342<br />

160<br />

5.08<br />

Energy<br />

(w)<br />

1.59 x io5<br />

0<br />

R<strong>at</strong>e<br />

(Btu/min)<br />

9052<br />

The leak r<strong>at</strong>e through the drywell penetr<strong>at</strong>ion seals is<br />

-9.20 x io1* SL/s (1.95 x io5 ft3/min).<br />

0


0.0<br />

110<br />

Table 9.5<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + No HPCI/RCIC<br />

(TUB*)<br />

Time<br />

(sec) Event<br />

Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure = 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure - 35°C (95°F)<br />

0*2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0*2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0*2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0*3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0*5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

!*0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

i'O Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2.0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.<br />

3.0 Turbine trips off (turbine stop valves fully closed).


Ill<br />

Time<br />

(sec) Event<br />

3»5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5.0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Seven (7) out of thirteen (13) S/RVs start to open in<br />

response to pressure rise above the setpoint.<br />

5.2 W<strong>at</strong>er-steam mixture level recovers 0.51 m (20 in.)<br />

from the previous momentary 1.02 m (40-in.) drop.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 7 S/RVs are completely closed.<br />

15.7 Four out of 13 S/RVs start to open.<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

21.0 Narrow range (NR) sensed w<strong>at</strong>er level reaches low alarm<br />

(Level 4), i.e., 5.98 m (235.50 in.) above Level 0, or<br />

5.00 m (196.44 in.) above TAF.<br />

22.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure rises to<br />

35.13°C (95.24°F) in response to the first S/RV pops.<br />

29.0 All 4 S/RVs are completely closed.<br />

29.7 Two out of 13 S/RVs start to open.


112<br />

Time<br />

(sec) Event<br />

47.0 All 2 S/RVs are completely closed.<br />

47.7 <strong>One</strong> out of 13 S/RVs starts to open.<br />

56.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.3°C (95.54°F).<br />

56.0 NR sensed w<strong>at</strong>er level reaches low level alarm (Level 3),<br />

i.e., 5.50 m (216.00 in.) above Level 0, or 4.50 m (176.94<br />

in.) above TAF.<br />

90.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.4°C (95.72°F).<br />

101.0 The S/RV is completely closed. The same S/RV continues to<br />

cycle on and off on setpoints throughout the sequence.<br />

625 Wide range sensed w<strong>at</strong>er level reaches low w<strong>at</strong>er level<br />

set-point (Level 2), i.e., 4.18 m (164.50 in.) above Level 0<br />

<strong>at</strong> 2/3 core height, or 2.96 m (116.50 in.) above TAF.<br />

625 HPCI and RCIC systems are not turned on because they are<br />

assumed to be unavailable.<br />

20 min. Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure reaches 46°C<br />

(114°F).<br />

33 min. Core uncovery time. Steam-w<strong>at</strong>er mixture level is <strong>at</strong> 3.54 m<br />

(11.61 ft) above bottom of the core.<br />

40 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell<br />

pressure exceeds 13.8 KPa (2.0 psi). The HPCI/RCIC systems<br />

are not affected. Drywell and wetwell temper<strong>at</strong>ure are 72°C<br />

(162°F) and 55°C (130°F), respectively. Mass and energy<br />

addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 33 4.36 x io3 9.25 x io7 5.26 x io6<br />

Hydrogen 6 x 10 9 8.62 x io-7 2.92 x io~2 1.66 x io"3<br />

60 min. Mass and energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 15.6 2.07 x io3 5.06 x 107 2.88 x 106<br />

Hydrogen 2.8 x io~3 3.76 x io"1 2.15 x iq1* 1.22 x io3


70<br />

80<br />

Time<br />

(sec)<br />

min.<br />

min.<br />

Core melting starts.<br />

113<br />

Event ^^^^<br />

Drywell and wetwell temper<strong>at</strong>ures are 75°C (167°F) and 63°C<br />

(145°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e<br />

(kg/s) (lb/min)<br />

Steam 5.68 7.51 x io2<br />

Hydrogen 0.19 2.53 x io1<br />

Energy R<strong>at</strong>e<br />

(w) (Btu/min)<br />

2.22 x io7 1.26 x io6<br />

2.29 x io6 1.30 x io5<br />

96 min. W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

97 min. Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

99 min. The corium slumps down to vessel bottom.<br />

101 min. The debris is starting to melt through the bottom head.<br />

Drywell and wetwell temper<strong>at</strong>ures are 97°C (207°F) and 71°C<br />

(159°F), respectively. Meanwhile, local pool w<strong>at</strong>er tempera<br />

ture <strong>at</strong> the discharging bay exceeds 149°C (300°F). Steam<br />

condens<strong>at</strong>ion oscill<strong>at</strong>ions could acceler<strong>at</strong>e due to the con<br />

tinuous discharge of superhe<strong>at</strong>ed noncondensable gases into<br />

the suppression pool. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are;<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 18.6 5.46 x io3 5.42 x io7 3.08 x io6<br />

Hydrogen 6.8 x io-2 8.93 3.59 x io5 2.04 x io**<br />

129 min. Vessel bottom head fails, resulting in a pressure increase<br />

of 0.34 MPa (49 psia).<br />

129.03 min. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 1546°C (2815°F) ini<br />

tially. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are<br />

1.36 x 107 and 2.50 x io7 w<strong>at</strong>ts, respectively.


114<br />

Time<br />

(sec) Event<br />

165 min. Drywell and wetwell temper<strong>at</strong>ures are 141°C (286°F) and 74°C<br />

(166°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 5.46 722.83 1.59 x io5 9052<br />

Hydrogen 3.3 x io-2 4.38 0 0<br />

CO2 2.58 341.88<br />

CO 0.69 91.35<br />

190 min. Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 204°C (400°F) and start<br />

to vent through the primary containment.<br />

193 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment.<br />

219 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (14.7 psia).<br />

Drywell and wetwell temper<strong>at</strong>ures are 598°C (1109°F) and 78°C<br />

(173°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Steam<br />

Hydrogen<br />

CO2<br />

CO<br />

Mass<br />

(kg/s)<br />

0.70<br />

0.24<br />

2.32<br />

5.03<br />

R<strong>at</strong>e<br />

(lb/min)<br />

92<br />

32<br />

307<br />

666<br />

Energy R<strong>at</strong>e<br />

(w) (Btu/min)<br />

1.59 x IO5 9052<br />

0 0<br />

The leak r<strong>at</strong>e through the containment failed areas is<br />

-2.90 x io5 X./b (-6.15 x io5 ft3/min).<br />

250 min. Drywell and wetwell temper<strong>at</strong>ures are 675°C (1247°F) and 78°C<br />

(173°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Steam<br />

Hydrogen<br />

C02<br />

CO<br />

Mass<br />

(kg/s)<br />

6.84<br />

0.25<br />

1.53<br />

5.25<br />

R<strong>at</strong>e<br />

(lb/min)<br />

905<br />

33<br />

203<br />

695<br />

Energy R<strong>at</strong>e<br />

(w) (Btu/min)<br />

1.59 x 105 9052<br />

0 0


115<br />

Time<br />

(sec) Event<br />

The leak r<strong>at</strong>e through the containment failed area is<br />

-4.91 x io4* l/s (-1.04 x io5 ft3/min).<br />

309 min. R<strong>at</strong>e of concrete decomposition is -4.65 x io1* gm/s.<br />

R<strong>at</strong>e of he<strong>at</strong> added to <strong>at</strong>mosphere is -1.20 x 10* kW.<br />

367 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (-14.7 psia)<br />

and temper<strong>at</strong>ures are 854°C (1570°F) and 77°C (171°F), re<br />

spectively. The leak r<strong>at</strong>e through the containment failed<br />

area is -3.94 x \if i/s (~8.35 x io4* ft3/min).<br />

733 min. Drywell and wetwell temper<strong>at</strong>ures are 546°C (~1014°F) and<br />

77°C (170°F), respectively. The leak r<strong>at</strong>e through the con<br />

tainment failed area is -2.12 x io3 A/s (-4.50 x<br />

103 ft3/min).


116<br />

Table 9.6<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant: Complete <strong>St<strong>at</strong>ion</strong> Blackout<br />

Sequence of Events<br />

CSB + No HPCI/RCIC & SORV (Small Break LOCA)<br />

(TUPS' )<br />

Time<br />

(sec) Event<br />

0.0 Loss of all AC power and diesel gener<strong>at</strong>ors. The plant<br />

is initially oper<strong>at</strong>ing <strong>at</strong> 100% power.<br />

Initial drywell temper<strong>at</strong>ure = 66°C (150°F)<br />

Initial wetwell temper<strong>at</strong>ure = 35°C (95°F)<br />

0.2 Full load rejection (i.e., fast closure of turbine<br />

control valves) occurs.<br />

0.2 Recircul<strong>at</strong>ion pumps and condenser circul<strong>at</strong>ory w<strong>at</strong>er<br />

pumps trip off. Loss of condenser vacuum occurs.<br />

Core flow is provided by n<strong>at</strong>ural circul<strong>at</strong>ion.<br />

0.2 Reactor pressure increases suddenly due to load rejec<br />

tion.<br />

0.3 Scram pilot valve solenoids are deenergized due to<br />

load rejection. Control rod motion begins.<br />

0.5 Turbine bypass valves start to open due to load rejec<br />

tion.<br />

1.0 Neutron flux starts to decrease after an initial in<br />

crease to over 100% r<strong>at</strong>ed power level.<br />

1.0 Reactor power starts to decrease slowly after an ini<br />

tial rise.<br />

2.0 Control rods are 40% inserted from fully withdrawn<br />

position.<br />

2.0 Main steamline isol<strong>at</strong>ion valves (MSIVs) start to close<br />

(relay-type reactor trip system), resulting in a rapid<br />

steam-line pressure rise.<br />

2.0 Turbine bypass valves are tripped to close.<br />

3.0 Control rods are 75% inserted from fully withdrawn<br />

position.<br />

3.0 Turbine trips off (turbine stop valves fully closed).


117<br />

Time<br />

(sec) Event<br />

3.5 Power gener<strong>at</strong>ion due to delayed neutrons and fission<br />

product decay drops to 10% of initial r<strong>at</strong>ed power gen<br />

er<strong>at</strong>ion.<br />

4.0 Feedw<strong>at</strong>er turbines trip off.<br />

5.0 MSIVs are fully closed, resulting in a momentary 0.69<br />

MPa (100 psi) pressure increase and 1.02 m (40-in.)<br />

drop of w<strong>at</strong>er-steam mixture level due to collapsing of<br />

voids.<br />

5.0 All control rods are fully inserted.<br />

5.0 Reactor vessel pressure exceeds the lowest setpoint <strong>at</strong><br />

7.52 MPa (1090 psi) of safety/relief valves (S/RVs).<br />

5.0 Seven (7) out of thirteen (13) S/RVs start to open in<br />

response to pressure rise above the setpoint.<br />

5.2 W<strong>at</strong>er-steam mixture level recovers 0.51 m (20 in.)<br />

from the previous momentary 1.02 m (40-in.) drop.<br />

5.5 S/RV steam blowdowns into the pressure suppression<br />

pool through the T-quenchers begin.<br />

7.5 Feedw<strong>at</strong>er flow drops below 20%.<br />

9.0 Feedw<strong>at</strong>er flow decreases to zero.<br />

10.0 Power gener<strong>at</strong>ion due to fission product decay drops to<br />

approxim<strong>at</strong>ely 7.2% of r<strong>at</strong>ed power gener<strong>at</strong>ion.<br />

15.0 All 6 S/RVs are completely closed. <strong>One</strong> S/RV is stuck<br />

open (SORV); this has the same effect as a small break<br />

LOCA of equivalent break area of 0.015 m2 (0.1583<br />

ft2).<br />

15.7 Four out of 13 S/RVs start to open.<br />

17.0 Neutron flux drops below 1% of initial full power<br />

level.<br />

21.0 Narrow range (NR) sensed w<strong>at</strong>er level reaches low alarm<br />

(Level 4), i.e., 5.98 m (235.50 in.) above Level 0, or<br />

5.00 m (196.44 in.) above TAF.<br />

22.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure rises to<br />

35.13°C (95.24°F) in response to the first S/RV pops.<br />

29.0 All 4 S/RVs are completely closed.<br />

29.7 Two out of 13 S/RVs start to open.


118<br />

Time<br />

(sec) Event<br />

47.0 All 2 S/RVs are completely closed.<br />

47.7 <strong>One</strong> out of 13 S/RVs starts to open.<br />

56.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.3°C (95.54°F).<br />

56.0 NR sensed w<strong>at</strong>er level reaches low level alarm (Level 3),<br />

i.e., 5.50 m (216.00 in.) above Level 0, or 4.50 m (176.94<br />

in.) above TAF.<br />

90.0 Suppression pool w<strong>at</strong>er average temper<strong>at</strong>ure is approxim<strong>at</strong>ely<br />

35.4°C (95.72°F).<br />

101.0 The S/RV is completely closed. The same S/RV continues to<br />

cycle on and off on setpoints throughout the sequence.<br />

625 Wide range sensed w<strong>at</strong>er level reaches low w<strong>at</strong>er level<br />

set-point (Level 2), i.e., 4.18 m (164.50 in.) above Level 0<br />

<strong>at</strong> 2/3 core height, or 2.96 m (116.50 in.) above TAF.<br />

625 HPCI and RCIC systems are not turned on because they are<br />

assumed to be unavailable.<br />

17.2 min. Core uncovery time. Steam-w<strong>at</strong>er mixture level is <strong>at</strong> 3.62 m<br />

(11.88 ft) above bottom of the core.<br />

20 min. Auto-isol<strong>at</strong>ion signal initi<strong>at</strong>es as increase of drywell<br />

pressure exceeds 13.8 KPa (2.0 psi). The HPCI/RCIC systems<br />

are not affected. Drywell and wetwell temper<strong>at</strong>ure are 73°C<br />

(163°F) and 55°C (130°F), respectively. Mass and energy<br />

addition r<strong>at</strong>es into the wetwell are:<br />

Mass r<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 60 7.94 x io3 1.69 x io8 9.61 x io6<br />

Hydrogen 8.53 x io-13 1.13 x io~10 3.19 x io"6 1.81 x io~7<br />

40 min. Mass and energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 10.30 1.36 * 103 3.41 x io7 1.94 x io6<br />

Hydrogen 2.38 x IO-1* 3.15 x io"2 1.61 x io3 91.56


119<br />

Time<br />

(sec) Event<br />

56.6 min. Core melting starts.<br />

60 min. Drywell and wetwell temper<strong>at</strong>ures are 75°C (167°F) and 63°C<br />

(145°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 2.73 3.61 x io2 1.23 x io7 6.99 x io5<br />

Hydrogen 0.49 6.48 x io1 7.05 x io6 4.01 x io5<br />

78 min. W<strong>at</strong>er level in vessel drops below bottom grid elev<strong>at</strong>ion.<br />

79 min. Bottom grid fails and temper<strong>at</strong>ure of structures in bottom<br />

head is above w<strong>at</strong>er temper<strong>at</strong>ure.<br />

81 min. The corium slumps down to vessel bottom.<br />

81.5 min. The debris is starting to melt through the bottom head.<br />

Drywell and wetwell temper<strong>at</strong>ures are 82°C (180°F) and 71°C<br />

(159°F), respectively. Meanwhile, local pool w<strong>at</strong>er tempera<br />

ture <strong>at</strong> the discharging bay exceeds 149°C (300°F). Steam<br />

condens<strong>at</strong>ion oscill<strong>at</strong>ions could acceler<strong>at</strong>e due to the con<br />

tinuous discharge of superhe<strong>at</strong>ed noncondensable gases into<br />

the suppression pool.<br />

101 min. Mass and energy addition r<strong>at</strong>es into the wetwell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 1.25 165.35 3.47 x io6 1.97 x io5<br />

Hydrogen 4.45 x io"* 0.06 1.03 x io3 58.58<br />

142.5 min. Vessel bottom head fails, resulting in a pressure increase<br />

of 0.34 MPa (49 psia).<br />

152.5 min. Debris starts to boil w<strong>at</strong>er from containment floor.<br />

162.5 min. Debris starts to melt the concrete floor of the containment<br />

building. Temper<strong>at</strong>ure of debris is 2013°C (3655°F) ini<br />

tially. Internal he<strong>at</strong> gener<strong>at</strong>ion in metals and oxides are<br />

2.43 x io7 and 1.26 x io7 w<strong>at</strong>ts, respectively.


120<br />

Time<br />

(sec) Event<br />

162.5 min. Drywell and wetwell temper<strong>at</strong>ures are 128°C (262°F) and 74°C<br />

(166°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 0.057 7.54 1.59 x io5 9052<br />

Hydrogen 0 0 0 0<br />

167.8 min. Drywell electric penetr<strong>at</strong>ion assembly seals have failed as<br />

the containment temper<strong>at</strong>ure exceeds 204°C (400°F) and start<br />

to vent through the primary containment.<br />

175.2 min. Containment failed as the containment temper<strong>at</strong>ure exceeds<br />

260°C (500°F) and all electric penetr<strong>at</strong>ion modules are blown<br />

out of the containment.<br />

185.3 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (14.7 psia).<br />

Drywell and wetwell temper<strong>at</strong>ures are 314°C (598°F) and 78°C<br />

(173°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

Steam 1.65 218.26 1.59 x io5 9052<br />

Hydrogen 0.025 3.31 0 0<br />

C02 5.79 765.88<br />

CO 0.526 69.58<br />

The leak r<strong>at</strong>e through the containment failed areas is<br />

~3.00 x io* A/s (-6.36 x io* ft3/min).<br />

206 min. Drywell and wetwell temper<strong>at</strong>ures are 610°C (1130°F) and 78°C<br />

(173°F), respectively. Mass and energy addition r<strong>at</strong>es into<br />

the drywell are:<br />

Mass R<strong>at</strong>e Energy R<strong>at</strong>e<br />

(kg/s) (lb/min) (w) (Btu/min)<br />

C02 1.83 242<br />

Hydrogen 0.20 26 0 0<br />

Steam 1.36 180 1.59 x io5 9052<br />

CO 4.15 549


121<br />

Time<br />

(sec) Event<br />

The leak r<strong>at</strong>e through the containment failed area is<br />

-2.94 x 10* A/s (-6.24 x io* ft3/min).<br />

222.5 min. R<strong>at</strong>e of concrete decomposition is -4.46 x io* gm/s.<br />

R<strong>at</strong>e of he<strong>at</strong> added to <strong>at</strong>mosphere is -3.71 x 10* kW.<br />

254.5 min. Drywell and wetwell pressures are <strong>at</strong> 0.10 MPa (-14.7 psia)<br />

and temper<strong>at</strong>ures are 746°C (1375°F) and 77°C (171°F), re<br />

spectively. The leak r<strong>at</strong>e through the containment failed<br />

area is -5.54 x io* A/s (-1.17 x io5 ft3/min).<br />

501 min. Drywell and wetwell temper<strong>at</strong>ures are 815°C (-1500°F) and<br />

77°C (170°F), respectively. The leak r<strong>at</strong>e through the con<br />

tainment failed area is -2.34 x io* A/s (-4.96 x<br />

10* ft3/min).


Sequence Event<br />

1 CSB + HPCI/RCIC<br />

2 CSB + HPCI/RCIC + SORV<br />

3 CSB + Manual RCIC/SRV<br />

4 CSB + Manual RCIC/SRV + SORV<br />

5 CSB + iNo HPCI/RCIC<br />

6 CSB + No HPCI/RCIC + SORV<br />

Table 9.7. Predicted times to key events<br />

Core Core<br />

uncover reflood<br />

302<br />

315<br />

21 22<br />

11 12<br />

33<br />

17<br />

Core<br />

uncover<br />

again<br />

347<br />

337<br />

Accident progression time<br />

(min)<br />

Start<br />

melt<br />

355<br />

388<br />

395<br />

396<br />

69<br />

57<br />

Core<br />

slump<br />

392<br />

419<br />

449<br />

453<br />

95<br />

78<br />

Vessel<br />

failure<br />

426<br />

515<br />

539<br />

543<br />

128<br />

143<br />

Wetwell<br />

failure<br />

130<br />

145 '/<br />

Drywell<br />

EPA vent<br />

503<br />

515<br />

539<br />

543<br />

190<br />

168<br />

Drywell<br />

failure<br />

Wetwell failure is due to forces of steam jet impingement and condens<strong>at</strong>ion oscill<strong>at</strong>ions resulting from excessive thermal<br />

str<strong>at</strong>ific<strong>at</strong>ion in the suppression pool.<br />

Drywell electric penetr<strong>at</strong>ion assembly seals start to vent when the ambient temper<strong>at</strong>ure exceeds 204°C (400°F).<br />

Drywell electric penetr<strong>at</strong>ion assembly seals become decomposed and are<br />

per<strong>at</strong>ure exceeds 260°C (500°F).<br />

blown out of the containment when the ambient tem<br />

TJest estim<strong>at</strong>e value.<br />

Containment would fail <strong>at</strong> 288 min. using WASH-1400 failure criterion of st<strong>at</strong>ic pressuriz<strong>at</strong>ion <strong>at</strong> 190 psia.<br />

/, Best estim<strong>at</strong>e value.<br />

514<br />

580<br />

601<br />

596<br />

e<br />

193<br />

175<br />

to<br />

ro


123<br />

Figure 9.12 shows the reactor vessel pressure distribution; it re<br />

mains approxim<strong>at</strong>ely constant during the first 240 minutes when the steam<br />

mass flow through the SRV discharge into the suppression pool (Fig. 9.13)<br />

is balanced by HPCI injection (Fig. 9.14). The pressure increases after<br />

the HPCI injection has stopped upon the assumed loss of dc power <strong>at</strong> 4 h<br />

into the transient.<br />

The mass of w<strong>at</strong>er and the mass of steam within the reactor vessel are<br />

shown in Figs. 9.15 and 9.16 respectively. The rel<strong>at</strong>ively rapid decrease<br />

in steam inventory beginning <strong>at</strong> about 305 minutes as shown in Fig. 9.16 is<br />

due to depletion in the production of hydrogen (Fig. 9.17) by the<br />

Zirconium-w<strong>at</strong>er reaction (Fig. 9.18) before the onset of core melting<br />

(Fig. 9.19). The large amount of energy released by the Zr-H20 reaction<br />

(Fig. 9.20) before the core slumps into the lower head causes an increase<br />

in the steaming r<strong>at</strong>e and the reactor vessel pressure.<br />

The large amount of energy release in the predicted corium-w<strong>at</strong>er in<br />

teraction after reactor vessel failure would cause a significant contain<br />

ment pressure spike. The vertical concrete penetr<strong>at</strong>ion resulting from<br />

corium <strong>at</strong>tack is shown in Fig. 9.21.<br />

9.5 Containment Responses<br />

As previously discussed, containment failure could occur either in<br />

the drywell or in the wetwell if a core meltdown accident were to occur <strong>at</strong><br />

the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant. The radiological consequences of a wet<br />

well failure would be less severe than those of a drywell failure, because<br />

a significant fraction of the released fission products would be dissolved<br />

or deposited in the suppression pool.<br />

9.5.1 Drywell Response<br />

Drywell failure would occur in the EPA when the elastomeric sealing<br />

m<strong>at</strong>erials undergo degrad<strong>at</strong>ion and lose sealing integrity <strong>at</strong> ambient tem<br />

per<strong>at</strong>ures gre<strong>at</strong>er than 204°C (400°F)i8» 22. This does not preclude the<br />

possibility of an earlier failure of the wetwell by overpressuriz<strong>at</strong>ion.<br />

An EPA typical of those installed in the <strong>Browns</strong> <strong>Ferry</strong> unit 1 drywell liner<br />

is shown in Fig. 9.22.<br />

The masses of steam and hydrogen accumul<strong>at</strong>ed in the drywell and wet<br />

well following core melt in the base case TB' are shown in Figs. 9.23<br />

through 9.26. For this case, wetwell failure by overpressuriz<strong>at</strong>ion is not<br />

preducted to occur.<br />

The drywell temper<strong>at</strong>ure responses for the sequences TB' and TUB ' are<br />

shown in Figs. 9.27 and 9.28 respectively; the general trends are very<br />

similar in the two sequences, except th<strong>at</strong> high temper<strong>at</strong>ures are reached<br />

much sooner in sequence TUB', as would be expected.* The corresponding<br />

drywell pressure responses for these two sequences are shown in Figs. 9.29<br />

through 9.36.<br />

*In sequence TUB', it is assumed th<strong>at</strong> the HPCI and RCIC systems<br />

are unavailable from the inception of the <strong>St<strong>at</strong>ion</strong> Blackout. Thus boiloff,<br />

core uncovery, and the subsequent events would occur sooner.


(x 105)<br />

77.0-<br />

76.0-<br />

S 75.0<br />

ui<br />

cc<br />

w 74.0<br />

CO<br />

CC<br />

a.<br />

><br />

CO<br />

73.0-<br />

> 72.0 H<br />

<<br />

2<br />

cc<br />

a.<br />

71.0-<br />

70.0<br />

69.0<br />

0.0<br />

PRESSURE INCREASE FOLLOWING MSIV CLOSURE<br />

50.0 100.0<br />

150.0<br />

dc POWER LOST ,<br />

I<br />

200.0<br />

TIME (min)<br />

250.0<br />

Fig. 9.12 Reactor vessel pressure.<br />

300.0<br />

ORNL-DWG 81-8523 ETD<br />

r-CORE UNCOVERY<br />

—I<br />

350.0 400.0<br />

ro


~r3><br />

600.0 -r<br />

500.0<br />

w 400.0<br />

Q.<br />

o cc<br />

UJ<br />

r-<br />

<<br />

CC<br />

<<br />

UJ<br />

to<br />

300.0-<br />

200.0-<br />

100.0-<br />

0.0<br />

dc POWE R LOST<br />

SRV FLOW AND HPCI INJECTION<br />

BECOME BALANCED<br />

100.0<br />

HPCI INJECTION STOPS-,<br />

—I<br />

150.0 200.0<br />

TIME (min)<br />

CORE SLUMPS INTO LOWER PLENUM<br />

250.0<br />

Fig. 9.13 Steam mass flow r<strong>at</strong>e from primary system.<br />

300.0<br />

ORNL-DWG 81-8524 ETD<br />

CORE UNCOVERY<br />

T<br />

350.0<br />

400.0<br />

to


120.0<br />

100.0-<br />

> 80.0-<br />

cc<br />

D<br />

V)<br />

V)<br />

UJ<br />

cc<br />

CL<br />

o<br />

r-<br />

60.0-<br />

< 40.0<br />

o<br />

§ 20.0<br />

0.0<br />

0.0 50.0<br />

SRV FLOW AND HPCI INJECTION<br />

BECOME BALANCED<br />

100.0 150.0<br />

I<br />

200.0<br />

TIME (min)<br />

250.0<br />

Fig. 9.14 HPCI flow r<strong>at</strong>e into pressure vessel.<br />

-dc POWER LOST<br />

HPCI INJECTION STOPS<br />

300.0 350.0<br />

ORNL-DWG 81-8525 ETD<br />

—f<br />

400.0<br />

ro<br />

as


CT><br />

(x 104)<br />

30.0<br />

25.0-<br />

a 20.0<br />

<<br />

cc<br />

a.<br />

rr 15.0<br />

UJ<br />

<<br />

u.<br />

O<br />

to<br />

to<br />

<<br />

10.0-<br />

5.0-<br />

0.0<br />

0.0 50.0 100.0 150.0<br />

I<br />

200.0<br />

TIME (min)<br />

I<br />

250.0<br />

Fig. 9.15 Mass of w<strong>at</strong>er in primary system.<br />

LOSS OF dc POWER<br />

BOILOFF BEGINS<br />

I<br />

300.0<br />

ORNL-DWG 81-8526 ETD<br />

CORE SLUMPS-<br />

I<br />

350.0 400.0<br />

IO<br />

~4


S<br />

UJ<br />

(x 103)<br />

20.0-<br />

18.0<br />

16.0<br />

<br />

CO<br />

> rr<br />

<<br />

2<br />

cc<br />

0_<br />

z<br />

12.0<br />

10.0<br />

CO<br />

CO<br />

<<br />

s 8.0<br />

S<br />

<<br />

UJ<br />

CO<br />

6.0-<br />

4.0-<br />

2.0<br />

0.0 50.0 100.0<br />

dc POWER LOST<br />

BOILOFF BEGINS<br />

150.0<br />

I<br />

200.0<br />

TIME (min)<br />

CORE UNCOVERY<br />

—I<br />

250.0<br />

Fig. 9.16 Steam mass in primary system.<br />

300.0<br />

ORNL-DWG 81-8527 ETD<br />

CORE SLUMPS-<br />

—T—<br />

350.0 400.0<br />

ro<br />

oo


* »<br />

300.0<br />

250.0-<br />

o> 200.0<br />

CO<br />

a!<br />

Z<br />

z 150.0<br />

UJ<br />

O<br />

O<br />

cc<br />

Q<br />

>x<br />

100.0<br />

50.0-<br />

0.0<br />

0.0 50.0<br />

100.0 150.0<br />

H2 BUILDUP DUE TO Zr-H20 REACTION<br />

200.0<br />

TIME (min)<br />

CORE UNCOVERY<br />

Fig. 9.17 Hydrogen mass in primary system.<br />

1<br />

I<br />

250.0 300.0<br />

ORNL-DWG 81-8528 ETD<br />

CORE-J<br />

SLUMPS<br />

350.0 400.0<br />

ro


Q<br />

UJ<br />

I-<br />

O<br />

<<br />

UJ<br />

cc<br />

Q<br />

<<br />

0.20<br />

0.15-<br />

o0.10- r-<br />

<<br />

CC<br />

u_<br />

0.05-<br />

0.00<br />

0.0 50.0 100.0 150.0 200.0<br />

TIME (min)<br />

250.0<br />

Fig. 9.18 Fraction of clad reacted.<br />

ORNL-DWG 81-8529 ETD<br />

300.0 350.0 400.0<br />

o


00 50.0 100.0 150.0 200.0 250.0<br />

TIME (min)<br />

Fig. 9.19 Fraction of core melted.<br />

300.0<br />

ORNL-DWG 81-8530 ETD<br />

350.0 400.0<br />

00


(x 107)<br />

10.0<br />

o 8.0-<br />

Io<br />

<<br />

UJ<br />

CC<br />

o<br />

CN<br />

X<br />

I<br />

N<br />

5<br />

O CC<br />

U_<br />

6.0-<br />

Q<br />

£ 4.0<br />

<<br />

cc<br />

UJ<br />

z<br />

UJ<br />

o<br />

S 2.0<br />

UJ<br />

Z<br />

UJ<br />

0.0 +<br />

0.0 50.0 100.0 150.0<br />

HIGH INITIAL REACTION RATE<br />

200.0<br />

TIME (min)<br />

CORE UNCOVERY<br />

250.0 300.0<br />

Fig. 9.20 Energy gener<strong>at</strong>ed from Zr-^O reaction.<br />

ORNL-DWG 81-8531 ETD<br />

350.0 400.0<br />

OJ<br />

to


800.0 -T<br />

700.0-<br />

E<br />

^ 600.0<br />

o<br />

r-<br />

<<br />

£E 500.0-<br />

UJ<br />

Q.<br />

£ 400.0-1<br />

cc<br />

o<br />

g 300.0<br />

<<br />

o<br />

rcc<br />

UJ<br />

><br />

200.0-<br />

100.0-<br />

0.0 +<br />

0.0<br />

CORE UNCOVERY-<br />

VESSEL BOTTOM<br />

HEAD FAILS-<br />

T T<br />

100.0 200.0 300.0 400.0 500.0 600.0<br />

TIME (min)<br />

Fig. 9.21 Vertical concrete penetr<strong>at</strong>ion.<br />

ORNL-DWG 81-8532 ETD<br />

CONCRETE PENETRATION COMPLETED<br />

I I<br />

700.0 800.0<br />

—I 1 !<br />

900.0 1000.0 1100.0<br />

OJ<br />

OJ


END SHIELD<br />

FOR RADIATION<br />

PROTECTION<br />

FIELD WELD<br />

SHIELD<br />

SUPPORT<br />

FIELD WELD<br />

PRIOR TO<br />

INSTALLATION<br />

CONTAINMENT<br />

HEADER PLATES<br />

FIELD WELD<br />

Fig. 9.22 Typical electrical penetr<strong>at</strong>ion assembly canister.<br />

ORNL-DWG 81-8533 ETD<br />

CONNECTOR<br />

MOUNTING<br />

HOLES<br />

VALVE AND<br />

PRESSURE TAP<br />

OJ


(x 103)<br />

18.0<br />

16.0<br />

14.0<br />

_ 12.0 H<br />

O)<br />

25 looH<br />

r-<br />

S 80H<br />

CO<br />

<<br />

6.0-<br />

VESSEL BOTTOM HEAD FAILS<br />

CORE UNCOVERY<br />

DRYWELL VENTING THROUGH<br />

FAILED EPA SEALS<br />

—\r\l\ JL<br />

T T<br />

100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1000.0 1100.0<br />

TIME (min)<br />

Fig. 9.23 Mass of steam in drywell.<br />

DRYWELL EPA SEALS FAIL<br />

ORNL-DWG 81-8534 ETD<br />

H<br />

OJ<br />

On


250.0<br />

200.0-<br />

5 150.0<br />

o<br />

o<br />

cc<br />

Q<br />

>-<br />

CO<br />

CO<br />

<<br />

100.0-<br />

50.0<br />

DRYWELL H2 SWEPT INTO WETWELL<br />

AS VESSEL BOTTOM HEAD FAILS<br />

Zr-H20 REACTION BEGINS-<br />

0.0- T T<br />

0.0 100.0 200.0 300.0 400.0<br />

500.0 600.0<br />

TIME (min)<br />

Fig. 9.24 Mass of hydrogen in drywell.<br />

ORNL-DWG 81-8535 ETD<br />

-SPIKE DUE TO H2 RETURN FROM WETWELL<br />

FAILURE OF DRYWELL EPA SEALS<br />

i<br />

700.0 800.0 900.0 1000.0 1100.0<br />

OJ<br />

ON


9000.0<br />

8000.0<br />

7000.0<br />

_ 6000.0-<br />

< 5000.0<br />

H<br />

C/3<br />

O 4000.0co<br />

CO<br />

<<br />

3000.0-1<br />

2000.0-<br />

1000.0<br />

0.0<br />

VESSEL BOTTOM HEAD FAILS<br />

CONTINUED RELIEF<br />

VALVE ACTUATION<br />

0.0 100.0 200.0<br />

CORE SLUMPS<br />

I CORE UNCOVERY<br />

I I<br />

300.0 400.0 500.0 600.0 700.0<br />

TIME (min)<br />

Fig. 9.25 Mass of steam in wetwell.<br />

-FAILURE OF DRYWELL EPA SEALS<br />

—I 1<br />

800.0 900.0<br />

ORNL-DWG 81-8536 ETD<br />

-n<br />

1000.0 1100.0<br />

OJ<br />

^J


UJ<br />

O<br />

O<br />

CC<br />

Q<br />

><br />

I<br />

u.<br />

o<br />

CO<br />

800.0<br />

700.0-<br />

600.0-<br />

500.0<br />

400.0<br />

< 300.0<br />

200.0-<br />

100.0-<br />

0.0<br />

DRYWELL H2 SWEPT INTO<br />

WETWELL AS VESSEL<br />

BOTTOM HEAD FAILS<br />

Zr-H20 REACTION BEGINS-<br />

1 I<br />

0.0 100.0 200.0 300.0 400.0<br />

M<br />

T<br />

500.0<br />

TIME (min)<br />

H, RETURNED TO DRYWELL AS EPA<br />

SEALS FAIL AND CONTAINMENT VENTS<br />

I I<br />

600.0 700.0<br />

Fig. 9.26 Mass of hydrogen in wetwell.<br />

—I I<br />

800.0 900.0<br />

ORNL-DWG 81-8537 ETD<br />

1<br />

1000.0 1100.0<br />

OJ<br />

oo


1600.0<br />

1400.0-<br />

~ 1200.0<br />

cc<br />

D<br />

r-<br />

<<br />

£ iooo.o<br />

s<br />

UJ<br />

UJ<br />

S<br />

800.0-<br />

cc<br />

<<br />

| 600.0<br />

o o<br />

400.0-<br />

200.0-<br />

0.0<br />

INCREASE DURING<br />

CORIUM-CONCRETE<br />

REACTION<br />

VESSEL BOTTOM HEAD FAILS<br />

T T<br />

FAILURE OF DRYWELL EPA SEALS<br />

T T T T T<br />

ORNL-DWG 81-8538 ETD<br />

100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0 1000.0 1100.0<br />

TIME (min)<br />

Fig. 9.27 Drywell temper<strong>at</strong>ure distribution (TB').<br />

r-1<br />

OJ<br />

VO


1600.0-1<br />

1400.0-<br />

uT 1200.0 H<br />

cc<br />

I-<br />

<<br />

£ 1000.0-1<br />

UJ<br />

UJ<br />

GC<br />

<<br />

o.<br />

800.0-<br />

1 600.0o<br />

o<br />

400.0-<br />

200.0-<br />

VESSEL BOTTOM<br />

HEAD FAILS-<br />

0.0<br />

INCREASE DURING CORIUM<br />

CONCRETE REACTION<br />

T<br />

h-vT<br />

FAILURE OF DRYWELL EPA SEALS<br />

T I<br />

600.0<br />

TIME (min)<br />

100.0 200.0 300.0 400.0 500.0<br />

Fig. 9.28 Drywell temper<strong>at</strong>ure distribution (TUB')<br />

ORNL-DWG 81-8539 ETD<br />

700.0 800.0<br />

o


s.<br />

cc<br />

UJ<br />

cc<br />

Q.<br />

r-<br />

Z<br />

UJ<br />

cc<br />

<<br />

S<br />

o o<br />

(x 105)<br />

10.0<br />

9.0-<br />

80<br />

7.0-<br />

6.0-<br />

5.0<br />

^ 4.0-<br />

<<br />

io<br />

3.0-<br />

2.0-<br />

VESSEL BOTTOM HEAD FAILS-<br />

100.0<br />

ORE UNCOVERY<br />

—T r 1 i ^ 1 1—<br />

200.0 300.0 400.0 500.0 600.0 700.0<br />

TIME (min)<br />

Fig. 9.29 Drywell total pressure (TB'),<br />

FAILURE OF DRYWELL EPA SEALS<br />

ORNL-DWG 81-8540 ETD<br />

T T<br />

800.0 900.0 1000.0 1100.0


CO<br />

0.<br />

UJ<br />

CC<br />

3<br />

CO<br />

CO<br />

UJ<br />

cc<br />

Q.<br />

(x 105)<br />

8.0<br />

7.0-<br />

6.0-<br />

5.0-<br />

< 4.0-<br />

cc<br />

<<br />

Q.<br />

<<br />

UJ<br />

r-<br />

CO<br />

3.0-<br />

2.0-<br />

1.0-<br />

0.0<br />

VESSEL BOTTOM HEAD FAILS<br />

100.0<br />

CORE UNCOVERY<br />

i r Ti<br />

i^ i r<br />

200.0 300.0 400.0 500.0 600.0 700.0 800.0<br />

TIME (min)<br />

FAILURE OF DRYWELL EPA SEALS<br />

Fig. 9.30 Drywell steam partial pressure (TB').<br />

ORNL-DWG 81-8541 ETD<br />

I I I<br />

900.0 1000.0 1100.0<br />

ro


CO<br />

Q.<br />

(x 104)<br />

10.0<br />

8.0-<br />

uj6.0rr a.<br />

r-<br />

CC<br />

<<br />

Q.<br />

o<br />

o<br />

cc<br />

Q<br />

>-<br />

I<br />

4.0<br />

2.0<br />

0.0<br />

H, SWEPT INTO WETWELL AS<br />

VESSEL BOTTOM HEAD FAILS-<br />

Zr-H20 REACTION BEGINS-<br />

FAILURE OF DRYWELL EPA SEALS<br />

0.0 1000 200.0 300.0 400.0 500.0 600.0 700.0 800.0 900.0<br />

TIME (min)<br />

Fig. 9.31 Drywell hydrogen partial pressure (TB').<br />

ORNL-DWG 81-8542 ETD<br />

1000.0<br />

-I<br />

1100.0<br />

H><br />

OJ


(x 104)<br />

30.0-<br />

« 25.0<br />

0-<br />

0.0<br />

NON-CONDENSABLES SWEPT INTO WETWELL<br />

AS VESSEL BOTTOM HEAD FAILS<br />

I 1 I I<br />

0.0 100.0 200.0 300.0 400.0<br />

I I<br />

500.0 600.0<br />

TIME (min)<br />

•FAILURE OF DRYWELL EPA SEALS<br />

Fig. 9.32 Drywell non-condensables partial pressure (TB')<br />

ORNL-DWG 81-8543 ETD<br />

700.0 800.0 900.0 1000.0 1100.0<br />

*»<br />

*•


(ed) sansssad iNswiavdwoo nvioi<br />

in<br />

O O<br />

"~ r-*<br />

X<br />

I I I I<br />

q o<br />

Oo<br />

o<br />

«b io IO -^ o<br />

frj<br />

00<br />

CO<br />

CO<br />

cc<br />

3<br />

l u<br />

rH<br />

cc<br />

Q<br />

UJ<br />

8<br />

c<br />

1<br />

co<br />

_i<br />

<<br />

UJ<br />

CO<br />

<<br />

o.<br />

UJ<br />

cu<br />

u<br />

3<br />

CO<br />

co<br />

OJ<br />

M<br />

f-HJ<br />

VESSEL BOTTOM HEAD FAILS—<br />

rr<br />

O<br />

00<br />

O<br />

5<br />

Q<br />

I<br />

145


CO<br />

(x 105)<br />

6.0<br />

5.0-<br />

uj 4.0<br />

cc<br />

3<br />

CO<br />

CO<br />

UJ<br />

cc<br />

-J 3.0-1<br />

<<br />

ioc<br />

<<br />

Q.<br />

< 2.0<br />

UI<br />

co<br />

1.0-<br />

0.0<br />

0.0<br />

VESSEL<br />

BOTTOM<br />

HEAD<br />

FAILS-<br />

^<br />

100.0 200.0<br />

-FAILURE OF DRYWELL EPA SEALS<br />

300.0 400.0<br />

TIME (min)<br />

500.0 600.0<br />

Fig. 9.34 Drywell steam partial pressure (TUB'),<br />

ORNL-DWG 81-8545 ETD<br />

700.0 800.0<br />

H><br />

ON


o<br />

Q_<br />

UJ<br />

CC<br />

3<br />

UJ<br />

IX<br />

a.<br />

(x 104)<br />

8.0<br />

7.0-<br />

6.0<br />

5.0-<br />

3 4.0<br />

cc<br />

<<br />

a.<br />

Z<br />

UJ<br />

a<br />

o<br />

cc<br />

a<br />

>x<br />

3.0-<br />

2.0-<br />

1.0-<br />

0.0-f<br />

H2 SWEPT INTO<br />

WETWELL AS<br />

VESSEL BOTTOM<br />

HEAD FAILS-<br />

Zr-H20<br />

REACTION<br />

BEGINS<br />

200.0<br />

FAILURE OF DRYWELL EPA SEALS<br />

300.0 400.0<br />

TIME (min)<br />

500.0 600.0<br />

Fig. 9.35 Drywell hydrogen partial pressure (TUB').<br />

ORNL-DWG 81-8546 ETD<br />

700.0 800.0<br />

•vj


(x 104)<br />

25.0<br />

£ 20.0-<br />

3<br />

CO<br />

CO<br />

UJ<br />

cc<br />

Q.<br />

^ 150<br />

cc<br />

<<br />

CO<br />

UJ<br />

_l<br />

<<br />

CO<br />

z<br />

o<br />

u<br />

I<br />

z<br />

o<br />

z<br />

10.0-<br />

5.0<br />

0.0 -f<br />

Zr-H20<br />

REACTION/<br />

BEGINS-<br />

VATMOSPHERIC<br />

PRESSURE<br />

0.0 100.0<br />

I<br />

200.0<br />

-NON-CONDENSABLES SWEPT INTO WETWELL<br />

AS VESSEL BOTTOM HEAD FAILS<br />

FAILURE OF DRYWELL EPA SEALS<br />

300.0 400.0<br />

TIME (min)<br />

I<br />

500.0<br />

—T<br />

600.0<br />

Fig. 9.36 Drywell non-condensables partial pressure (TUB'),<br />

ORNL-DWG 81-8547 ETD<br />

I<br />

700.0 800.0<br />

oo


149<br />

As the drywell ambient temper<strong>at</strong>ure exceeds 204°C (400°F), the EPA<br />

elastomeric sealing m<strong>at</strong>erials start to deterior<strong>at</strong>e and venting of the<br />

drywell begins. When the ambient temper<strong>at</strong>ure has exceeded 260°C (500°F),<br />

the EPA elastomeric sealing m<strong>at</strong>erials have decomposed to such an extent<br />

th<strong>at</strong> the EPA seals are blown out of the containment wall by the elev<strong>at</strong>ed<br />

pressure within the drywell. This gre<strong>at</strong>ly increases the containment leak<br />

age (Fig. 9.10).<br />

9.5.2 Wetwell response<br />

The condens<strong>at</strong>ion of the SRV steam discharge within the pressure sup<br />

pression pool is generally accomplished without undue pressure stresses on<br />

the containment wall. If, however, conditions are such th<strong>at</strong> complete con<br />

dens<strong>at</strong>ion of the steam discharge does not occur, pressure loads signifi<br />

cantly in excess of design limits can result, leading eventually to wet<br />

well rupture.<br />

Relief valve steam discharge into the pressure suppression pool is<br />

accompanied by pressure oscill<strong>at</strong>ions of varying characteristics which are<br />

functions of the steam mass flux and local pool w<strong>at</strong>er temper<strong>at</strong>ures as well<br />

as the type of sparger device installed <strong>at</strong> the discharge line terminus.<br />

It has been observed th<strong>at</strong> condens<strong>at</strong>ion instability can occur when a<br />

submerged pipe vent discharges steam <strong>at</strong> flow r<strong>at</strong>es higher than critical<br />

(sonic discharge) with a sufficiently high ambient pool temper<strong>at</strong>ure- the<br />

so-called "Wurgassen effect". The threshold of instability is character<br />

ized by an increase in the amplitude of pressure oscill<strong>at</strong>ions which nor<br />

mally accompany condens<strong>at</strong>ion <strong>at</strong> supercritical flow r<strong>at</strong>es.<br />

At present, ramshead-type sparger devices are installed on the relief<br />

valve tail pipe discharge lines <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Plant. The ramshead<br />

device consists of two 90° elbows welded back-to-back to form a modified<br />

T-junction, and provides an improvement in condens<strong>at</strong>ion performance over<br />

th<strong>at</strong> of a straight vertical pipe. The horizontal discharge from the ram<br />

shead allows the rising convection currents and induced secondary flows to<br />

circul<strong>at</strong>e cooler w<strong>at</strong>er around the steam plumes r<strong>at</strong>her than stagn<strong>at</strong>e<br />

against a downward flow of steam. However, small scale tests have shown<br />

th<strong>at</strong> it also has the potential to produce unstable condens<strong>at</strong>ion and con<br />

comitant large pressure stresses when sufficiently high pool w<strong>at</strong>er temper<br />

<strong>at</strong>ure is reached during supercritical (sonic) discharge. For this reason,<br />

certain limit<strong>at</strong>ions on plant oper<strong>at</strong>ion are established in the <strong>Browns</strong> <strong>Ferry</strong><br />

Technical Specific<strong>at</strong>ions to preclude any possible steam discharge through<br />

the ramshead devices <strong>at</strong> pool temper<strong>at</strong>ures gre<strong>at</strong>er than 77°C (170°F).<br />

In the near future, the ramshead devices <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Plant<br />

will be replaced by T-quencher sparger devices similar to th<strong>at</strong> shown in<br />

Fig. D-2 of Appendix D. Tests have shown th<strong>at</strong> the T-quencher spargers<br />

produce lower loads during the initial air-clearing upon relief valve ac<br />

tu<strong>at</strong>ion and permit smooth condens<strong>at</strong>ion of the steam discharge <strong>at</strong> pool tem<br />

per<strong>at</strong>ures up to 93°C (200°F). For this study, it was assumed th<strong>at</strong> the SRV<br />

discharge lines termin<strong>at</strong>e in T-quencher spargers.<br />

Although the use of T-quenchers considerably improves the steam con<br />

dens<strong>at</strong>ion characteristics rel<strong>at</strong>ed to SRV steam discharges, the constricted<br />

flows introduced by the T-quencher have caused insufficient thermal mixing<br />

in the suppression pool. The resultant thermal str<strong>at</strong>ific<strong>at</strong>ion in the pool


150<br />

can produce much higher local w<strong>at</strong>er temper<strong>at</strong>ure in the vicinity of the Tquenchers<br />

although the average pool temper<strong>at</strong>ure remains quite low.<br />

The problem of thermal str<strong>at</strong>ific<strong>at</strong>ion has been found to be signific<br />

ant for the sequences TUB' and TUPB', in which the HPCI and RCIC sys<br />

tems are assumed inoper<strong>at</strong>ive. Without injection capability, core uncovery<br />

and subsequent degrad<strong>at</strong>ion occur early in the <strong>St<strong>at</strong>ion</strong> Blackout when the<br />

level of decay he<strong>at</strong> is rel<strong>at</strong>ively high so th<strong>at</strong> a large amount of super<br />

he<strong>at</strong>ed steam and noncondensibles is discharged from the T-quenchers into<br />

the suppression pool in a short period of time. The average suppression<br />

pool temper<strong>at</strong>ure is plotted as a function of time for sequences TB' and<br />

TUB* in Figs. 9.37 and 9.38 respectively.<br />

In sequence TUB', it is realistically assumed th<strong>at</strong> without oper<strong>at</strong>or<br />

action, reactor vessel pressure control over the long term would be by re<br />

pe<strong>at</strong>ed cycling of the same relief valve.* Because of the high steam mass<br />

flux into the suppression pool bay in which the discharging T-quencher is<br />

loc<strong>at</strong>ed, significant thermal str<strong>at</strong>ific<strong>at</strong>ion would be expected. MARCH com<br />

put<strong>at</strong>ions show th<strong>at</strong> the difference between the local and average suppres<br />

sion pool temper<strong>at</strong>ures can be estim<strong>at</strong>ed to increase from about 5°C <strong>at</strong> the<br />

beginning of the transient to about 40°C 100 minutes l<strong>at</strong>er. This means<br />

th<strong>at</strong> the suppression pool would lose its condens<strong>at</strong>ion effectiveness; the<br />

resulting pressure loads from the SRV discharge of steam and noncondensi<br />

bles would rapidly increase, leading to a possible rupture of the wetwell<br />

which could occur before the overtemper<strong>at</strong>ure-induced failure of the dry-<br />

well.<br />

The drywell pressure sign<strong>at</strong>ures for the sequences TB' and TUB' are<br />

shown in Figs. 9.29 through 9.36. The general trends are again very sim<br />

ilar, except for the timing of events. The pressure peaks for the sequence<br />

TB' are generally higher than those for the sequence TUB'; this is <strong>at</strong>tri<br />

buted to the presence of a larger w<strong>at</strong>er inventory as a result of the fourhour<br />

period of HPCI injection during sequence TB'.<br />

The wetwell temper<strong>at</strong>ure sign<strong>at</strong>ures are given in Figs. 9.37 and 9.38,<br />

and the average pressure distributions are given in Figs. 9.39 through<br />

9.46 for sequences TB-* and TUB'. The plotted pressures do not include the<br />

effect of pressure waves resulting from condens<strong>at</strong>ion instabilities or the<br />

vapor jet plumes eman<strong>at</strong>ing from the T-quencher spargers.<br />

*A1though four of the thirteen SRVs share the lowest nominal setpoint<br />

of 7.72 MPa (1105 psig), practical consider<strong>at</strong>ions dict<strong>at</strong>e th<strong>at</strong> there<br />

would be one lowest-set valve.


UJ<br />

cc<br />

3<br />

r-<br />

550.0<br />

500.0-<br />

cc 450.0<br />

ui<br />

a.<br />

UJ<br />

r-<br />

2 400.0 H<br />

r-<br />

CC<br />

<<br />

a.<br />

O<br />

o<br />

350.0-<br />

300.0<br />

FAILURE OF VESSEL BOTTOM HEAD<br />

Zr-H20 REACTION BEGINS<br />

CORE UNCOVERY<br />

-VENTING BY FAILURE OF<br />

DRYWELL EPA SEALS<br />

-i 1 1 1 1 I 1<br />

0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 800.0<br />

TIME (min)<br />

Fig. 9.37 Wetwell temper<strong>at</strong>ure distribution (TB').<br />

ORNL-DWG 81-8548 ETD<br />

900.0 1000.0 1100.0


UJ<br />

cc<br />

3<br />

r-<br />

550.0 -r<br />

500.0<br />

cc 450.0<br />

UJ<br />

o.<br />

UJ<br />

UJ<br />

H<br />

CC<br />

<<br />

a.<br />

O O<br />

400.0-<br />

350.0-<br />

300.0<br />

0.0<br />

FAILURE OF VESSEL BOTTOM HEAD<br />

Zr-H20 REACTION BEGINS<br />

100.0 200.0<br />

-VENTING BY FAILURE OF DRYWELL EPA SEALS<br />

—1<br />

300.0<br />

1<br />

400.0<br />

TIME (min)<br />

500.0<br />

Fig. 9.38 Wetwell temper<strong>at</strong>ure distribution (TUB').<br />

—I<br />

600.0<br />

ORNL-DWG 81-8549 ETD<br />

700.0 800.0<br />

to


(x 105)<br />

10.0-<br />

9.0<br />

« CD 8(H<br />

Q.<br />

UJ<br />

CC<br />

3<br />

CO<br />

CO<br />

UJ<br />

cc<br />

Q.<br />

UJ<br />

5<br />

rcr<br />

<<br />

o.<br />

5<br />

O<br />

o<br />

7.0-<br />

6.0-<br />

5.0-<br />

4.0-<br />

3.0-<br />

2.0-<br />

FAILURE OF VESSEL BOTTOM HEAC<br />

Zr-H20 REACTION BEGINS<br />

1.0-<br />

0.0 100.0 200.0 300.0 400.0<br />

500.0 600.0<br />

TIME (min)<br />

-VENTING BY FAILURE OF<br />

DRYWELL EPA SEALS<br />

Fig. 9.39 Wetwell total pressure (TB'),<br />

ORNL-DWG 81-8550 ETD<br />

T<br />

T T<br />

700.0 800.0 900.0 1000.0 1100.0<br />

0/1<br />

OJ


CD<br />

Q.<br />

(x 104<br />

25.0-1<br />

20.0-<br />

UJ<br />

CC<br />

| 15.0<br />

UJ<br />

cc<br />

Ol<br />

r-<br />

CC<br />

<<br />

Q.<br />

<<br />

UJ<br />

I-<br />

10.0-<br />

5.0-<br />

0.0<br />

FAILURE OF VESSEL BOTTOM HEAD-<br />

CORE UNCOVERY<br />

T<br />

100.0 200.0 300.0 400.0<br />

—I I<br />

500.0 600.0<br />

TIME (min)<br />

VENTING BY FAILURE OF<br />

DRYWELL EPA SEALS<br />

ATMOSPHERIC PRESSURE<br />

—I 1<br />

700.0 800.0<br />

Fig. 9.40 Wetwell steam partial pressure (TB')<br />

ORNL-DWG 81-8551 ETD<br />

1 I<br />

900.0 1000.0 1100.0<br />

On


CD<br />

Ch<br />

(x 104)<br />

25.0<br />

20.0-<br />

oi<br />

cc<br />

3<br />

CO<br />

£ 15.0cc<br />

r-<br />

0C<br />

<<br />

CL<br />

UJ<br />

o<br />

O<br />

cc<br />

a<br />

>x<br />

10.0-<br />

5.0-<br />

0.0<br />

FAILURE OF VESSEL BOTTOM HEAD<br />

Zr-H20 REACTION BEGINS<br />

0.0 100.0 200.0 300.0<br />

400.0 500.0<br />

TIME (min)<br />

-VENTING BY FAILURE OF<br />

DRYWELL EPA SEALS<br />

T<br />

600.0<br />

Fig. 9.41 Wetwell hydrogen partial pressure (TB'),<br />

ORNL-DWG 81-8552 ETD<br />

—I 1 I I<br />

700.0 800.0 900.0 1000.0 1100.0<br />

On


CD<br />

Ql<br />

CC<br />

(x 105)<br />

7.0<br />

6.0<br />

w 5.0<br />

CO<br />

UJ<br />

cc<br />

CL<br />


200.0 300.0 400.0<br />

TIME (min)<br />

500.0<br />

Fig. 9.43 Wetwell total pressure (TUB').<br />

ORNL-DWG 81-8554 ETD<br />

600.0 700.0 800.0


CO<br />

Q.<br />

(x 104)<br />

6.0<br />

5.0-<br />

m 4.0<br />

cc<br />

3<br />

CO<br />

CO<br />

UJ<br />

cc<br />

Q.<br />

rcc<br />

<<br />

3.0-<br />

< 2.0 H<br />

UJ<br />

rco<br />

1.0-<br />

0.0<br />

FAILURE OF<br />

VESSEL<br />

BOTTOM<br />

HEAD<br />

0.0 100.0 200.0<br />

VENTING BY FAILURE<br />

OF DRYWELL EPA SEALS<br />

WETWELL ATMOSPHERE IS NOT PURE STEAM<br />

T I<br />

T<br />

300.0 400.0<br />

TIME (min)<br />

500.0 600.0<br />

Fig. 9.44 Wetwell steam partial pressure (TUB').<br />

ORNL-DWG 81-8555 ETD<br />

I<br />

700.0 800.0<br />

on<br />

CO


(x 104)<br />

20.0<br />

£ 15.0-<br />

UJ<br />

cc<br />

3<br />

UJ<br />

cc<br />

Cl<br />

j* 10.0-<br />

oc<br />

< CL<br />

z<br />

UJ<br />

(J<br />

O<br />

CC<br />

Q<br />

£ 5.0-1<br />

0.0<br />

FAILURE OF<br />

VESSEL<br />

BOTTOM<br />

HEAD<br />

0.0<br />

II<br />

100.0 200.0 300.0 400.0<br />

TIME (min)<br />

VENTING BY FAILURE OF DRYWELL EPA SEALS<br />

SOME HYDROGEN REMAINS IN WETWELL ATMOSPHERE<br />

500.0 600.0<br />

Fig. 9.45 Wetwell hydrogen partial pressure (TUB')<br />

ORNL-DWG 81-8556 ETD<br />

I<br />

700.0 800.0<br />

On


(x 105)<br />

6.0<br />

_ 5.0-<br />

CO<br />

Cu<br />

CC<br />

3<br />

CO<br />

J2 4.0<br />

cc<br />

CL<br />

rcc<br />

<<br />

a.<br />

CO<br />

CO<br />

<<br />

CO<br />

z<br />

UJ<br />

Q<br />

z<br />

o o<br />

I<br />

z<br />

o<br />

z<br />

3.0-<br />

2.0-<br />

1.0-<br />

0.0<br />

FAILURE OF<br />

VESSEL<br />

BOTTOM<br />

HEAD<br />

0.0 100.0 200.0<br />

VENTING BY FAILURE OF DRYWELL EPA SEALS<br />

ORNL-DWG 81-8557 ETD<br />

SOME NON-CONDENSABLES REMAIN IN WETWELL ATMOSPHERE<br />

300.0<br />

I<br />

400.0<br />

TIME (min)<br />

Fig. 9.46 Wetwell non-condensables partial pressure (TUB')<br />

500.0 600.0 700.0 800.0<br />

o><br />

o


161<br />

10. PLANT STATE RECOGNITION AND OPERATOR MITIGATING ACTIONS<br />

10.1 Introduction<br />

The accident sign<strong>at</strong>ures developed in Sect. 9 provide baseline infor<br />

m<strong>at</strong>ion for six possible sequences leading to core meltdown th<strong>at</strong> might oc<br />

cur during a <strong>St<strong>at</strong>ion</strong> Blackout. The objectives of this chapter are to ex<br />

amine these same sequences from the oper<strong>at</strong>or's standpoint in order to<br />

identify and evalu<strong>at</strong>e potential preventive and corrective actions keyed to<br />

the time windows available.<br />

As discussed in Sect. 9, a number of plant safety systems would func<br />

tion autom<strong>at</strong>ically during a <strong>St<strong>at</strong>ion</strong> Blackout. The autom<strong>at</strong>ic safety system<br />

responses include reactor scram, vessel pressure control by SRV oper<strong>at</strong>ion,<br />

and level control through cycling of the HPCI system. Thus, assuming no<br />

independent secondary failures, the reactor could be maintained in a safe<br />

stable st<strong>at</strong>e without oper<strong>at</strong>or action until DC power is lost <strong>at</strong> an assumed<br />

four hours into the <strong>blackout</strong>. After the loss of DC power, oper<strong>at</strong>or action<br />

would be crucial in <strong>at</strong>tempting to avert the impending core degrad<strong>at</strong>ion.<br />

10.2 Plant St<strong>at</strong>e Recognition<br />

To enable the oper<strong>at</strong>or to better identify and evalu<strong>at</strong>e potential<br />

mitig<strong>at</strong>ing actions during a <strong>St<strong>at</strong>ion</strong> Blackout, the accident progression is<br />

c<strong>at</strong>egorized into a number of plant st<strong>at</strong>es. The available time windows for<br />

each plant st<strong>at</strong>e are determined from the baseline inform<strong>at</strong>ion provided in<br />

Sect. 9. The loc<strong>at</strong>ion of the plant st<strong>at</strong>es within each sequence is shown<br />

in Fig. 10.1, with the sequence chosen for the fission product transport<br />

analysis of Volume 2 indic<strong>at</strong>ed by a dashed line.<br />

Plant St<strong>at</strong>e 1 (0-s). This is the initial st<strong>at</strong>e <strong>at</strong> the moment of loss of<br />

offsite and onsite power, and is common to all of the <strong>blackout</strong> sequences.<br />

Plant St<strong>at</strong>e 2 (0-625 s). This st<strong>at</strong>e represents the period of autom<strong>at</strong>ic<br />

plant safety system response and is common to the six sequences considered<br />

in detail in this report.<br />

Plant St<strong>at</strong>e 3 (625 s-240 min). This st<strong>at</strong>e is applicable to sequences<br />

TB-* and TPB'. It is characterized by the availability of adequ<strong>at</strong>e de<br />

cay he<strong>at</strong> removal by relief valve oper<strong>at</strong>ion and the HPCI and RCIC injection<br />

systems, which are dependent on DC power from the unit b<strong>at</strong>tery.<br />

Plant St<strong>at</strong>e 3A (625 s-240 min). This st<strong>at</strong>e is applicable to' sequences<br />

TVB' and TVPB'. It is characterized by oper<strong>at</strong>or action to control level<br />

by oper<strong>at</strong>ion of the RCIC system (only) and to rapidly depressurize the re<br />

actor vessel by remote-manual relief valve actu<strong>at</strong>ion. The loss of fluid<br />

through the relief valve exceeds the capacity of the RCIC system for a<br />

short period of time, which causes a momentary core uncovery early in these<br />

sequences.<br />

Plant St<strong>at</strong>e 3B (625 s-28 min). This st<strong>at</strong>e is applicable to sequences TUB'<br />

and TUPB'. In these sequences, the HPCI and RCIC systems are assumed to be<br />

inoperable from the inception of the <strong>blackout</strong>, because of equipment fail<br />

ure. This st<strong>at</strong>e is characterized by decreasing w<strong>at</strong>er level.<br />

Plant St<strong>at</strong>e 4 (240-295 min). This st<strong>at</strong>e is applicable to sequences TB' and<br />

TPB'. This is the period immedi<strong>at</strong>ely following the loss of DC power,


INITIATING EVENT -<br />

LOSS OF OFFSITE<br />

AND ONSITE<br />

ac POWER<br />

YES<br />

A<br />

V NO<br />

SYSTEM<br />

AUTOMATIC<br />

RESPONSES<br />

HPCI AND<br />

RCIC<br />

OPERABLE<br />

ONLY RCIC<br />

OPERABLE<br />

STATE 3B<br />

MANUAL SRV<br />

DEPRESSURIZATION<br />

WITHIN 15 min.<br />

STATE 3A<br />

LOSS OF dc POWER -<br />

HPCI/RCIC INOPERABLE<br />

| STATE 4<br />

I<br />

STATE 4A<br />

SRV<br />

DEPRESSURIZATION<br />

BEFORE LP ECCS<br />

RESTORATION<br />

I STATE(<br />

STATE 5B<br />

LOW PRESSURE ECCS<br />

OPERABLE - OFFSITE<br />

ac POWER RESTORED<br />

STATE 8A<br />

STATE 7A<br />

STATE 8B<br />

Fig. 10.1 Oper<strong>at</strong>or key action event tree.<br />

ORNL-DWG 81-8163 ETD<br />

NO CORE DAMAGE (TPB')<br />

CORE MELT ITPB)<br />

CORE MELT (TB'l<br />

NO CORE DAMAGE<br />

NO CORE DAMAGE (T,B' AND T,PB')<br />

CORE MELT IT„B' ANDTVPB')<br />

NO CORE DAMAGE<br />

POTENTIAL CORE DAMAGE<br />

NO CORE DAMAGE (TUPB')<br />

CORE MELT (TUPB'I<br />

CORE MELT (TUB')<br />

POTENTIAL CORE DAMAGE


163<br />

power, characterized by the unavailability of the HPCI and RCIC systems<br />

and a steadily decreasing reactor vessel w<strong>at</strong>er level.<br />

Plant St<strong>at</strong>e 4A (240-305 min). This st<strong>at</strong>e is applicable to sequences<br />

TVB' and TVPB', and follows the loss of DC power. This st<strong>at</strong>e is char<br />

acterized by a depressurized reactor vessel, unavailability of the HPCI<br />

and RCIC systems, and a steadily decreasing vessel w<strong>at</strong>er level.<br />

Plant St<strong>at</strong>e 5 (295-305 min). This st<strong>at</strong>e is applicable to sequence TPB'<br />

and is characterized by a stuck-open relief valve, so th<strong>at</strong> the reactor<br />

vessel is depressurized.<br />

Plant St<strong>at</strong>e 5B (28-38 min). This st<strong>at</strong>e is applicable to sequence TUPB'.<br />

This sequence involves the combined secondary failures of inoper<strong>at</strong>ive HPCI<br />

and RCIC systems and a stuck-open relief valve (SORV) from the inception<br />

of the <strong>blackout</strong>. It is characterized by a rapidly decreasing w<strong>at</strong>er level.<br />

Plant St<strong>at</strong>e 6 (295-355 min). This st<strong>at</strong>e is applicable to sequence TB'<br />

only. It is characterized by boiloff of the reactor vessel w<strong>at</strong>er inven<br />

tory due to autom<strong>at</strong>ic relief valve actu<strong>at</strong>ion with the reactor vessel fully<br />

pressurized, and termin<strong>at</strong>es with the beginning of core melt.<br />

Plant St<strong>at</strong>e 6B (28-70 min). This st<strong>at</strong>e is applicable to sequence TUB'.<br />

It is characterized by a pressurized reactor vessel, core uncovery, and<br />

the beginning of core melt.<br />

Plant St<strong>at</strong>e 7 (305-360 min). This st<strong>at</strong>e is applicable to sequence TPB'.<br />

It is characterized by a depressurized reactor vessel, unavailability of<br />

the low pressure ECCS injection systems, decreasing w<strong>at</strong>er level, core un<br />

covery, and the beginning of core melt.<br />

Plant St<strong>at</strong>e 7A (305-360 min). This st<strong>at</strong>e is applicable to sequences<br />

TVB' and TVPB' is identical to st<strong>at</strong>e 7.<br />

Plant St<strong>at</strong>e 7B (38-360 min). This st<strong>at</strong>e is applicable to sequence TUPB'<br />

and is identical to st<strong>at</strong>e 7.<br />

Plant St<strong>at</strong>e 8 (305-360 min). This st<strong>at</strong>e is applicable to sequence TPB'.<br />

It is characterized by a depressurized reactor vessel and the recovery of<br />

AC power, which permits the restor<strong>at</strong>ion of normal vessel w<strong>at</strong>er level.<br />

Plant St<strong>at</strong>e 8A (305-360 min). This st<strong>at</strong>e is applicable to sequences<br />

TVB' and TVPB' and is identical to st<strong>at</strong>e 8.<br />

Plant St<strong>at</strong>e 8B (38-360 min). This st<strong>at</strong>e is applicable to sequence TUPB'<br />

and is identical to st<strong>at</strong>e 8.<br />

10.3 Oper<strong>at</strong>or Key Action Event Tree<br />

For sequences TUB' and TUPB', and after the loss of DC power in the<br />

case of sequences TB', TPB', TVB', and TVPB', mitig<strong>at</strong>ing action by the<br />

oper<strong>at</strong>or is essential if core degrad<strong>at</strong>ion is to be avoided and the plant<br />

brought to a safe stable st<strong>at</strong>e.<br />

Upon restor<strong>at</strong>ion of AC power, the oper<strong>at</strong>or's primary responsibility<br />

is to ensure vessel depressuriz<strong>at</strong>ion and oper<strong>at</strong>ion of the low pressure in<br />

jection systems.<br />

The oper<strong>at</strong>or key action event tree is shown in Fig. 10.1.<br />

10.4 Oper<strong>at</strong>or Mitig<strong>at</strong>ing Actions<br />

In addition to continued efforts to restore electrical power, the<br />

recommended actions after the loss of w<strong>at</strong>er injection capability when


164<br />

boiloff and core damage become inevitable include the use of portable<br />

pumps, perhaps provided by fire engines, to flood the drywell in an <strong>at</strong><br />

tempt to preclude melt-through of the reactor vessel. If successful, this<br />

would keep the degraded core inside the vessel and prevent gross contain<br />

ment failure and the corresponding major releases of radioactivity. For<br />

the sequences TUB' and TUPB', in which injection capability is assumed lost<br />

<strong>at</strong> the inception of the <strong>blackout</strong>, a drywell flooding r<strong>at</strong>e of 3,200 H/s<br />

(50,000 gpm) would be necessary to flood the drywell to the level of the<br />

reactor vessel core prior to reactor vessel melt-through.


165<br />

11. INSTRUMENTATION AVAILABLE FOLLOWING<br />

LOSS OF 250 VOLT DC POWER<br />

Reactor vessel level and pressure control can be maintained during a<br />

<strong>St<strong>at</strong>ion</strong> Blackout for as long as 250 volt DC power from the unit b<strong>at</strong>tery<br />

remains available, as discussed in Sect. 8. The instrument<strong>at</strong>ion available<br />

during this initial phase of a <strong>St<strong>at</strong>ion</strong> Blackout was discussed in Sect. 5.<br />

It is the purpose of this section to discuss the instrument<strong>at</strong>ion which<br />

would remain oper<strong>at</strong>ional after the unit b<strong>at</strong>tery is exhausted; this final<br />

phase of a <strong>St<strong>at</strong>ion</strong> Blackout would constitute a Severe Accident because<br />

there would be no means of injecting w<strong>at</strong>er into the reactor vessel to<br />

maintain a w<strong>at</strong>er level over the core.<br />

In addition to the 250 volt unit b<strong>at</strong>tery system, there are two smal<br />

ler b<strong>at</strong>tery systems which supply power to Control Room instrument<strong>at</strong>ion and<br />

alarm circuits. The first of these is a 24 volt DC system which supplies<br />

power to the Source Range and Intermedi<strong>at</strong>e Range neutron flux monitors as<br />

well as radi<strong>at</strong>ion monitors for the off-gas, RHR Service W<strong>at</strong>er, Liquid Radwaste,<br />

Reactor Building Closed Cooling W<strong>at</strong>er, and Raw Cooling W<strong>at</strong>er sys<br />

tems, none of which would be oper<strong>at</strong>ional during a <strong>St<strong>at</strong>ion</strong> Blackout. The<br />

24 volt b<strong>at</strong>teries for this system are designed to supply the connected<br />

loads for a period of 3 hours without recharging. Since the 250 volt sys<br />

tem b<strong>at</strong>teries are expected to last for a period of four to six hours, it<br />

is unlikely th<strong>at</strong> the 24 volt system would remain available after the 250<br />

volt DC unit distribution system has failed.<br />

The second of the smaller b<strong>at</strong>tery systems is a 48 volt DC power sup<br />

ply and distribution system for the oper<strong>at</strong>ion of the plant's communic<strong>at</strong>ion<br />

and annunci<strong>at</strong>or systems. This system comprises three b<strong>at</strong>teries, one of<br />

which supplies the plant communic<strong>at</strong>ions system while the remaining two<br />

b<strong>at</strong>teries are for the annunci<strong>at</strong>or system. However, the system design pro<br />

vides th<strong>at</strong> the total st<strong>at</strong>ion annunci<strong>at</strong>or load can be supplied from one<br />

b<strong>at</strong>tery. The 48 volt DC system b<strong>at</strong>teries are capable of supplying the<br />

connected loads for a period of eight hours without recharging. This is<br />

well beyond the period of expected oper<strong>at</strong>ion of the 250 volt DC systems<br />

and assures continued availability of the plant communic<strong>at</strong>ions system.<br />

The efficacy of the annunci<strong>at</strong>or system depends upon the availability of<br />

the power supplies to the signal transmission systems of the various sen<br />

sors as well as the 48 volt DC system. Most of the alarm annunci<strong>at</strong>or cap<br />

ability will be lost when the unit b<strong>at</strong>tery fails.<br />

There is reason to believe th<strong>at</strong> plant preferred 120 volt AC single<br />

phase power would remain available for a significant period of time after<br />

failure of the unit b<strong>at</strong>tery. Plant preferred power is obtained from the<br />

plant 250-volt DC system during a <strong>St<strong>at</strong>ion</strong> Blackout by means of a DC-motor,<br />

AC gener<strong>at</strong>or combin<strong>at</strong>ion. The plant b<strong>at</strong>tery is similar to each of the<br />

unit b<strong>at</strong>teries, but would be more lightly loaded during a <strong>St<strong>at</strong>ion</strong> Black<br />

out. The major loads on the plant b<strong>at</strong>tery are the turbo-gener<strong>at</strong>or oil<br />

pumps and seal-oil pumps for the three <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong>s. These pumps<br />

could be stopped within one hour after the inception of a <strong>St<strong>at</strong>ion</strong> Blackout<br />

since the turbo-gener<strong>at</strong>ors will have stopped rolling and there is no jack<br />

ing capability under <strong>St<strong>at</strong>ion</strong> Blackout conditions.<br />

Assuming th<strong>at</strong> plant preferred power does remain available during the<br />

period of core uncovery following the loss of the unit b<strong>at</strong>tery, two


166<br />

sources of valuable inform<strong>at</strong>ion powered by this system and loc<strong>at</strong>ed outside<br />

of the Control Room would remain. The first is an indic<strong>at</strong>ion of the tem<br />

per<strong>at</strong>ures <strong>at</strong> various points within the drywell provided both by a recorder<br />

and an indic<strong>at</strong>or-meter for which the displayed drywell temper<strong>at</strong>ure can be<br />

selected by a set of toggle-switches. *<br />

The second inform<strong>at</strong>ion source provided by plant-preferred power<br />

consists of the temper<strong>at</strong>ures <strong>at</strong> various points on the surface of the re<br />

actor vessel as provided by 46 <strong>at</strong>tached copper-constantan thermocouples.<br />

Unfortun<strong>at</strong>ely, the indic<strong>at</strong>ing range for the instruments reporting the<br />

thermocouple responses is only 315.6°C (0-600°F). However, when the in<br />

strument responses for the thermocouples <strong>at</strong>tached near or on the bottom of<br />

the reactor vessel are pegged <strong>at</strong> the high end, the oper<strong>at</strong>or can be sure<br />

th<strong>at</strong> the core is uncovered, and the only fluid within the vessel is super<br />

he<strong>at</strong>ed steam. Both the drywell temper<strong>at</strong>ure indic<strong>at</strong>ion and the reactor<br />

vessel thermocouple recorder are mounted on panel 9—47, which is loc<strong>at</strong>ed<br />

on the back of the Control Room Panels.<br />

Inform<strong>at</strong>ion concerning the reactor vessel w<strong>at</strong>er level would also be<br />

available outside the Control Room from the mechanical Yarway indic<strong>at</strong>ion<br />

(which requires no electrical power) loc<strong>at</strong>ed <strong>at</strong> the scram panels on the<br />

second floor of the reactor building; this would provide direct indic<strong>at</strong>ion<br />

of the reactor vessel w<strong>at</strong>er level over the range from 14.94 to 9.47 m (588<br />

to 373 in.) above vessel zero. The lower boundary of this Yarway indic<strong>at</strong><br />

ing range is 0.33 m (13 in;) above the top of the active fuel in the<br />

core.<br />

There would be no indic<strong>at</strong>ion of reactor vessel pressure after loss of<br />

the unit b<strong>at</strong>tery. However, it is expected th<strong>at</strong> the vessel pressure would<br />

be maintained in the range of 7.722 to 7.377 MPa (1105 to 1055 psig) by<br />

repe<strong>at</strong>ed autom<strong>at</strong>ic actu<strong>at</strong>ion of a primary relief valve for as long as the<br />

reactor vessel remains intact.<br />

It should be noted th<strong>at</strong> the emergency lighting for the Control Room<br />

is supplied from the 250 volt DC system; after failure of this system<br />

hand-held lighting for the Control Room would be necessary. The door se<br />

curity system is supplied by plant preferred power and would remain oper<br />

able as long as the plant 250 volt DC system is functional. The area<br />

radi<strong>at</strong>ion monitors loc<strong>at</strong>ed throughout the plant are powered from the<br />

Instrument<strong>at</strong>ion and Control buses and would not be oper<strong>at</strong>ional from the<br />

inception of a <strong>St<strong>at</strong>ion</strong> Blackout.


167<br />

12. IMPLICATIONS OF RESULTS<br />

The purpose of this section is to provide a discussion of the pre<br />

sent st<strong>at</strong>e of readiness <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant to cope with a<br />

<strong>St<strong>at</strong>ion</strong> Blackout. The discussion will include consider<strong>at</strong>ion of the avail<br />

able instrument<strong>at</strong>ion, the level of oper<strong>at</strong>or training, the existing emer<br />

gency procedures, and the overall system design.<br />

12.1 Instrument<strong>at</strong>ion<br />

The availability of Control Room instrument<strong>at</strong>ion during the period of<br />

a <strong>St<strong>at</strong>ion</strong> Blackout in which 250 volt DC power remains available has been<br />

discussed in Sect. 5. The most important parameters while injection cap<br />

ability remains are the reactor vessel level and pressure, and these would<br />

be adequ<strong>at</strong>ely displayed in the Control Room during this period. This in<br />

strument<strong>at</strong>ion available after the loss of DC power was discussed in Sect.<br />

11.<br />

The existing instrument<strong>at</strong>ion <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1 which would be<br />

important during a <strong>St<strong>at</strong>ion</strong> Blackout is summarized below, with additional<br />

inform<strong>at</strong>ion concerning the power supplies. The instrument<strong>at</strong>ion is discus<br />

sed in the order given in reference 28, and is loc<strong>at</strong>ed in the Control Room<br />

unless otherwise indic<strong>at</strong>ed.<br />

I. Core<br />

A. Core Exit Temper<strong>at</strong>ure — not available <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong>.<br />

B. Control Rod Position— the rod position indic<strong>at</strong>ing system is<br />

powered by the 120V AC unit-preferred system, which would be<br />

available during a <strong>St<strong>at</strong>ion</strong> Blackout for as long as 250V-CC<br />

power remains available from the unit b<strong>at</strong>tery.<br />

C. Neutron Flux _ The Source Range and Intermedi<strong>at</strong>e Range moni<br />

tors are powered by the 24 volt DC b<strong>at</strong>tery system, which is de<br />

signed to supply the connected loads for a period of 3 hours<br />

under the conditions of a <strong>St<strong>at</strong>ion</strong> Blackout. The Source and In<br />

termedi<strong>at</strong>e Range detectors are withdrawn from the core during<br />

power oper<strong>at</strong>ion to a point 0.61 m (2 ft) below the bottom of the<br />

active fuel to increase their active life, and these detectors<br />

could not be reinserted during a <strong>St<strong>at</strong>ion</strong> Blackout. However, the<br />

rel<strong>at</strong>ive changes in neutron flux following reactor scram will<br />

produce a proportional change in Source Range meter (range: 0.1<br />

to IO6 CPS) response when the detector is fully withdrawn.<br />

II. Reactor Coolant System<br />

A. RCS Pressure — one channel of reactor vessel pressure powered<br />

by the feedw<strong>at</strong>er inverter and another channel powered by the<br />

unit-preferred system, each with a range of 8.274 MPa (0 to 1200<br />

psig), would be available during a <strong>St<strong>at</strong>ion</strong> Blackout for as long<br />

as the unit b<strong>at</strong>tery continues to supply 250 volt DC power.<br />

B. Coolant Level in the Reactor — two channels of reactor vessel<br />

level instrument<strong>at</strong>ion, one each powered by the feedw<strong>at</strong>er in<br />

verter and the unit-preferred system would be available during<br />

<strong>St<strong>at</strong>ion</strong> Blackout for as long as the 250 volt DC unit b<strong>at</strong>tery


168<br />

system remains functional. These two channels each have a range<br />

of 1.524 M (0 to 60 in.) and provide indic<strong>at</strong>ion of the reactor<br />

vessel w<strong>at</strong>er level between 13.41 and 14.94 m (528 and 588 in.)<br />

above the bottom of the vessel, a range which extends over the<br />

upper portion of the steam separ<strong>at</strong>ors. Additional level infor<br />

m<strong>at</strong>ion would be available outside of the Control Room, as fol<br />

lows:<br />

o Two channels of Yarway level indic<strong>at</strong>ion over the range from<br />

9.47 to 14.94 m (373 to 588 in.) above the bottom of the ves<br />

sel are available <strong>at</strong> the backup control panel loc<strong>at</strong>ed in the<br />

Backup Control Room. This instrument<strong>at</strong>ion is powered from<br />

the unit-preferred system; the lower limit of this indic<strong>at</strong>ion<br />

is 0.33 m (13 in.) above the top of the active fuel in the<br />

core.<br />

o The Yarway instruments are loc<strong>at</strong>ed <strong>at</strong> the scram panel on the<br />

second floor of the reactor building and mechanically display<br />

the reactor vessel w<strong>at</strong>er level over the same range as th<strong>at</strong><br />

electrically transmitted to the backup control panel. This<br />

level indic<strong>at</strong>ion <strong>at</strong> the Yarway instruments requires no elec<br />

trical power, and would remain available even after all DC<br />

power was lost.<br />

C. Main Steamline Flow — two channels of steam flow instrumenta<br />

tion powered by the feedw<strong>at</strong>er inverter would provide an indica<br />

tion of total steam flow [range: 2016 kg/s (0 to 16 x IO6<br />

lbs/h)] during a <strong>St<strong>at</strong>ion</strong> Blackout while the unit b<strong>at</strong>tery remains<br />

functional.<br />

D. Main Steamline Isol<strong>at</strong>ion Valves' Leakage Control System Pressure<br />

— not applicable to <strong>Browns</strong> <strong>Ferry</strong>.<br />

E. Primary System Safety Relief Valve Positons, Including ADS —<br />

There is no provision for indic<strong>at</strong>ion of the actual position of<br />

any primary relief valve, including those assigned to the ADS<br />

system. Under normal oper<strong>at</strong>ing conditions, the oper<strong>at</strong>or can<br />

identify a leaking relief valve by means of the recorded tail<br />

pipe temper<strong>at</strong>ures available on charts behind the Control Room<br />

panels, or by the recently installed (December, 1980) acoustic<br />

valve monitors. Both of these leakage detection systems would<br />

be inoperable under <strong>St<strong>at</strong>ion</strong> Blackout conditions.<br />

On the other hand, remote-manual actu<strong>at</strong>ion of a relief<br />

valve is accomplished by energizing the associ<strong>at</strong>ed DC solenoid<br />

oper<strong>at</strong>or, and each valve has lights on the control panel which<br />

indic<strong>at</strong>e whether or not the solenoid for th<strong>at</strong> valve is ener<br />

gized. The capability for this indirect indic<strong>at</strong>ion of success<br />

ful remote-manual valve actu<strong>at</strong>ion is maintained during the per<br />

iod of a <strong>St<strong>at</strong>ion</strong> Blackout in which 250 volt DC power is avail<br />

able from the unit b<strong>at</strong>tery.<br />

F. Radi<strong>at</strong>ion Level in Coolant — not available <strong>at</strong> <strong>Browns</strong> <strong>Ferry</strong>.<br />

III. Containment<br />

A. Primary Containment Pressure — Drywell pressure instrumenta<br />

tion with a range of 0.55 MPa (0-80 psia) powered by the<br />

unit-preferred system will be available during a <strong>St<strong>at</strong>ion</strong>


169<br />

Blackout while the unit b<strong>at</strong>tery remains functional. A set of 12<br />

vacuum breakers ensures th<strong>at</strong> the pressure in the pressure sup<br />

pression pool torus cannot exceed the drywell pressure by more<br />

than 0.003 MPa (0.5 psi).<br />

B. Containment and Drywell Hydrogen Concentr<strong>at</strong>ion — Instruments<br />

for this purpose are provided for each <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong>, but<br />

would not be available during a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

C. Containment and Drywell Oxgyen Concentr<strong>at</strong>ion — Instruments<br />

for this purpose are provided, but as in the case of the hydro<br />

gen monitors, are powered from the Instrument<strong>at</strong>ion and Control<br />

buses which would not be available during a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

D. Primary Containment Isol<strong>at</strong>ion Valve Position — During a Sta<br />

tion Blackout, valve position indic<strong>at</strong>ion is maintained for the<br />

Main Steam Isol<strong>at</strong>ion Valves (MSIV's) and for the systems which<br />

remain operable, i.e., the HPCI and the RCIC systems. However,<br />

valve position indic<strong>at</strong>ion for the primary containment isol<strong>at</strong>ion<br />

valves in the low-pressure injection systems which are powered<br />

by sources not available during a <strong>St<strong>at</strong>ion</strong> Blackout would be<br />

lost.<br />

E. Suppression Pool W<strong>at</strong>er Level — This instrument, powered by<br />

the unit-preferred system, would indic<strong>at</strong>e the w<strong>at</strong>er level in the<br />

torus with a range of 1.27 m (—25 to +25 in.) as long as the<br />

unit b<strong>at</strong>tery is functional.<br />

F. Suppression Pool W<strong>at</strong>er Temper<strong>at</strong>ure — This instrument<strong>at</strong>ion<br />

would not be available during a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

G. Drywell Pressure — This is synonymous with "Primary Contain<br />

ment Pressure" — see "A" above.<br />

H. Drywell Drain Sumps Level — not indic<strong>at</strong>ed. The frequency of<br />

drain pump oper<strong>at</strong>ion for each of the two 1.893 m^ (500 gal.)<br />

drain sumps in the drywell is indic<strong>at</strong>ed in the Control Room<br />

under normal conditions, but would not be operable during a Sta<br />

tion Blackout.<br />

I. High-Range Containment Area Radi<strong>at</strong>ion — not available <strong>at</strong><br />

<strong>Browns</strong> <strong>Ferry</strong>.<br />

IV. Power Conversion Systems<br />

A. Main Feedw<strong>at</strong>er Flow — one channel of flow instrument<strong>at</strong>ion<br />

with a range of 1008 kg/s (0 to 8 x IO6 lbs/h) and powered<br />

by the unit-preferred system is provided for each of the three<br />

feedw<strong>at</strong>er pumps. This instrument<strong>at</strong>ion would remain operable as<br />

long as the unit b<strong>at</strong>tery is functional.<br />

B. Condens<strong>at</strong>e Storge Tank Level — The condens<strong>at</strong>e storage tank<br />

level indic<strong>at</strong>ion [range: 9.75 m (0 to 32 ft)] is powered by the<br />

unit-preferred system and would remain oper<strong>at</strong>ional until the<br />

unit b<strong>at</strong>tery is exhausted.<br />

V. Auxiliary Systems<br />

A. Steam Flow to RCIC — This instrument<strong>at</strong>ion is powered by the<br />

Instrument<strong>at</strong>ion and Control buses and would not be available<br />

during a <strong>St<strong>at</strong>ion</strong> Blackout.


170<br />

B. RCIC Flow — The RCIC pumped flow is indic<strong>at</strong>ed over a range<br />

of 0.044 m3/s (0-700 GPM) on the flow controller, which is<br />

powered by the unit-preferred system and would be available as<br />

long as the unit b<strong>at</strong>tery is functional.<br />

VI. Radi<strong>at</strong>ion Exposure R<strong>at</strong>es — The permanently-installed radi<strong>at</strong>ion<br />

monitors loc<strong>at</strong>ed throughout the plant are powered from the Instrument<strong>at</strong>ion<br />

and Control buses and would not be oper<strong>at</strong>ional during a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

The available Control Room instrument<strong>at</strong>ion is adequ<strong>at</strong>e to monitor the<br />

plant response to a <strong>St<strong>at</strong>ion</strong> Blackout during the estim<strong>at</strong>ed four-hour period<br />

during which 250 volt DC power would remain available from the unit b<strong>at</strong><br />

tery. After the unit b<strong>at</strong>tery is exhausted, virtually all Control Room in<br />

strument<strong>at</strong>ion would be lost and w<strong>at</strong>er could no longer be injected into the<br />

reactor vessel to make up for th<strong>at</strong> lost to the pressure suppression pool<br />

through relief valve actu<strong>at</strong>ion. Consequently, the reactor vessel w<strong>at</strong>er<br />

level would slowly decrease until the core became uncovered.<br />

The most important single parameter during the period of decreasing<br />

w<strong>at</strong>er level following loss of the unit b<strong>at</strong>tery is the reactor vessel<br />

level, which could be monitored <strong>at</strong> the Yarway instruments on the second<br />

floor of the Reactor Building as described in part III B above. In addi<br />

tion, the drywell ambient temper<strong>at</strong>ures and the reactor vessel surface tem<br />

per<strong>at</strong>ures would remain available as long as the plant-preferred 250 volt-<br />

DC system is functional, as described in Sect. 11.<br />

12.2 Oper<strong>at</strong>or Preparedness<br />

There is currently no specific training provided <strong>Browns</strong> <strong>Ferry</strong> Oper<br />

<strong>at</strong>ors in regard to plant response or required oper<strong>at</strong>or actions in the ev<br />

ent of a complete <strong>St<strong>at</strong>ion</strong> Blackout.<br />

A <strong>St<strong>at</strong>ion</strong> Blackout casualty can be run <strong>at</strong> the TVA <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> 1<br />

simul<strong>at</strong>or by selecting the pre-programmed loss-of-offsite-power casualty<br />

and then having the simul<strong>at</strong>or oper<strong>at</strong>or immedi<strong>at</strong>ely punch the diesel-gener<strong>at</strong>or<br />

manual trips in the control room. Since the instrument<strong>at</strong>ion in the<br />

simul<strong>at</strong>ed control room is powered from several diverse sources representa<br />

tive of those <strong>at</strong> the actual plant, the resulting effect closely models a<br />

<strong>St<strong>at</strong>ion</strong> Blackout. This procedure was developed and tested by TVA simula<br />

tor oper<strong>at</strong>ing personnel as an effort in cooper<strong>at</strong>ion with this study, but<br />

has not been used for oper<strong>at</strong>or training.<br />

There is no Emergency Oper<strong>at</strong>ing Instruction to cover a <strong>St<strong>at</strong>ion</strong> Black<br />

out <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant, but there are Emergency Oper<strong>at</strong>ing<br />

Instructions for the loss of individual subsections of the overall AC sys<br />

tem.<br />

With two exceptions, the current level of oper<strong>at</strong>or training and the<br />

existing Emergency Oper<strong>at</strong>ing Instructions are believed adequ<strong>at</strong>e to prepare<br />

the oper<strong>at</strong>or to cope with a <strong>St<strong>at</strong>ion</strong> Blackout during the initial phase in<br />

which 250 volt-DC power would remain available. The first exception in<br />

volves the need to depressurize the reactor vessel within the first hour.<br />

The Technical Specific<strong>at</strong>ions provide th<strong>at</strong> the reactor vessel must be de<br />

pressurized to less than 1.48 MPa (200 psig) if the pressure suppression<br />

pool temper<strong>at</strong>ure exceeds 48.9°C (120°F); this is based on a maximum per<br />

missible temper<strong>at</strong>ure of 76.7°C (170°F) for the pool so th<strong>at</strong> complete con<br />

dens<strong>at</strong>ion of steam is ensured in the event of a LOCA. The Emergency


3 M O<br />

o ro 13<br />

rt X to<br />

C i-t<br />

P p. fu<br />

< p. It<br />

P rt p.<br />

B 3<br />

rt OQ<br />

3<br />

CT OQ rt M<br />

P1 3<br />

rt p O CO<br />

M It<br />

P CO rt l-j<br />

3 rt P 3<br />

Oj p i-I O<br />

to rt<br />

< o<br />

rt i-t<br />

1-1<br />

- <<br />

to<br />

Oh CO<br />

rt CO<br />

X) to<br />

rt I-h<br />

to »•<br />

CO<br />

o n<br />

Ml |-J<br />

3<br />

rt Oh<br />

XT to<br />

it H<br />

P- XT<br />

O rt<br />

3<br />

CO<br />

O fD<br />

P O<br />

O cd B<br />

O rH 0J<br />

O P CD<br />

pJ O CD<br />

p 7T<br />

3 o pit<br />

G co<br />

P- Ml<br />

CO CU<br />

rr Oj rt<br />

p. rt 3<br />

O "3 rt<br />

3 rt rt<br />

rt OQ<br />

CT CD ^<br />

rt CO<br />

Ml C l-l<br />

O M rt<br />

H-x<br />

rt " N C<br />

P<br />

XT<br />

to<br />

cr co<br />

P Vrr<br />

cd<br />

rt rt<br />

rt to<br />

XT<br />

to<br />

n><br />

rt<br />

XI<br />

-S "3<br />

P- l-l<br />

H-1 fD<br />

rH CO<br />

CD<br />

P.°<br />

rt w<br />

co B H<br />

rt XT<br />

rr i-t rt<br />

XT OQ<br />

rt ro co<br />

3 rt<br />

3 O O<br />

rt ^ o<br />

rt 3<br />

O- O Oj<br />

X)<br />

Mi ft rt<br />

O i-j X<br />

i-t p n<br />

rr rt<br />

rt p.-a<br />

3" 3 rr<br />

rt OQ P-<br />

H- XI<br />

3 O 3<br />

OQ XI i-l<br />

rt Xi<br />

rt i-t O<br />

3d fu CD<br />

rt rr rt<br />

_ O<br />

<br />

O 13<br />

H O<br />

O<br />

?o<br />

o<br />

O.<br />

Oj i-t<br />

p P- rt It<br />

CO It P rt<br />

P- O 3<br />

rt o It 13<br />

X 3 o rt<br />

-3 P 1-1 p.<br />

rt<br />

rt B<br />

XT CO<br />

rt<br />

cr m<br />

M Prt<br />

N<br />

P<br />

P It<br />

Oj P-<br />

O. O<br />

p- 3<br />

It •<br />

P*<br />

o<br />

P XT<br />

rH G<br />

CO<br />

It<br />

P- rt<br />

B p<br />

rt i-t<br />

\-H<br />

Ml Vho<br />

l-t l-l<br />

rt<br />

p<br />

o<br />

O<br />

c<br />

l-l<br />

M<br />

ro<br />

3<br />

prt<br />

o<br />

O 3<br />

CD<br />

i-i<br />

rt £<br />

Oj P-<br />

3 rt<br />

rt -T<br />

to<br />

rt P P<br />

CD CD<br />

X)<br />

C 1TJ<br />

fT O O<br />

rt O CD<br />

rt rt co<br />

CT Oh p.<br />

G<br />

i-l M<br />

rt ro<br />

3d a-<br />

H. fu<br />

O rt<br />

3- rt<br />

H<br />

i-I<br />

P<br />

P-<br />

3<br />

P-<br />

3<br />

OQ<br />

3 o<br />

O 3<br />

rt<br />

p -a<br />

3 o<br />

rr o<br />

° 3 rt 2<br />

P<br />

i-t rt<br />

rt rt <<br />

XT OQ rt<br />

« rt<br />

3d O<br />

Pn<br />

>c<br />

3d rt<br />

O<br />

rH i-H<br />

P- O<br />

CD 3<br />

rt OQ<br />

CO<br />

B i-t<br />

p ^<br />

-! o<br />

ro p.<br />

p pco<br />

3<br />

cd ro<br />

ro<br />

m cr<br />

«. «^<br />

p<br />

p- It<br />

3 p.<br />

ro B<br />

o. (D<br />

3 Hrt<br />

O<br />

rt 03<br />

3 a.<br />

^ rr<br />

H-<br />

O O<br />

•a 3<br />

rt CD<br />

M<br />

fu O<br />

rt 03<br />

P- 3<br />

O Oj<br />

m ro<br />

P<br />

ro m<br />

p<br />

i-t o<br />

M P<br />

rt<br />

P CO<br />

o p.<br />

0Q O H<br />

3 13 P<br />

ro cr<br />

r* _^ l-l I-<br />

Oj P- XC p rt<br />

ton' rt<br />

n fu s<br />

P 3 M 3 O<br />

rt p P<br />

i-t<br />

Oj O<br />

o<br />

P rt<br />

O. O o<br />

XI<br />

p rt<br />

1-1<br />

C/n P<br />

i-i<br />

O rt<br />

o.<br />

o<br />

H Ml<br />

3d<br />

fD rr<br />

P-<br />

T) B<br />

i-t rt<br />

fD<br />

co cr<br />

rt rt<br />

3 Ml<br />

rt O<br />

H<br />

o n><br />

"^ r.<br />

to o<br />

O<br />

cu rl<br />

rt rt<br />

So<br />

3<br />

rt r><br />

»-i O<br />

fu <<br />

p. rt<br />

3 H<br />

H-^<br />

3 „<br />

OQ O<br />

O<br />

H- O<br />

B C<br />

•a i-i<br />

rH CO<br />

cr xr<br />

h ro Cfl fD<br />

o> o 03 03 fD<br />

FT 13<br />

to to 2fD a O<br />

l-t M 2 B P- l-l<br />

CO P 3 pj -a 3<br />

rt<br />

M i-t o-<br />

rt O td o o> to<br />

O i-i<br />

oj It* > < 3 Xi<br />

n P- rr i-i<br />

n Oh p. fD<br />

3- CO 7?x> fD O CO<br />

fD O O Oh P. CD<br />

M, G -5 X> G<br />

P- 03 rr fD P p H<br />

fD O<br />

i-t CD rr P-<br />

CO fD P- O<br />

N<br />

CO CL CO M CD fD 03<br />

I<br />

c 3<br />

P-<br />

O X) fD P-<br />

rt 13 MOO<br />

I cr h 0Q Mi 3<br />

O<br />

fD >


172<br />

recommended order of removal of loads if the loss of AC power is per<br />

ceived to be long-term.<br />

3. Recovery procedures should be developed to provide a detailed method<br />

for recovery of vital power supplies and equipment in a safe, effi<br />

cient manner upon restor<strong>at</strong>ion of AC power following a <strong>St<strong>at</strong>ion</strong> Black<br />

out.<br />

12.3 System Design<br />

The existing system design provides sufficient instrument<strong>at</strong>ion and<br />

equipment to maintain decay he<strong>at</strong> removal capability for several hours dur<br />

ing a <strong>St<strong>at</strong>ion</strong> Blackout. The only questionable fe<strong>at</strong>ure of the existing de<br />

sign with regard to the <strong>St<strong>at</strong>ion</strong> Blackout sequence is the provision for<br />

autom<strong>at</strong>ic shifting of the HPCI pump suction to the pressure suppression<br />

pool on high sensed pool level. As discussed in Sect. 8.1, this can lead<br />

to failure of the HPCI system because of the high temper<strong>at</strong>ure of the pre<br />

ssure suppression pool w<strong>at</strong>er <strong>at</strong> the time the shift in pump suction oc<br />

curs.<br />

Separ<strong>at</strong>e provision is made for an autom<strong>at</strong>ic shift of the HPCI pump<br />

suction if the normal condens<strong>at</strong>e storage tank w<strong>at</strong>er source becomes ex<br />

hausted. Thus it appears th<strong>at</strong> the autom<strong>at</strong>ic high pool w<strong>at</strong>er level shift<br />

must have been straight-forwardly based on a concern for the effect of<br />

high w<strong>at</strong>er level in the pressure suppression pool. The basis is not given<br />

in the Technical Specific<strong>at</strong>ions, and it should be noted th<strong>at</strong> there is no<br />

corresponding provision for the RCIC system. It is recommended th<strong>at</strong> the<br />

desirability of an autom<strong>at</strong>ic shift in HPCI pump suction on high suppres<br />

sion pool w<strong>at</strong>er level be reexamined and if found necessary, th<strong>at</strong> the basis<br />

be included in oper<strong>at</strong>or training.


1. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Appendix F.<br />

173<br />

13. REFERENCES<br />

2. Nuclear Regul<strong>at</strong>ory Commission Memorandum from H. R. Denton to Chair<br />

man Ahearne, d<strong>at</strong>ed September 26, 1980: Subject: STATION BLACKOUT.<br />

3. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Paragraph 8.5.2.<br />

4. R. L. Scott, "<strong>Browns</strong> <strong>Ferry</strong> Nuclear Power-Plant Fire on March 22,<br />

1975," Nuclear Safety, 17-5, 592-611 (1976).<br />

5. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Response to AEC Question 4.8.<br />

6. Staff Report, Anticip<strong>at</strong>ed Transients Without Scram for Light W<strong>at</strong>er<br />

Reactors, NUREG-0460, Vol. 2, p. XVI-74.<br />

7. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Response to AEC Question 12.2.16.<br />

8. Continuous System Modeling Program III (CSMP III) Program Reference<br />

Manual, IBM Corpor<strong>at</strong>ion, 4th Ed. (December 1975).<br />

9. "Decay Energy Release R<strong>at</strong>es Following Shutdown of Uranium-Fueled<br />

Thermal Reactors," ANS-5.1, American N<strong>at</strong>ional Standards Institute<br />

(1971).<br />

10. R. T. Lahey, Jr. and P. S. Kam<strong>at</strong>h, "The Analysis of Boiling W<strong>at</strong>er Re<br />

actor Long-Term Cooling," Nuclear Technology, Vol. 49 (June 1980).<br />

11. J. F. Wilson, R. J. Grenda, and J. F. P<strong>at</strong>terson (A-C), "Steam-W<strong>at</strong>er<br />

Separ<strong>at</strong>ion Above a Two-Phase Interface," Trans, Am Nucl. Soa.,<br />

4,356 (1961).<br />

12. R. T. Lahey, Jr. and F. J. Moody, "The Thermal Hydraulics of a Boil<br />

ing W<strong>at</strong>er Nuclear Reactor," American Nuclear Society (1977).<br />

13. R. 0. Wooton and H. I. Avci, MARCH Code Description and User's Man<br />

ual, B<strong>at</strong>telle Columbus Labor<strong>at</strong>aories/USNRC Report NUREG/CR-1711 (Oc<br />

tober 1980).<br />

14. D. W. Hargroves and L. J. Metcalfe, CONTEMPT-LT/028: A Computer<br />

Program for Predicting Containment Pressure-Temper<strong>at</strong>ure Response to a<br />

Loss of Coolant Accident, EG&G Idaho, Inc./USNRC Report NUREG/CR-<br />

0255 (TREE-1279) (March 1979).<br />

15. <strong>Browns</strong> <strong>Ferry</strong> Emergency Oper<strong>at</strong>ing Instruction No. 36, Loss of CooTsant<br />

Accident inside Drywell*<br />

16. S. E. Mays, et al, Second IREP St<strong>at</strong>us Report, Risk Assessment for<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant <strong>Unit</strong> 1, January 1981 (Preliminary).


17. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Section 8.6.<br />

174<br />

18. D. D. Yue and W. A. Condon, "Severe Accident Sequence Assessment of<br />

Hypothetical Complete <strong>St<strong>at</strong>ion</strong> Blackout <strong>at</strong> the <strong>Browns</strong> <strong>Ferry</strong> Nuclear<br />

Plant," 1981 Intern<strong>at</strong>ional ANS/ENS Topical Meeting on Probabilistic<br />

Risk Assessment, Port Chester, N.Y., September 20-24, 1981.<br />

19. Reactor Safety Study, WASH-1400 (NUREG-75/014), U.S. Nuclear Regu<br />

l<strong>at</strong>ory Commission, 1975.<br />

20. F. E. Haskin, et al, "Analysis of a Hypothetical Core Meltdown Acci<br />

dent Initi<strong>at</strong>ed by Loss of Offsite Power for the Zion I PWR," NUREG/<br />

CR-1988, Sandia N<strong>at</strong>ional Labor<strong>at</strong>ories, 1981.<br />

21. M. L. Corradini, "Analysis and Modelling of Steam Explosion Experi<br />

ments," NUREG/CR-2072, Sandia N<strong>at</strong>ional Labor<strong>at</strong>ories, April 1981.<br />

22. D. D. Yue, "Electric Penetr<strong>at</strong>ion Assembly," U.S. P<strong>at</strong>ent 4, 168, 394,<br />

September 1979.<br />

23. American Nuclear Society Proposed Standard ANS-5.1, "Decay Energy<br />

Release R<strong>at</strong>es Following Shutdown of Uranium — Fueled Thermal<br />

Reactors," October 1971, revised October 1973.<br />

24. ANSI/ANS-5.1 (1979), "Decay He<strong>at</strong> Power in Light W<strong>at</strong>er Reactors,"<br />

August 1979.<br />

25. W. B. Wilson, et al, "Actinide Decay Power," LA-UR 79-283, Los Alamos<br />

Scientific Labor<strong>at</strong>ory, June 1979.<br />

26. T. E. Lobdell, "REDYV01 User Manual," NEDO-14580, August 1977.<br />

27. D. D. Christensen, "Interim <strong>Browns</strong> <strong>Ferry</strong> RELAP4/MOD7, <strong>St<strong>at</strong>ion</strong> Black<br />

out Calcul<strong>at</strong>ion," DDC-2-80 Idaho N<strong>at</strong>ional Engineering Labor<strong>at</strong>ory,<br />

October 31, 1980.<br />

28. Table 3, BWR VARIABLES, of Revision 2 to Regul<strong>at</strong>ory Guide 1.97, "In<br />

strument<strong>at</strong>ion for Light-W<strong>at</strong>er-Cooled Nuclear Power Plants to Access<br />

Plant and Environs Conditions During and Following an Accident"<br />

(December 1979).<br />

29. <strong>Browns</strong> <strong>Ferry</strong> FSAR, Paragraph 5.2.1.<br />

30. Safety Evalu<strong>at</strong>ion Report — Mark I Containment Long-Term Program,<br />

NUREG-0661, July 1980.<br />

31. Three Dimensional Pool Swell Modeling of a Mark I Suppression System,<br />

EPRI NP-906, October 1978.<br />

32. H. Nariai, I. Aya, M. Kobayaski, "Thermo-Hydraulic Behavior in a<br />

Model Pressure Suppression Containment During Blowdown," Topics in<br />

Two-Phase He<strong>at</strong> Transfer and Flow, pp. 89-98, Winter ASME Meeting,<br />

1978.


175<br />

33. W. G. Anderson, P. W. Huber, A. A. Sonin, "Small Scale Modeling of<br />

Hydrodynamic Forces in Pressure Suppression Systems," NUREG/CR-0003,<br />

March 1978.<br />

34. B. D. Nichols, C. W. Hirt, "Numerical Simul<strong>at</strong>ion of Boiling W<strong>at</strong>er<br />

Reactor Vent-Clearing Hydrodynamics," Nucl. Sci. &Engr., 73,<br />

196-209.<br />

35. D. Brosche, "Model for the Calcul<strong>at</strong>ion of Vent Clearing Transients in<br />

Pressure Suppression'System," Nucl, Engr. & Des., 38, 131-141,<br />

1976.<br />

36. J. S. Marks, G. B. Andeen, "Chugging and Condens<strong>at</strong>ion Oscill<strong>at</strong>ion<br />

Tests," EPRI NP-1167, September 1979.<br />

37. L. E. Stanford, C. C. Webster, "Energy Suppression and Fission Pro<br />

duct Transport in Pressure-Suppression Pools," ORNL-TM-3448, April<br />

1972.<br />

38. M. Okazaki, "Analysis for Pressure Oscill<strong>at</strong>ion Phenomena Induced by<br />

Steam Condens<strong>at</strong>ion in Containment with Pressure Suppression System,"<br />

Nucl. Sci. and Tech. iA» PP« 30-42, January 1979.<br />

39. J. S. Marks, G. B. Andeen, "Chugging and Condens<strong>at</strong>ion Oscill<strong>at</strong>ion,"<br />

Condens<strong>at</strong>ion He<strong>at</strong> Transfer, pp. 93-102, 18th N<strong>at</strong>ional He<strong>at</strong> Transfer<br />

Conference, San Diego, California, August 1979.<br />

40. W. Kowalchuk, A. A. Sonin, "A Model for Condens<strong>at</strong>ion Oscill<strong>at</strong>ions in<br />

a Vertical Pipe Discharging Steam into a Subcooled W<strong>at</strong>er Pool,"<br />

NUREG/CR-0221, June 1978.<br />

41. D. A. Sargis, J. H. Stubhmiller, S. S. Wang, "A Fundamental Thermal<br />

Hydraulic Model to Predict Steam Chugging Phenomena," Topic in Two-<br />

Phase He<strong>at</strong> Transfer and Flow, pp. 123-133, Winter ASME Meeting,<br />

1978.<br />

42. P. A. Sargis, et al., "Analysis of Steam Chugging Phenomena, Vol. 1,"<br />

EPRI-NP-1305, Janauary 1981.<br />

43. B. J. P<strong>at</strong>terson, "Mark I Containment Program: Montice-llo T-Quencher<br />

Thermal Mixing Test Final Report," NEDO-24542, August 1979.<br />

44. "TRAC-P1A An Advanced Best-Estim<strong>at</strong>e Computer Program for PWR LOCA<br />

Analysis," Los Alamos Scientific Labor<strong>at</strong>ory, NUREG/CR-0665, LA-7777-<br />

MS, May 1979.<br />

45. U.S. Roh<strong>at</strong>gi and P. Saha, "Constitutive Rel<strong>at</strong>ions in TRAC-P1A,"<br />

Brookhaven N<strong>at</strong>ional Labor<strong>at</strong>ory, NUREG/CR-1651, BNL-NUREG-51258,<br />

August 1980.


176<br />

46. "Applic<strong>at</strong>ion of the Coupled Fluid Structure Code PELE-IC to Pressure<br />

Suppression Analysis — Annual Report to NRC for 1979," Lawrence<br />

Livermore Labor<strong>at</strong>ory, NUREG/CR-1179, UCRL-52733.<br />

47. C. W. Hirt, B. D. Nichols, and N. C. Romero, "SOLA — A Numerical<br />

Solution Algorithm for Transient Fluid," Los Alamos Scientific<br />

Labor<strong>at</strong>ory, LA-5852 (1975).<br />

48. <strong>Browns</strong> <strong>Ferry</strong> Startup Test Instruction No. 15, High Pressure Injec<br />

tion System.<br />

49. Flow Diagram Condens<strong>at</strong>e Storage and Supply System, DWG No. 47W818-1<br />

RIO.<br />

50. <strong>Browns</strong> <strong>Ferry</strong> System Oper<strong>at</strong>ing Instruction No. 64, Primary Contain<br />

ment <strong>Unit</strong> I, II, or III.<br />

51. <strong>Browns</strong> <strong>Ferry</strong> FSAR Section 7.3, Primary Containment and Reactor<br />

Vessel Isol<strong>at</strong>ion Control System.<br />

52. <strong>Browns</strong> <strong>Ferry</strong> System Oper<strong>at</strong>ing Instruction No. 73, High Pressure<br />

Coolant Injection System <strong>Unit</strong> I, II, or III.<br />

53. <strong>Browns</strong> <strong>Ferry</strong> Startup Test Instruction No. 14, Reactor Core Isol<strong>at</strong>ion<br />

Cooling System.<br />

54. <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant Hot License Training Program, Volume 4,<br />

Reactor Core Isol<strong>at</strong>ion Cooling System.<br />

55. <strong>Browns</strong> <strong>Ferry</strong> FSAR Section 4.7, Reactor Core Isol<strong>at</strong>ion Cooling Sys<br />

tem.<br />

56. <strong>Browns</strong> <strong>Ferry</strong> FSAR Figure 4.7-3, Reactor Core Isol<strong>at</strong>ion Cooling Sys<br />

tem Process Diagram.<br />

57. <strong>Browns</strong> <strong>Ferry</strong> System Oper<strong>at</strong>ing Instruction No. 71, Reactor Core Iso<br />

l<strong>at</strong>ion Cooling <strong>Unit</strong> I, II, or III.<br />

58. B. J. P<strong>at</strong>terson, "Mark I Containment Program: Monticello T-Quencher<br />

Thermal Mixing Test Final Report," NEDO-24542, August 1979.


177<br />

ACKNOWLEDGEMENT<br />

Mr. William A Condon made a significant contribution to this report by<br />

performing the MARCH code calcul<strong>at</strong>ions and preparing the associ<strong>at</strong>ed<br />

plots for the six st<strong>at</strong>ion <strong>blackout</strong> accident sequences discussed in<br />

Chapters 9 and 10. This accomplishment is especially noteworthy because<br />

all MARCH computer runs in support of this project were by necessity<br />

made remotely on the CDC computer facilities <strong>at</strong> Brookhaven N<strong>at</strong>ional<br />

Labor<strong>at</strong>ory. Mr. Condon's work was in partial fulfillment of the re<br />

quirements for the degree of Master of Science with major in Nuclear<br />

Engineering <strong>at</strong> the University of Tennessee, and his lone hours of<br />

dedic<strong>at</strong>ed effort are gr<strong>at</strong>efully acknowledged.


179<br />

APPENDIX A<br />

LISTING OF PLANT RESPONSE CODE BWR-LACP


181<br />

**$CONTINUOUS SYSTEM MODELING PROGRAM III V1M3 TRANSLATOR OUTPUT$*$<br />

*<br />

LABEL BWR-LACP CCJOE<br />

LABEL CONTAINMENT MODEL WITH i-NOOE POOL<br />

* MACRO SUBPROGRAM FOR POOL WATER TEMP CALCULATION<br />

MACRO XNQI,TI,WEI.MWI,LWI-«W(TL,TRILWL,LWR,TWIO,FWI,FSVI,FTEItFOI,FSIJ<br />

* MACRO TC CALCULATE MASS ENERGY BALANCES FOR SP WATER NOOE I<br />

* INPUTS :<br />

* TL»TR«TEMPS OF WATER IN ADJACENT NODES<br />

* LWL,LWR=LEVELS OF ADJACENT NODES<br />

* TWIO-INITIAL WATER TEMP CF NCDE I<br />

* FWl-FRACTION OF TOTAL SP WATER VOL IN NCDE I(CONSTANT)<br />

* FSVI-FRACTION OF SAFETY VALVE FLOW DIRECTED TO NODE I<br />

* FTEI"FRACTION OF TURBINE EXHAUST DIRECTED TO NOOE I<br />

* FDI-*FRACTION OF PUMP OUSCHARGE DIRECTED TG NODE I<br />

* FSI*FRACTlON OF PUMP SUCTION TAKEN FROM NODE I<br />

* MASS BALANCE<br />

*<br />

* WSSPW*PUMP SUCTION FLCWCTOTAL FROM SP)<br />

* WOSPW-PUMP OISCHARGE FLOWCTOTAL TO SP)<br />

* OUTPUTS:<br />

* XNQI»FRACTIN<br />

* XNQI-FRACTGON OF STM DISCH TC NOOE I NOT QUENCHED<br />

* XNQINFRACTION OF STM DISCH TO NOOE I NOT QUENCHED<br />

* TI*AVG. WATER TEMP OF NODE I (DEG-F)<br />

* WE I-RATE OF EVAPORATION FROM NOOE I (LB/SEC)<br />

* MWI»MASS OF WATER IN NODE I (LB)<br />

* LWI-WATER LEVEL OF NODE I (IN)<br />

*<br />

* VWSPOINITIAL TOTAL SP WATER VOLUME (CU. FT. )<br />

MWIO-»FWI*VWSPO*(63.9-.019*TWI0)<br />

CMWI-MNTGRL(0.,XQI*(FSVI«WSSV*FTEI*WSTE)*FINI-F$I*WSSPW-WEI)<br />

FINI*ta£CL+WEQR+FWI*WCSPG+FDI*WOSPW<br />

MWI-*MWIO+CMWI<br />

VWI*MWI/(63.9-.0l9*TI)<br />

LWI*AFGEN(SPLEV,VWI/FWI)<br />

*<br />

* CALC. QUENCH FRACTION FROM ASSUMPTION OF NO QUENCH WHEN NOOE VAPOR<br />

* PRESSURE EQUAL TC TOTAL GAS PRESSURE<br />

PVAPI-NLFGEN(SPFOT.TI)<br />

XQI*LIMIT(0.,l.,(PTSPG-PVAPI-OPQZ)/DPQR)<br />

XNQIM1.-XQI)<br />

* SPFOT(TI)=SAT. PRESS AS F OF Tl<br />

* DPQZ*DIFFERENCE(PSI) OF PTSPG OVER PVAPI REQUIRED FOR ANY<br />

* QUENCHING TO TAKE PLACE<br />

* DPZR»RANGE(PSI) CF PTSPG OVER PVAPI CVER WHICH QUENCHING<br />

* GOES FROM 0.0 TO 100PERCENT<br />

*<br />

* EVAPORATION RATE BASED ON ECUN.13-33, KREITH'S 'HEAT TRANSFER'<br />

* PSSPG=STM. PART PRESSURE ON SP GAS<br />

* ASSPW-SURF AREA OF SP WATER(FT.SQ)<br />

WEI*(WEIN/WEID>*CCMPAR(PVAPI,PSSPG)<br />

WEIN*ASSPW*FWI*HSI*12.3*(PVAPI-PSSPG)*PTSPG*VGSP<br />

WEID-(PNSPG*2.-PVAPI)*TGSPR*(MSSPG+MNSPG)<br />

HSI»5.83E-05*((ABS(TI-TGSP))**.333)<br />

*<br />

* EQUALIZATION FLOWS FROM ACJACENT NODE(S)<br />

* FWE«EQ. FLOW CONSTANT (LB/SEC/(INCH LEVEL DIFF) )<br />

WEQL~FWE*(LWL-LWI)<br />

WEQR-»FWE*(LWR-LWI )<br />

* ENERGY BALANCE<br />

* HEAT TRANSF RATES TO METAL ANO ATMCSPHERE NEGLEGIBLE


183<br />

* XL1=0=ZER0 PCINT FOR DC HEIGhT(FT ): COINCODES WITH BOAF<br />

* XL2=HEIGHT AT JET PUMP SUCTICN(FT)<br />

* XL3=HE1GHT AT TOP OF CORE OUTLET PLENUM(FT)<br />

* XL4-HEIGHT AT BOTTOM OF STEAM SEPARATORS!FT)<br />

CONSTANT ACCR=82., AC0P=234., ART=42.3<br />

CONSTANT CP0=3293., EQXO=.5, FFLASH=.001<br />

CONSTANT LHEDER=23.4, LOP=5.58, LRT=1C0<br />

CONSTANT LB0T=24.85<br />

CONSTANT PC0R=5518., PRATED=1095.<br />

CONSTANT TAULEN=.75, TCFUEL=9.5<br />

CONSTANT VFREE=13000., VCLP=3350., V1DC=192.,WRATED=259.<br />

*<br />

* CARD TO INITIALIZE AT ARBITRARY TIME POINT<br />

CONSTANT HC10=312.05,LDC0=28.63,PO=125.,T0=14430.,RH0G0=.2788<br />

* INITIAL CORE FLOW GUESS DEPENDS ON LCCO AND PRELO<br />

CONSTANT WGUESS=8310.<br />

* REFERENCE PARAMETERS FOR CALCULATION OF NATURAL CIRCULATION<br />

* FLOW RESISTANCE COEFFICIENT<br />

CONSTANT CPREF=3293., PRELR=.32, PRR=1020<br />

LDCR=27.58, XREF=.133, WREF=9111., HREF=522.<br />

* RUN CONTROL PARAMETERS<br />

CCNSTANT HINJIN=58.,RC ICMX=82.9876<br />

*<br />

* FUNCTION SUBPROGRAMS<br />

* CAVOID(XIN,XCUT,WTOTAL,TSAT,RHOF,RHOG)<br />

* DKFUN(T)=P/PO AS A FUNCTION OF TIME AFTER SHUTDOWN<br />

* QREGAVJBCTTGM,TOP,KAPPA,PEKAVG)=(AVG HT. FLUX FROM A TO B)/(CORE AVG)<br />

* RH0TP(RH0F,RHOG,V0ID)=2-PHASE DENSITY<br />

* XLENDC(V0L0CI=00WNC0MER LEVEL AS FUNCTICN OF LIQUID VOLUME<br />

* VOID(QUALITY,TOTAL FLOW,FLOW AREA,TSAT.RHOF,RHOG)=POINT VOID FRACTION<br />

* VOLDC(LCC)=DCWNCCMER HEIGHT ABOVE BOT CF ACT. FUEL<br />

*<br />

* STEAM TABLE CSMP INTERPOLATION FUNCTIONS<br />

* VSATF(PRESS)=SAT FLUIO SPECIFIC VOL(FT**3/LB )<br />

FUNCTICN VSATF=15.,.0167, 50.,.0173, 100.,.0177, 200.,.0184,...<br />

400.,.0193, 600.,.0201, 800.,.0209, 1000.,.0216, 1203 .,.0223,.. .<br />

1400.,.0231<br />

*<br />

* VSATG(PRESS)=SAT GAS SPECIFIC VCL(FT**3/LB)<br />

FUNCTION VSATG=15.,26.3, 50.,8.51, 75.,5.81,100.,4.43,...<br />

150.,3.01,200.,2.29,400.,1.16, 600.,.77,800.,.569,...<br />

1000.,.446,1200.,.362,1400...302<br />

*<br />

* HSATF(PRESSURE)-SAT FLUID ENTHALPY(BTU/LB)<br />

FUNCTION rSATF=15.,181., 50.,250., 100.,298., 2C0.,355.,...<br />

400. ,424., 600.,472., 800.,510., 1000.,543., 1200.,572.,...<br />

1400.,599.<br />

*<br />

* HSATG(PRESSURE) = SAT GAS ENTHALPY IBTU/LB)<br />

FUNCTION HSATG=15.,U51., 50.,1174., 100.,1187., 200.,1198. ,...<br />

400. ,1205., 600.,1204., 800.,1199., 1000.,1193., 1203 .»1185 . , . ..<br />

1400.,1175.<br />

*<br />

* TSATM(PRESSUREJ=SAT MIXTURE TEMPERATURE(DEG-F)<br />

FUNCTION TSATM=15.,213., 50.,281., 100.,328., 2C0.,382.,...<br />

400.,445., 600.,486., 800.,518., ICOO.,545., 1200.,567.....<br />

1400.,587.<br />

*<br />

* VSC(ENTHALPY)=SUBCOOLED FLUIC SPECIFIC VOL(FT**3/LB )<br />

FUNCTICN VSC=21.4,.016, 121.,.0163, 221., .0169, 272.,.0174,...<br />

376.,.0185, 431.,.0193, 488.,.0203, 549.,.0217, 562. , .0221,.. .<br />

575.,.0224<br />

* CALCULATION CF INITIAL SATURATION PROPERTIES<br />

RH0F0=1./(AFGEN(VSATF,P0))<br />

HFO=AFGEN1HSATF,PO)<br />

HGO=AFGEN(HSATG, PO)<br />

TSAT0=FUNGEN(TSATf,2,P0)<br />

* SUBCOOLED WATER DENSITY<br />

RHOSC0=l./(AFGEN(VSC,HCI0))


184<br />

* CALCULATION OF FLOW RESISTANCE COEFFICIENT<br />

* NEEDS: REFERENCE CONDITIONS FOR NATURAL CIRCULATION:CPREF,PRELR,PRR,XREF,<br />

* WREF, HREF, LDCR<br />

* RETURNS: LOSS COEFFICIENT: KLOSSU<br />

* CALCULATION OF REFERENCE DENSITIES AND SATURATION PROPERTIES<br />

HFR*AFGEN <br />

RHOSCR=l./(AFGEN(VSC,HREF))<br />

QT0TR=CPREF*PRELR*947.8<br />

* THIS EXP FOR LSC ASSUMES AVG POWER=CORE AVG IN SC REGION<br />

LSCR*12.*WREF*(HFR-HREF)/QT0TR<br />

LBR«12.-LSCR<br />

RSCAVR=RHOFR/2.+RHOSCR/2.<br />

* FUNCTION SUBPROGRAM CAVOIO RETURNS AVERAGE CORE BOILING REGION<br />

* VOID FRACTION FRCM THE GIVEN INPUTS<br />

CAVR-CAVOID(0..XREF,WREF,TSATR,RHOFR,RHOGR)<br />

RHOBR=RHOTP(RHOFR,RHOGR,CAVR)<br />

RCC0RR=RSCAVR*LSCR/12.+RHCBR*L8R/12.<br />

RHOPR=RHOTP(RHOFR,RHOGR,OPVR)<br />

* FUNCTION VOID RETURNS POINT VOID FRACTION FROM GIVEN INPUTS<br />

OPVR=»VCID(XREF,WREF, ACOP.TSATR, RHOFR, RHOGR)<br />

RGRTR=RHOTP(RHOFR,RHOGR,RTVR)<br />

RTVR*VOIDUREF, WREF, ART, TSATR, RHOFR, RHOGR)<br />

RDP*LCCR*RH0SCR/144.-R0RTR»LRT/144.-...<br />

RH0PR*L0P/144.-R0C0RR*12./144.<br />

KLOSSU=ROP/(WREF*WREF)<br />

*<br />

* INITIAL RELATIVE POWER<br />

*<br />

PREL0=(DKFUN(T0)*.94*EXP(-T0/TCFUEL))<br />

QT0T0=PREL0*CP0*947.8<br />

*<br />

* CALCULATION CF INITIAL TOTAL FLOW BY ITERATIVE SOLUTION, WITH<br />

* STARTING FLOW GUESS INPUT BY USER<br />

WCIQ-IMPHWGUESS, .OOl.WCAL)<br />

XOU»(CTOTO/WCIO+HCIO-HFO)/(HGO-HFO)<br />

XO*LIMIT(0.001,1.00O,X0U)<br />

* THIS EXP FOR LSC ASSUMES AVG POWER=CORE AVG IN SC REGION<br />

LSC0»LIMIT(0.,12.,12.*WCI0*IHF0-HCI0)/QT0T0)<br />

LBO-12.-LSCO<br />

* CALCULATION OF INITIAL DENSITIES<br />

RSCAV0=RHCFO/2.+RHOSCO/2.<br />

waoo~wcio*xo<br />

* VOID AT BOTTOM AND TOP OF BOILING REGION CALC. BY DFVOID<br />

* FUNCTION SUBPROGRAM, THEN AVERAGED TO GIVE CORE AVERAGE VOID<br />

CAVINO=DFVOID(ACOR,WCIO,0.,TSATO,RHOFO,RHOGO)<br />

CAVEXO=DFVOIO(ACOR,WCIO-WBOC,WBOO,TSATO,RHOFO,RHOGO)<br />

CAVO=(CAVINO+CAVEXO)/2.<br />

RHOBO=RHOTP(RHCFO,RHOG0,CAVO)<br />

ROC0RO=RSCAV0*LSC0/l2.'>RHCBO*LBO/12.<br />

ROPO-RHOTP(RHOFO.RHOGO.OPVO)<br />

OPVO=CFVOIO(ACOP,WCIO-WBOO,WBOO,TSATO,RHOFO,RHOGO)<br />

RCRT0=RHQTP(RHOFO,RHOGO,RTVO)<br />

RTVO-DFVOID(ART,WCIO-WBOO,WBOO,TSATO.RHOFO,RHOGO)<br />

* NET GRAVITY PRESS DROP!PSI) AVAILABLE FOR UNRECOV. DROP ACROSS CORE<br />

LDCX=LIMIT(0.,LOCR,LDCO)<br />

UNREC0=LDCX*RH0SC0/144. + (12.+LRT+L0P-LDCX)*RH0G0/144.-...<br />

RORT0*LRT/144.-R0P0-»LOP/l44.-ROCORC*12./l44.<br />

DPO=LIMIT(.0001,1000..UNRECO)<br />

WCAL-»SQRT(DP0*RHOB0/( KLOSSU*RHOBR) )<br />

* ENO ITERATIVE LOOP<br />

* OOWNCOMER AND LOWER PLENUM INITIALIZATION<br />

* VOLUME CF WATER IN DOWNCOMER NODE GIVEN BY FUNCTION


185<br />

* VOLDCl ) AS A FUNCTICN OF WATER LEVEL<br />

MOCO» VOLDC(LDCO)*RHOSCO<br />

MHOCO=MDCO*HCIO<br />

MLPO*VOLP*RHCSCO<br />

MHLPO=MLPO*HCIO<br />

*<br />

G=4.75*ART*RH0G0<br />

MTOTO*(LSCO*RSCAVO+LBO*RHOBO)*ACOR-t-LCP*ACCP*ROPO+LRT*ART*RORTO*G<br />

*<br />

* PRESSURE CALCULATION INITIALIZATION<br />

RHOSVR=l./FUNGEN(VSATG,2,PRATED)<br />

UCSRV»WRATED/SQRT(PRATED*RHOSVR)<br />

MSTO-IVFREE-VOLDCUDCO) )*RHOGO<br />

UMST0»MST0*(HG0-P0*144./(778.*RH0G0))<br />

*<br />

* INITIALIZATION FOR SUPPRESSION PCOL CALCULATION<br />

*<br />

*<br />

* CONSTANTS FCR CONTAINMENT MODEL<br />

*<br />

* AOMET=HEAT TRANS AREA BET DW MET AND CW ATMOS(FT**2J<br />

* APMET=HEAT TRANSF AREA BET SP MET AND SP ATMOS<br />

* ASSPW=AREA OF POOL WATER SURFACE(SQ.FT.)<br />

* BDWSPO*CU.FT/SEC/PSI FLOW WHEN DOWNCCMERS CLEARED<br />

* BSPDWOCU.FT/SEC/PSI OF FLOW WHEN VALVE OPEN<br />

* CDMET=MASS*SPEC HEAT OF OW METAL(BTU/DEG-F)<br />

* CPAIR=MASS*SPEC HEAT OF AIR IN SP CHAMBER ROOM<br />

* CPMET=MASS*SPEC HEAT OF SP METAL IN CONT WITH GAS<br />

* DM-AMOUNT OF STM. QUENCHED!UNIFORMLY ARCUNO POOL) IF THERE<br />

* IS ELAPSED TIME BETWEEN NOMINAL START AND INITIALIZATION OF THE RUN<br />

* DPQR=RANGE(PSI) OVER WHICH QUENCH FRACTION GOES FROM 1 TO 0.<br />

* WITH INCREASING VAPOR PRESSURE<br />

* DPQZ=MARGIN(PSI) ABOVE SATURATION FOR COMPLETE QUENCHING<br />

* FDI,FSI=FRACTION OF POOL COOLING DISCHARGE AND SUCTION TO POOL NODE I<br />

* FWE=FLOW BETWEEN S.P. NODES(LB/SEC) PER INCH OF WATER LEVEL OIFFEKENCE<br />

* FW INFRACT ION OF POOL WATER CONTAINED IN POOL NODE I<br />

* FSVI*FRACTIQN OF TOTAL SRV FLOW DISCHARGED TO POOL NODE I<br />

* FTEI=FRACTION OF TURBINE EXHAUST DISCHARGED TO POOL NODE I<br />

* FLSPG, FLOWG=FRACTION OF ATM. LEAKED TO RX-BLDG. PER SECOND<br />

* GCH=GAS CONSTANT OF H2<br />

* GCM*GAS CONSTANT OF MIMISC.)<br />

* GCN~GAS CONSTANT OF N2<br />

* GCS-GAS CONSTANT OF H20 VAP(PSI*FT**3/LB*DEG-R)<br />

* HSRREF=OELTA TO REREFERENCE STM ENTHALPY FROM ASME STEAM TABLES<br />

* TO PERFECT GAS EXP. THAT HAS H=0.0 AT 0 DEG-R<br />

* HSTE=ENTH OF TURBINE EXHAUSTIBTU/LB)<br />

* HJMDWO- INITIAL DW GAS HUMIDITY (PERCENT)<br />

* HUMSPO-INITIAL SP GAS HUMIDITY (PERCENT)<br />

* KMIX-EMPIRICLE CONSTANT FOR NAT. CIRC MIXING FLOW BET. POOL NODES<br />

* LBASE=»NCMINAL STARTING LEVEL OF POOLdN. FROM INST. 0.)<br />

* MHSPGO,MHOWGO=INITIAL MASSES OF H(LBS)<br />

* MMSPGO,MMOWG0=INITIAL MASSES OF M (LBS)<br />

* POCVP*PRESS. DIFF NECESSARY TO CLEAR THE VENT<br />

* PIPES FOR FLOW FRCM DW TO SP<br />

* PTDWGO- INITIAL TOTAL PRESS OF DW GAS (PSIA)<br />

* PTSPGO-INITIAL TOTAL PRESS OF SP GAS (PSIA)<br />

* QRVHLO=REACTCR(+PIPING) HEAT LOSSES (MW) FOR TEMP DIFF=OTRVHL(DEG-F)<br />

* TAUFDW=AVERAGE RESIDENCE TIME OF FOG IN DW(SEC)<br />

* TAUFSP=AVERAGE RES. TIME OF FOG IN SP<br />

* TAUVRV=TIME CONSTANT FOR SP VAC RELIEF VALVE TO LIFT(SEC)<br />

* TBASE-NCMINAL STARTING TEMP CF POOL(CEG-F)<br />

* TBII-PROVISION FOR BIASING STARTING TEMP CF POOL NODE I<br />

* TD=OISCH. TEMP(F) OF POOL COOLING FLOW<br />

* TDMETO-INITIAL DRYWELL METAL TEMP IF)<br />

* TGDWO*INITIAL DW GAS TEMPtDEG-F)<br />

* TGSPO*INITIAL SP GAS TEMP (DEG-F)<br />

* TPAIROMNITIAL SP CHAMBER ROOM TEMP


186<br />

* TPMETO=INITIAL TEMP : SP METAL IN CONTACT WITH SP GAS<br />

* VGOW=TOTAL FREE VOLUME OF DW (FT**3)<br />

* VTSP=TOTAL FREE VOLUME OF SP (FT**3)<br />

* WOLEAK=LEAK RATE(LB/SEC) OF SAT. WATER FROM RV TO DRYWELL<br />

* WDSPW=DISCHARGE FLOW OF POOL COOLING(LB/SEC)<br />

* WSSPW=SUCTION FLOW OF POOL COOL ING!LB/SEC)<br />

*<br />

*<br />

* GEOMETRY AND PHYSICAL CHARACTERISTICS<br />

CONSTANT ACMET=1.65E04,APMET=1.7E04,ASSPW=10860.<br />

CONSTANT BDWSP0=2500.,BSPDWO=2000.<br />

CONSTANT CDMET=8.33E04,CPAIR=3200.,CPMET=5.82E04<br />

CONSTANT DPQR=2. ,DPQZ=2.<br />

CONSTANT GCH=5.361,GCM=.2436,GCN=.3829,GCS=.5955<br />

CONSTANT HSTE=915.,HSRREF=-854.5,P0CVP=1.75<br />

CONSTANT TAUVRV=3.,TAUFDW=30.,TAUFSP=15.<br />

CONSTANT VGDW=159000.,VTSP=267600.<br />

*<br />

* POOL NQDALIZATICN<br />

CONSTANT FD1=1.,FS1=1.,FWI =1.,FSV1=1.,FTE1=1.,FWE=>5000.,KMIX=950.<br />

*<br />

* INITIALIZATION<br />

CONSTANT DM=0. ,HUMDW0=18. 4,HUMSP0=79.4 ,LBASE=1C23<br />

CONSTANT MHSPGO=0.,MHDWGO=0.,MMSPGO=0.,MHDWG0=0.<br />

CONSTANT PTDWG0=23.15,PTSPG0=23.65,TBASE=169.1,TBI1=0.<br />

CONSTANT TGDV«0=268. ,TGSP0=161.,TDMET0=212.,TPMET0=145.1,TPAIRO=155.<br />

»<br />

* RUN CONTROL<br />

CONSTANT FLDWG=0.,FLSPG=0.,TD=90.,GRVHL0=1.,DTRVHL=404.<br />

CONSTANT W0LEAK=.68,WSSPW=C.,W0SPW=0.<br />

HD=TC-32.<br />

* INITIALIZATION CALC. FOR DW AND SP MASS AND ENERGY BALANCES<br />

* ASSUME ZERO INITIAL HYDROGEN AND MISC. GAS<br />

*<br />

* FUNCTION TABLES<br />

* FUNCTION SPLEV : SP LEVEL!INCHES FROM INSTRUMENT ZERO) AS A FUNCTION A<br />

* FUNCTION CF VOLUME(CU.FT)<br />

FUNCTION SPLEV=0.,-182.,20222.,-134.,74646.,-62.,...<br />

117344.,-14.,130129.,0.,139300.,10<br />

182563.,58.,242176.,130.,267611.,190.<br />

*<br />

* FUNCTION STFOSV: SATURATION TEMP AS A FUNCTION OF SPECIFIC<br />

* VOLUME<br />

FUNCTION STF0SV=2.83,363.5,4.65 ,324.1,7.65,288.2,12.2,257.6, ...<br />

20.1,228.,31.2,204.,44.7,185.6,76.4,160.5,158.9,129.6,. ..<br />

333.6,101.7,641.5,79.6,1235.,59.3<br />

* FUNCTION SPFOT : SATURATION PRESSURE AS A FUNCTION OF TEMPERATURE<br />

FUNCTICN SPF0T=59.3,.25,79.6,.5,1C1.7,1.0,132.9,2.4,...<br />

160.5,4.8,185.6,8.5,203.9,12.5, ...<br />

228.,20.,250.34,30.,288.2,56.,324.1,95.,363.5,160.,...<br />

381.8,200.,417.3,300.,444.6,400.,467.,500.,486.,600.,...<br />

503.,700.,525.,850.,544.6,1000.,556.,1100.,567.,1200.<br />

* PRELIMINARY CALCULATIONS<br />

SPDWO=NLFGEN(SPFOT,TGDWO)<br />

SPSPO=NLFGEN(SPFOT,TGSPO)<br />

PSDWGO=(HUMDWO/100.)*SPDWO<br />

PSSPG0=(HUMSP0/100.)*SPSPO<br />

PNSPGO=PTSPGO-PSSPGO<br />

PNOWGO=PTDWGO-PSDWGO<br />

MNSPG0=PNSPG0*!VTSP-VWSP0)/(GCN*(TGSP0+460.) )<br />

MNDWG0=PNOWG0*(VG0W)/(GCN*(TG0W0+460.))


*<br />

* VWSPO=INITIAL TOTAL WATER VOL IN SP<br />

*<br />

187<br />

MSSPG0=PSSPG0*(VTSP-VWSPO)/(GCS*(TGSPO+46O.))<br />

MSDWG0=PSDWG0*VGDW/(GCS*(TGDW0+460.))<br />

UMSPG0=(TGSPO+460.)*(MNSPGO*(.2475-.1851*GCN)+...<br />

MSSPG0*(.45-4.89/(TGSP0+460.)-.1851*GCS) )<br />

UMDWGO=(TGOWO*460.)*(MNDWGO*(.2475-.1851*GCN)+...<br />

MSDWGO*(.45-4.89/(TGDWO+460.J-.1851*GCS) )<br />

*<br />

* DEPTH LBASE SPECIFIED: INCHES FROM INST ZER0(4 IN BELOH CENTER)<br />

* TBASE IS NOMINAL STARTING TEfP CF PCOL<br />

* TBKI) PROVIDES FOR BIASING INITIAL TEMPS IN MULTI-NODE MODEL<br />

VII=2.462*AII<br />

AII=(LBASE-4.)*SQRT(34580.-LBASE*LBASE+8.*LBASE)*...<br />

34596.*ARSIN( (LBASE-4. )/186. ) + 54343.<br />

MW1II=FW1*VII*(63.9-.019*(TBASE*TBU))<br />

MII=MW1II<br />

DTBASE=(1190.-(TBASE-32.))*0M/(MII+0M)<br />

TIC1=TBASE+0TBASE+TBI1<br />

VWSP0=(MWlII+FWl*0M)/(63.9-.019*TICl)<br />

VGSPO=VTSP-VWSPO<br />

DYNAMIC<br />

* DYNAMIC PORTION OF REACTCR VESSEL CALCULATION<br />

#<br />

* RUN CONTROLS FOR INJECTION CONTROL<br />

LDCVZ=L0C*12.+216.<br />

LDDEL=REALPL(500.,2.OO.LDCVZ)<br />

RCICC=0.0<br />

HPCID=0.0<br />

WINJ=RCICMX*(RCICD*8.33*HPCID)*STEP(30.)<br />

* RUN CONTROLS FOR VESSEL PRESSURE CONTROL<br />

P0PEN=1120.<br />

PSHUT*1080.<br />

* CALCULATION OF DYNAMIC SATURATION PROPERTIES<br />

RH0F=1./(AFGEN(VSATF.P))<br />

RhOG=l./(FUNGEN(VSATG,2,P)»<br />

HF=AFGEN(HSATF,P)<br />

HG=AFGEN(HSATG,P)<br />

TSAT=FUNGEN(TSATM,2,P)<br />

* INTERMEDIATE CALCULATIONS: AVERAGE HEAT FLUXES<br />

* 'DKFUN' RETURNS DECAY HEAT AS A FUNCTION OF TIME SINCE SCRAM<br />

* 'QREGAV RETURNS AVERAGE NORMALIZED POWER, GIVEN LOCATION OF TOP<br />

* AND BOTTCM OF REGION<br />

T=TO+TIME<br />

TMIN=T/60.<br />

PREL=(DKFUN(T)+.94*EXP(-T/TCFUEL) )<br />

QT0T=PREL*CP0*947.8<br />

QFCCR=QTOT/(12.*PCOR1<br />

AVMSC=QREGAV(0.,LSCD)<br />

AVMB=QREGAV(LSCD,LSCD+LBD)<br />

QFSC=AVMSC*QFCOR<br />

QFB=AVMB*QFCOR<br />

LSCD=REALPL!LSCO,TAULEN,LSC)<br />

L8D=REALPL(LB0,TAULEN,LB)<br />

* DOWNCOMER ANNULUS CALCULATION<br />

* NEEDS: CENSITIES: RHCOCRHOLP<br />

* FLOWS INTO DCWNCOMER: WINJ, WRECIR, WINJAS<br />

* INJECTION ENTHALPY: HINJIN<br />

* FLOWS OUT OF DOWNCOMER: WCI, WFLDC, WFLLP<br />

* REACTCR VESSEL PRESSURE: P


188<br />

* RETURNS: DOWNCOMER HEIGHT!ABOVE BOTTCM CF ACTIVE FUEL) : LDC<br />

* ENTHALPY INTO LOWER PLENUM: HDC<br />

* INTERMEDIATE CALCULATIONS: MASS RATE OF ASPIRATION FROM STEAM SPACE<br />

* DUE TO INJECTION FLOW; FLASHING RATE FRCM DC MASS; RECIRC FLOW RATE<br />

EQXX=EQXO*(LHEDER-LDC)/LHEDER<br />

EQX=LIMIT(0.,1.,ECXX)<br />

HINJFI*HINJIN+(HF-HINJIN)*EQX<br />

GP=7.23*WINJ<br />

WINTCT=INTGRL(0.,WINJ)<br />

GT=(WINT0T*7.481)/62.11<br />

WINJAS=(HF-HINJIN)*EQX*WINJ/(HG-HF)<br />

WFLDCX=MOC*FFLASH*(HDC-HF)<br />

WFLDC=LIMIT(0.,9999..WFLDCX)<br />

*<br />

* MASS AND ENERGY BALANCES(81 IS A LOGIC SIGNAL TO STOP THE<br />

* INTEGRATION WHEN LDC.LT.O(BELOW BCTTCM OF ACTIVE FUEL)<br />

CMDC=INTGRL(0.,DMOC)<br />

MOC=MCCO*CMOC<br />

DMDC*Bl*(WRECIR*WINJ+WINJAS-RHOCC*(WCI*WFLLP)/RHOLP-WFLDC)+WEXPC<br />

CMHDC=INTGRL(0.,DMHOC)<br />

MHDC=MHDCO*CMHDC<br />

DMHOC*Bl*(HF *WRECIR*W INJ*HINJIN+HG*WINJAS-...<br />

HDC*(WCI+WFLLP)*RHODC/RHOLP-WFLCC*FG)<br />

HDC=MHDC/MDC<br />

RHOOC=l./AFGEN(VSC,HDC)<br />

* DC LEVEL IS CALCULATED BY FUNCTION SUBPROGRAM XLENOCIVOLUME)<br />

VOC-»MCC/RK)OC<br />

LDC=XLENDC(VOC)<br />

LDL=LIMIT!0.,LDCR,LDC)<br />

* LOWER PLENUM CALCULATION<br />

* NEEDS: SAME AS DCWNCCMER<br />

* RETURNS: ENTHALPY AT CORE INLET(HLP)<br />

* INTERMEDIATE CALCULATIONS: LOWER PLENUM FLASHING RATE, LP WATER VOL<br />

* (VOLPW—USED FOR LOGIC CONTROL ONLY SINCE THE LOWER PLENUM IS<br />

* MODELED AS A CONSTANT VOLUME UNLESS COWNCOMER IS EMPTY) :<br />

HLP=MHLP/MLP<br />

VOLPW=MLP/RHOLP<br />

RHOLP=l./AFGEN(VSC,HLP)<br />

XWFLLP*(HLP-HF)*MLP*FFLASH<br />

WFLLP=LIMIT(0.,9999.,XWFLLP)<br />

* LOGIC CCNTROL<br />

*<br />

*<br />

X1B1=LDC-.001<br />

X2Bl"«V0LPW-l.01*VCLP<br />

B1N=N0R(X1B1.X281)<br />

B1=N0T(B1N><br />

* MASS AND ENERGY BALANCES<br />

*<br />

DMLP-*(WCI +WFLLP)*{RHOCC/RhOLP)*(Bl)-WCI-WFLLP*...<br />

B1N*(WINJ+WINJAS><br />

CMLP*INTGRL(0., OMLP)<br />

MLP=MLPO+CMLP<br />

DMHLP=H0C*(WCI+WFLLP)*RH0DC*B1/RH0LP+...<br />

BlN*(WINJ*HINJIN*HG*WINJAS)-WCI*HLP-WFLLP*HG<br />

CMHLP=INTGRL(0.,DMHLP)<br />

MHLP=MHLPO+CMHLP<br />

* CORE INLET FLOW CALC.(FORCE BALANCE)<br />

* NEEDS: DENSITIES: RHODC,RHOLP,RSCAV,RHCB,ROP, RORT<br />

* REACTOR VESSEL PRESSURE : P<br />

* FLOW OUT OF BOILING REGION: W80<br />

* REGION LENGTHS: LDC,LSC,LB<br />

* RETURNS: FLOW INTO CCRE: WCI<br />

*<br />

CMTOT«INTGRL(0. ,(WCI-WRECIR-WTOST+WFLLP))<br />

MTOT-MTOTO+CMTOT<br />

WB0=(QFB*PCOR*LBD)/(HG-HF)


*<br />

WPOO=MPOO*DHF/(HG-HF)<br />

HFD=REALPL(HF0,2.0,HF)<br />

DHF=(hF-HFD)/2.<br />

VST=VFREE-V0C<br />

DVST=CERIV(O..VST)<br />

VSVST=VST/MST<br />

* VST=T0TAL VAPOUR SPACE VOLUME<br />

* VSVST=SPECIFIC VOLUME OF STEAM<br />

*<br />

*<br />

190<br />

* TOTAL ENERGY BALANCE<br />

CUMT 0= IN T GRL 10.. DUMTO )<br />

UMT0=UMST0+CUMTO<br />

DUMTO=WTOST*HG+(WFLDC+WEVAPJ*HG-...<br />

WEXPC*HF-WC0N0*HG-WINJAS*HST-WSTC*HST-0VST*P*144./778.<br />

HST=UMT0/MST+PSTG*VSVST*144./778.<br />

* STEAM PRESSURE CALCULATED BY FUNCTICN SUBPROGRAM PFVH--STEAM PRESSURE<br />

* AS A FUNCTION OF SPECIFIC VOLUME AND ENTHALPY<br />

* PFVH REQUIRES AN INITIAL GUESS OF PRESSURE, PSTG<br />

PST=PFVH(HST,VSVST,PSTG)<br />

PSTG=REALPL(P0,2.0,PST)<br />

P=PST<br />

*<br />

* SAFETY RELIEF VALVE MODEL—TWO VALVES MCDELED~WSSV=TOTAL SRV FLOW<br />

L0GREL=L0GV1+L0GV2<br />

LOGVl=REALPLI0.,.62,L0GPVl)<br />

L0GV2=REALPL(0.,.62,L0GPV2)<br />

LCGPV1=RST(X1V1,X2V1,0.)<br />

LCGPV2=RST(X1V2,X2V2,0.)<br />

XIV1=C0MPAR(PSHUT, P)<br />

X1V2=C0MPAR(P0PEN-25.,P)<br />

X2V1-CCMPAR1P.P0PEN)<br />

X2V2=C0MPAR(P,P0PEN*25.)<br />

WSSV=UCSRV*SQRT(PSTG/VSVST)*LOGREL<br />

* WSTE=STEAM TURB EXHAUST FLOW(RCIC)<br />

* ENTHALPY IS ASSUMED=915. BUU/LB<br />

WSTE=(RCICD*(.00613*PST+1.1)+HPCI0*(.0387*PST*7.81))*STEP130.)<br />

* WSTC IS TOTAL STEAM FLOW RATE FROM REACTOR VESSEL TO CONTAINMENT<br />

WSTC=WSTE*WSSV<br />

* CYNAMIC PORTION OF CONTAINMENT CALCULATION<br />

*<br />

* CALLS TO SP WATER MACRO—ONLY ONE NECESSARY FUR THE SINGLE NOOE PCOL MODEL<br />

XNQ1 ,TP1 ,WE1 ,MWl ,LW1 =W(TP1,...<br />

TP1 ,LW1,LW1 ,TIC1 ,FW1 ,FSV1 ,FTE1 ,FD1 ,FS1 I<br />

VWSP=MWl/(63.9-.019*TPl)<br />

MWSP=MW1<br />

GWSP=7.481*VWSP<br />

TWSPAV=(63.9-MWSP/VWSP)/.019<br />

LWSPAV=AFGEMSPLEV,VWSP)<br />

* INTERFACE THE SP WATER TO THE SP GAS<br />

*<br />

*<br />

XNQDW=XNQ1<br />

WSSVNQ=WSSV*FSV1*XNQ1<br />

WSTENC=WSTE*FTE1*XNQ1<br />

WTESPW=WE1<br />

* INTERFACE VARIABLES : RV TO SUPPRESSION POOL<br />

* WSSV=STM. FLOW FROM RV THRU RELIEF VALVES(LB/SEC)<br />

* WSTE=STM FLOW FROM RV THRU TURBINES!RCIC+HPCI)<br />

* WHSV=HYDROGEN FLOW FROM RV ThRU RELIEF VALVES!LB/SEC)<br />

* HHM=HYDRCGEN ENTHALPY AT MIXED RV TEMP(BTU/LB) (REF TO 0. DEG R)<br />

* HSTE=ENTHALPY OF TURBINE EXHAUSE(ASME)<br />

* TM=MIXTURE TEMP OF RV STEAM SPACE


*<br />

*<br />

*<br />

191<br />

INTERFACE VARIABLES : RV TO DRYWELL<br />

WSDWR=STEAM FLOW, RELEASE TO DRYWELL(LB/SEC)<br />

HSDWR=ENTHALPY OF WSDWR(ASME)<br />

WHDWR-HYDROGEN FLOW, RELEASE TO DRYWELL!LB/SEC)<br />

HHDWR-ENTHALPY OF WHOWRIREF TO 0.0 DEG R)<br />

WMDWR=MISC. FLOW RELEASEO TO DRYWELL<br />

HMDHR-*ENTHALPY OF WMDWRIO.O DEG R)<br />

INTERFACE VARIABLES : SP WATER TO SP GAS<br />

WSSVNQ-TCTAL NCN-QUENCHED RELIEF VALVE FLOW FROM RV TO SP VIA RV'S<br />

WSTENQ-TOTAL NON-QUENCHED TURBINE EXHAUST FLOW<br />

WCSPG=TCTAL CONSECSATE FLOW, SPG TO SPW<br />

WTESPW-TOTAL EVAPORATION RATE, SPW TC SPG<br />

HSTSPW-ENTHALPY OF STEAM(REF 0. AT 0. OEG) AT MASS-WEIGHTED SP WATER<br />

TEMP, TWSP<br />

HCSPG*ENTHALPY OF CONDENSED SP STEAM(ASME)<br />

MASS BALANCES FOR SP GAS AND DW GAS<br />

INPUT FROM OTHER CALCULATIONS:<br />

VWSP*SP TITAL WATER VOL (FT**3> (VARIABLE)<br />

WSSNQ* TCTAL NON-QUENCHED STEAM FLOW (LE/SEC)<br />

WHSV- H FLOW FROM THE RV (THROUGH RELIEFS)<br />

WSOWR* FLOW RATE OF STEAM RELEASED DIRECT TO DRYWELL<br />

WHDWR- FLOW RATE CF HYDROGEN RELEASED TO DRYWELL<br />

WMDWR* FLOW RATE UF MISC. RELEASED OIRECT TO DRYWELL<br />

DEFINITIONS<br />

MS SPG<br />

MHSPG<br />

MASS STM IN SPG<br />

MASS H IN SPG<br />

MNSPG= MASS N IN SPG<br />

MMSPG'MASS M IN SPG<br />

FLOWS » LB/SEC UNLESS OTHERWISE SPECIFIED<br />

WSSVNG* TOTAL NON-QUENCHED STM FROM SV'S ANT TURB, EXHAUST<br />

WHSV- TCTAL HYDRCGEN FLOW FRCM RELIEF VALVES<br />

DWSP* DESIGNATES FLOW FROM DW TO SP<br />

SPOW- DESIGNATES FLOW FROM SP TO DW<br />

SPL» SP GAS LEAKAGE<br />

B* BULK FLOW RATE (FT**3/SEC)<br />

WCSPG- TOTAL CONDENSATE FLOW FROM SP GAS<br />

WCOWG* TOTAL CONDENSATE FLOW FROM DW GAS<br />

SP GAS MASS BALANCE:<br />

MSSPG«INTGRL(MSSPGO,WSSVNQ+WSDWSP*WSTENQ+WTESPW-WSSPDW-WSSPL-WCSPG)<br />

MHSPG=INTGRL (MHSPGO.WHSV+WHOWSP-WHSPDW-WHSPL)<br />

MNSPG- INTGRL(MNSPGO.WNDWSP-WNSPL-WNSPDW)<br />

MMSPG=INTGRL (MMSPGO.WMDWSP-WMSPL-WMSPDW)<br />

BSPL=VGSP*FLSPG<br />

WSSPL *BSP L*(MSS PG/VGSP)<br />

WHSPL'BSPL*(MHSPG/VGSP)<br />

WNSPL=BSPL*(MNSPG/VGSP)<br />

WMSPL=BSPL*(MMSPG/VGSP)<br />

BSPL*BULK LEAKAGE FRCM SP GAS<br />

FLSPG-FRACTION OF TOTAL SP GAS VOLUMES LEAKED PER SECONO<br />

VGSP»VOLUME OF SP GAS, VWSP-SP WATER VOLUME<br />

VGSP-VTSP-VHSP<br />

NOTE: 0.5 PSI IS NECESSARY TO OPEN VAC RELIEF VALVE<br />

BSPCWX=LIMIT(0.,1.E06,BSPDW0*(PTSPG-PTDWG-.5)I<br />

8SPDW-


* VAC RELIEF VALVE IS OPEN<br />

192<br />

BOWSPX=LIMIT (0.,l.E06,BDWSPO*(PTOWG-PTSPG-PDCVP))<br />

BOWSP-«REALPL(0.,TAUVRV,BOwSPX)<br />

WSDHSP»BDWSP*(MSDWG/VGDH)*XNQDW<br />

WHDWSP=BDWSP*(MHOWG/VGDH)<br />

WNDWSP-BOWSP*(MNDWG/VGDH)<br />

WMDWSP=BDWSP*(MMDWG/VGDW)<br />

* 80WSP0»(FT**3/SEC)/PSI WHEN DW PRESS IS GREAT ENOUGH<br />

* TO CLEAR THE VENT PIPE DOWNCOMERS<br />

* POCVP«PRESS DIFF. NECESSARY TO CLEAR THE VENT PIPES<br />

*<br />

WCSPG«WWCSPG+WVCSPG<br />

WVCSPG»(MSSPG/TAUFSP)*(1.-100./HUMSP)*C0MPAR(HUMSP,100.)<br />

* WWCSPG'RATE OF CQND. ON SPG WALL<br />

* WVCSPG-RATE OF COND. FROM SPG VOLUME<br />

*<br />

* DRYWELL MASS BALANCE:<br />

MSOWGMNTGRL(MSDWGO,WSDWR+WSSPDW-WSDWSP-WSDWL-WCDWG)<br />

MHOWG-INTGRL(MHOWGO.WHOWR-tWHSPCW-WHDWL-WHDWSP)<br />

MNDWG-*INTGRL(MNOWGO.WNSPOW-WNOWSP-WNDWL><br />

MMDWG*INTGRL(MMDWGO,WMDWR*WMSPOW-WMDWSP-WMDWL)<br />

*<br />

*<br />

WCDWG*WWCDWG*HVCDWG<br />

WVCDWG»(MSDWG/TAUFDW)*(1.-100./HUMOW)*COMPAR(HUMOW,100.)<br />

* HYDROGEN AND MISC RELEASES SET TO ZERO<br />

* FFRACT=FRACTION OF HOT LIQUID LEAK THAT FLASHES TO STEAM<br />

FFRACT-{AFGEN(HSATF.PST)-AFGEN(HSATF,PTOWG))/...<br />

(AFGEN(HSATG,PTDWGI-AFGEN(HSATF.PTDWG))<br />

WSDWR»WDLEAK*FFRACT<br />

HSDWR*AFGEN(HSATG,PTDWG)<br />

WHDWR=0.<br />

WMDWR«0.<br />

HHOWR-0.<br />

HMDWR-O.<br />

WWCDW&*RATE OF COND. ON DWG WALL<br />

WVCOWG-fRATE OF VOLUME COND. IN DRYWELL<br />

ENERGY BALANCES FOR CW AND SP GAS<br />

INPUT FRCM OTHER CALCULATIONS:<br />

HMDWR=ENTHALPY OF MISC. RELEASED DIRECT TO DRYWELL<br />

HHOWR'ENTHALPY OF HYOROGEN RELEASED OIRECT TO DRYWELL<br />

HHRV=ENTHALPY OF HYDROGEN IN REACTOR VESSEL<br />

HSRV*ENTHALPY OF STEAM IN REACTOR VESSEL<br />

HSDWR-ENTHALPY OF STEAM RELEASED DIRECT TO DRYWELL<br />

HSTE=ENTHALPY OF STEAM FROM TURBINE EXHAUST<br />

NOTE THAT THE ABOVE 3 ARE REF. TO ZERO AT 32.F WATER<br />

(ASME STM TABLES), BUT ARE RE-REF TO ZERO<br />

AT ZERO DEG-R FOR CONTAINMENT CALC.<br />

QVSPG,QVCWG*VOLUME HEAT SOURCE (FROM F.P.'S)<br />

QRVHL-HEAT LOSS (THROUGH INSULATION) FRCM RV TO SP GAS<br />

QLSPG=HEAT LOSS FROM SP GAS TO SP LINER<br />

QLDWG-HEAT LOSS FROM OW GAS TO DW LINER<br />

DEFINITIONS:<br />

TGSP-TEMF OF HOMOGENIZED SP GAS (DEF-F)<br />

TGDW«TEMP OF HOMOGENIZED DW GAS (DEG-F)<br />

UMSPG"TOTAL INTERNAL ENERGY OF SP GAS (BTU)<br />

UMDWG=TCTAL INTERNAL ENERGY OF DH GAS (BTU)<br />

MASS FLOWS DEFINED IN MASS BALANCE SECTION<br />

SP GAS ENERGY BALANCE:<br />

CUMSPG=INTGRL(0.0,DUMSPG)<br />

UMSPG»UMSPGO->CUMSPG


193<br />

DUMSPG-EPSSP-t-EPHSP+EPNSP-e-EPMSP+QVSPG-QLSPG-MWORK-t-QSSPG<br />

EPSSP*WSSVNQ*(HSSVNQ)*WSTENQ*(HSTE+HSRREF)+...<br />

WSOWSP*! HSTGDW )-( WSSPDW-t-WSSPL )*HSTGSP-. . .<br />

WCSPG*(HFGSP*HSRREF)+WTESPW*HSTSPW<br />

MWORK«DVOTPG*PTSPG*.1851<br />

DVDTPG-»(VGSP-VGSP0)/5.<br />

VGSPD«REALPL(VGSP0,5.,VGSP)<br />

* WSSVNQ-TQTAL SRV FLOH THAT EXITS SURFACE OF POOL<br />

* WSTENQ-TOTAL NON-QUENCHED STM FROM TURBINE EXHAUST<br />

* HSRREF»OELTA-H TO REREF. STEAM ENTHALPY<br />

* HFGOW»SAT FLUID ENTH AT DW TEMP(ASME)<br />

* HFGSP»SAT FLUID ENTH AT SP TEMPIASME)<br />

* HSSVNQ*ENTHALPY OF NON-QUENCHED STEAM ENTERING SP GASJREF TO 0.<br />

* AT 0. CEG-R)<br />

HSSVNC-HST+HSRREF<br />

HSTGSP».45*TGSPR-4.89<br />

HSTSPW*.45*(TWSPAV->460.)-4.89<br />

HSTGDW-.45* TGDWR-4.89<br />

*<br />

*<br />

*<br />

*<br />

*<br />

HFGSP-TGSP-32.<br />

HFGDW-TGDW-32.<br />

EPHSP«WHDWSP*HHTGCW+WHSV*HHRV-(HHSPOW->WHSPL)*HHTGSP<br />

HHTGSP-«3.466*TGSPR-40.<br />

HHTGDH«3.466*TGDWR-40.<br />

EPNSP«HNTGDW*WNDWSP-(WNSPCW+WNSPL)*HNTGSP<br />

HNTGSP-.2475*TGSPR<br />

HNTG0W«.2475*TGDWR<br />

EPMSP«HMTGOW*WMDWSP-(WMSPOW-i-WMSPL)*HMTGSP<br />

HMTGSP«.21*TGSPR-20.8<br />

HMTGDW».21*TGCWR-20.8<br />

* DRYWELL ENERGY BALANCE<br />

CUMDWG»INTGRL(0.0,OUMDWG)<br />

UMDWG«CUMDWG*UMOWGO<br />

DUMDWG-EPSDW+EPHDW+EPNDW+EPMOW+QVOWG*...<br />

QRVHL-QLOWG<br />

*<br />

*<br />

QSSPG»(TWSPAV-TGSP)*ASSPW*5.3E-05*((ABS(TWSPAV-TGSP))**.33><br />

QLSPG-QPMWET+QPHORY<br />

QVDWG=0.<br />

QVSPG»0.<br />

QRVHL«QRVHL0*948.*(TSAT-TGDW)/DTRVHL<br />

QLDWG»CDM<br />

EPSDW»(HSOWR*HSRREF)*WSDWR+HSTGSP*WSSPOW-HSTGOW*(WSDWSP-fWSOWL>-<br />

HFGOW*WCOWG<br />

EPHDW=HHDWR*WHDWR+HHTGSP*WHSPDW-HHTGDW*!WHDWSP*WHOWL)<br />

EPNDW«HNTGSP*WNSP0W-HNTGDW*(WNCWSP->WNOWL)<br />

EPMDW*HMDWR*W.-'DWR-t-HMTGSP*WMSPOW-HMTGCW*(WMDWSP+WMDWL)<br />

*<br />

* SOLUTION FOR DW AND SP GAS TEMPERATURES<br />

* ITERATION IS NOT NECESSARY SINCE THE S,N,H,ANO M<br />

* ENTHALPIES ARE ASSUMED LINEAR WITH TEMP:<br />

* H(N2)*.2475T, H(H20)*.45T-4.89, H(M)».21T-20.8, H(H)*3.466T-40.<br />

*<br />

TGSPR*(UMSPG+4.89*MSSPG+20.8*MMSPG+40.0*MHSPG)/...<br />

(MNSPG*(.2475-.1851*GCN)*MSSPG*(.45-.1851*GCS)


END<br />

STOP<br />

CALL DEBUG!1,0.0)<br />

CALL CEBUGd,3600.)<br />

CALL DEBUG(1,7600.)<br />

CALL DEBUG!1.1C80C.)<br />

CALL DEBUG!1,14400.)<br />

CALL CEBUGd,17999.)<br />

195


197<br />

APPENDIX B<br />

MODIFICATION TO MARCH SUBROUTINE ANSQ<br />

In the MARCH code, the calcul<strong>at</strong>ion of decay he<strong>at</strong>ing is carried<br />

out in subroutine ANSQ. For this study, the calcul<strong>at</strong>ion was modified<br />

to include the actinide decay he<strong>at</strong> source in a BWR following a burnup<br />

of 34,000 MWd/x. A listing of the revised subroutine follows:<br />

Subroutine ANSQ (ANS-TIME-TAP)<br />

C<br />

C ANSQ calcul<strong>at</strong>es the decay he<strong>at</strong> using ANS correla-<br />

C tions.<br />

ANS1=ANS2=0.0<br />

TVAR=TIME*60.0<br />

IF (TVAR-GT-10.0) GO TO 10<br />

ANS1=0.06950-0.001592*(ALOG(TVAR))<br />

IF (TVAR-LT-3.) ANS1=1.<br />

GO TO 40<br />

10 IF (TVnAJi.GT. 150.0) GO TO 20<br />

ANS1=0.069241-0.0069355*(ALOG(TVAR))<br />

GO TO 40<br />

20 IF (TVAR-GT.4.E6) GO TO 30<br />

ANS1=4.0954E-2-2.8324E-3*(ALOG(TVAR))<br />

GO TO 40<br />

30 ANS1=4.6893E-3-2.3800E-4*(ALOG(TVAR))<br />

40 TVAR=(TIME+TAP)*60.0<br />

IF (TV.AJi-GT-10.0) GO TO 50<br />

ANS2=6.950E-2-1.592E-3*(ALOG(TVAR))<br />

GO TO 80<br />

50 IF (TVhAhR-GT-150.0) GO TO 60<br />

ANS2=6.9241E-2-6.9355E-3*(ALOG(TVAR))<br />

GO TO 80<br />

60 IF (TVAR.GT-4.E6) GO TO 70<br />

ANS2=4.0954E-2-2.8324E-3*(ALOG(TVAR))<br />

GO TO 80<br />

70 ANS2=4.6893E-3-2.3800E-4*(ALOG(TVAR))<br />

80 ANS-ANS1-ANS2<br />

RETURN<br />

END


199<br />

APPENDIX C<br />

MARCH INPUT FOR ACCIDENT SEQUENCE TB'


SNLCOOL<br />

SEND<br />

202<br />

INDUCE<br />

NC0B*2,<br />

NHPV1=2,<br />

NRPV2*1,<br />

ICEC0B*-1,<br />

DTPNT=20.0,<br />

IDRY=-1,<br />

I«ET*2,<br />

RPOOL*7.801E06,<br />

TPOOL*95.0,<br />

VDRX=3.839E03,<br />

VTOROS=257700.0,<br />

BVNAX=5. 146E05,<br />

HSHP=-2,<br />

NSHP2*2,<br />

NCAV=-1,<br />

VCAV*4789.1,<br />

VFLR=15.0,<br />

AVBRK*292.0,<br />

CVBRK*4.04,<br />

VC(1)*159000.0,257700.0,<br />

AREA{1)=1.6399E03,1.098E04,<br />

HOH(1)*0.2.1.0,<br />

TEHPO(1)*150.,95.,<br />

N=10,<br />

NS


203<br />

DP ART=0.0208333,<br />

FZHCR*0.05,<br />

FZOCR*0.08.<br />

FZOS1=0. 1,<br />

WFE2*7992.,<br />

TFEO0=546.,<br />

FOLSG*0.0,<br />

PVSL=1000.,<br />

TCAV=1210.,<br />

ABRK*0.0,<br />

TBRK=45.0,<br />

DTPNTB*5.0,<br />

DTPN=-5.,<br />

VOLP*2.459E04,<br />

VOLS=9.638E03,<br />

WCST*3.11E06,<br />

F


205<br />

Appendix D<br />

PRESSURE SUPPRESSION POOL MODEL<br />

D.l Introduction<br />

The primary containment of each of the <strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant<br />

units is a Mark I pressure suppression pool system. The safety objective<br />

of the Mark I containment is to provide the capability, in the event of an<br />

accident, to limit the release of fission products to the environment.29<br />

The key to the safety objective of this system lies in the performance<br />

of the pressure suppression pool (PSP). The PSP is designed to rapidly<br />

and completely condense steam released from the reactor pressure vessel,<br />

to contain fission products released from the vessel, and to serve as a<br />

source of w<strong>at</strong>er for the emergency core cooling systems. If the PSP should<br />

fail to properly perform during an accident sequence, then there is a high<br />

probability th<strong>at</strong> fission products will be released to the environment.<br />

In the past few years, a major concern of the NRC, the BWR vendor,<br />

and the utilities who oper<strong>at</strong>e the early gener<strong>at</strong>ion BWRs has been scenar<br />

ios30 where it has not been conclusively shown th<strong>at</strong> the PSP will meet<br />

the performance requirements st<strong>at</strong>ed above. Specifically, there is a lack<br />

of inform<strong>at</strong>ion on condens<strong>at</strong>ion oscill<strong>at</strong>ions and the resulting loads they<br />

place on the PSP. In addition, there is the question of pressure suppres<br />

sion pool thermal str<strong>at</strong>ific<strong>at</strong>ion and the resulting impact of this phenome<br />

non on the condensing ability of the PSP.<br />

The problem of condens<strong>at</strong>ion oscill<strong>at</strong>ions* includes the analysis of<br />

both loads which origin<strong>at</strong>e <strong>at</strong> the downcomer exit during a large break loss<br />

of coolant accident (LOCA) and loads derived from the safety relief valve<br />

(SRV) discharge during normal blowdown to the PSP. The condens<strong>at</strong>ion os<br />

cill<strong>at</strong>ion problem involves coupling an analysis of the momentum trans<br />

port within the PSP to a stress analysis of the torus walls.<br />

The problem of pool thermal str<strong>at</strong>ific<strong>at</strong>ion is of interest because<br />

thermal layering of the w<strong>at</strong>er near a SRV discharge point can limit the<br />

ability of the PSP to condense the steam. Subsequently, this can lead to<br />

increased intensity of the condens<strong>at</strong>ion oscill<strong>at</strong>ion loads and possibly to<br />

overpressuriz<strong>at</strong>ion of the torus. Furthermore, the temper<strong>at</strong>ure distribu<br />

tion in the torus determines (to some extent) the distribution of fission<br />

products in the PSP during an accident. Thus, an analysis of fission pro<br />

duct transport to the environment will depend on an analysis of the tem<br />

per<strong>at</strong>ure distribution in the PSP.<br />

D.2 Purpose and Scope<br />

The purpose of this work is to study the dynamics of the Mark I pre<br />

ssure suppression pool (PSP). Knowledge of the response of the PSP is<br />

*In the liter<strong>at</strong>ure, when the condens<strong>at</strong>ion instability occurs outside<br />

the relief valve tailpipe it is termed "condens<strong>at</strong>ion oscill<strong>at</strong>ion." If it<br />

occurs inside the pipe, the phenomenon is called "chugging." Here, "con<br />

dens<strong>at</strong>ion oscill<strong>at</strong>ions" includes both of these effects.


206<br />

desired for transients ranging from a normal SRV discharge to a full<br />

blown, large break LOCA. The primary objective of this study is to im<br />

prove the available BWR pressure suppression pool analysis techniques. A<br />

secondary objective is to learn as much as possible about the complex<br />

phenomena involved in each of the transients (phenomena such as pool<br />

swell, condens<strong>at</strong>ion oscill<strong>at</strong>ion, chugging, and thermal str<strong>at</strong>ific<strong>at</strong>ion).<br />

An analysis of the PSP dynamics will necessarily involve accounting<br />

for the two phase flow of steam jets into subcooled w<strong>at</strong>er and the ensuing<br />

transport of mass, momentum, and energy by the mechanism of condens<strong>at</strong>ion.<br />

Because of the complex geometry of the PSP, (toroidal geometry plus large,<br />

submerged, complic<strong>at</strong>ed flow obstructions plus an air-w<strong>at</strong>er interface) the<br />

analysis tool used in this study will be a st<strong>at</strong>e-of-the-art, 3-D thermal<br />

hydraulics code.<br />

Pending completion of this work, it will be necessary to assume<br />

pool-averaged conditions for accident analyses.<br />

D.3 Description of the System<br />

The Mark I containment system consists of the drywell, the pressure<br />

suppression pool, the vent system connecting the drywell and PSP, a con<br />

tainment cooling system, isol<strong>at</strong>ion valves, and various service equipment.<br />

Figure D-l shows the arrangement of the drywell, PSP, and vent system<br />

within the Reactor Building.<br />

The drywell is a steel pressure vessel with a spherical lower portion<br />

and a cylindrical upper portion. It is designed for an internal pressure<br />

of 0.531 MPa (62 psig) <strong>at</strong> a temper<strong>at</strong>ure of 138°C (281°F). Normal environ<br />

ment in the drywell during plant oper<strong>at</strong>ion is an inert <strong>at</strong>mosphere of ni<br />

trogen <strong>at</strong> <strong>at</strong>mospheric pressure and a temper<strong>at</strong>ure of about 57°C (135°F).<br />

The vent system consists of 8 circular vent pipes which connect the<br />

drywell to the PSP. The vent pipes are designed to conduct flow from the<br />

drywell to the PSP (in the event of a LOCA) with minimum resistance, and<br />

to distribute this flow uniformly in the pool. The vent pipes are de<br />

signed for an internal pressure of 0.531 MPa (62 psig) with a temper<strong>at</strong>ure<br />

of 138°C (281°F); they are also designed to withstand an external pressure<br />

of 0.014 MPa (2 psi) above internal pressure.<br />

The pressure suppression pool is a toroidal shaped steel pressure<br />

vessel loc<strong>at</strong>ed below the drywell. The PSP contains about 3823 m3<br />

(135,000 ft3) of w<strong>at</strong>er and has an air space above the w<strong>at</strong>er pool of 3370<br />

m3 (119,000 ft3). Inside the PSP, extending around the circumference<br />

of the torus, is a 1.45 m (4.75 ft) diameter vent header. The 8 drywell<br />

vents connect to this vent header. Projecting down from the vent header<br />

are 96 downcomer pipes which termin<strong>at</strong>e 1.22 m (4 ft) below the surface of<br />

the w<strong>at</strong>er. At 13 unevenly distributed positions around the PSP, discharge<br />

lines from the safety relief valves extend through the vent pipes and ter<br />

min<strong>at</strong>e in a T-quencher device loc<strong>at</strong>ed near the bottom of the pool. Figure<br />

D-2 shows a cross section of the PSP and the rel<strong>at</strong>ive loc<strong>at</strong>ions of the<br />

vent pipe, vent header, downcomer, SRV discharge line, and the T-quencher,<br />

which has been rot<strong>at</strong>ed 90° for the purpose of illustr<strong>at</strong>ion. Near the<br />

bottom of the PSP, a 0.762 m (30-in.) suction header (ring header) cir<br />

cumscribes the torus and connects to the pool <strong>at</strong> four loc<strong>at</strong>ions. At<br />

<strong>Browns</strong> <strong>Ferry</strong>, the RHR, HPCI, core spray, and RCIC systems are supplied<br />

from this header.


SUPPRESSION<br />

CHAMBER<br />

TOROIDAL<br />

HEADER<br />

enclosed.<br />

207<br />

ORNL-DWG 79-7611A ETD<br />

DRYWELL<br />

REACTOR VESSEL<br />

REACTOR BUILDING<br />

Fig. D.l BWR reactor building showing primary containment system<br />

The torus which contains the pressure suppression pool is designed to<br />

essentially the same requirements as the drywell liner, i.e., a maximum<br />

internal pressure of 0.531 MPa (62 psig) <strong>at</strong> 138°C (281°F), but neither the<br />

drywell nor the torus is designed to withstand the stresses which would be<br />

cre<strong>at</strong>ed by a significant internal vacuum. To ensure th<strong>at</strong> a significant<br />

vacuum can not occur in the drywell, vacuum breaker valves are installed,<br />

which will open to permit flow from the PSP airspace into the drywell<br />

whenever the suppression pool pressure exceeds the drywell pressure by<br />

more than 3447 Pa (0.5 psi). Additional vacuum breaker valves with the<br />

same setpoints are installed to permit flow from the Reactor Building into<br />

the PSP airspace, to prevent a significant vacuum there.<br />

D.4 Identific<strong>at</strong>ion of the Phenomena<br />

The thermal hydraulic phenomena associ<strong>at</strong>ed with a BWR pressure sup<br />

pression pool are mainly those dealing with the PSP response during two


RING GIRDER<br />

ECCS<br />

SUCTION<br />

LINE<br />

t = 0.756 in.<br />

MAIN VENT-<br />

BELLOWS<br />

Fig. D.2 <strong>Browns</strong> <strong>Ferry</strong> Mark I containment pressure suppression<br />

pool.<br />

ORNL-DWG 81-8567 ETD<br />

SAFETY RELIEF VALVE<br />

DISCHARGE LINE<br />

ro<br />

o<br />

oo


209<br />

types of transients: (1) LOCA-rel<strong>at</strong>ed phenomena and (2) SRV-discharge<br />

phenomena.<br />

A. LOCA — Rel<strong>at</strong>ed Phenomena<br />

Immedi<strong>at</strong>ely following the pipe break in a LOCA, the drywell pressure<br />

and temper<strong>at</strong>ure increase very quickly. The pressure increase forces w<strong>at</strong>er<br />

standing in the downcomer to acceler<strong>at</strong>e rapidly into the PSP and impinge<br />

on the torus wall. Following the slug of w<strong>at</strong>er, air th<strong>at</strong> was in the vent<br />

pipes and drywell is forced into the PSP. This forms a bubble of air <strong>at</strong><br />

the downcomer exit which expands into the suppression chamber and causes<br />

the pool to swell. As the air bubble rises into the torus airspace, the<br />

w<strong>at</strong>er will experience a gravity-induced fallback and phase separ<strong>at</strong>ion will<br />

again occur.<br />

The pool swell transient described above lasts on the order of 3 to 5<br />

s.30 It has been studied by several authors, both experimentally31-33 and<br />

numerically.3•+,35 The consensus is th<strong>at</strong> pool swell impingement and drag<br />

loads induced during a LOCA are conserv<strong>at</strong>ively estim<strong>at</strong>ed and acceptable.<br />

Immedi<strong>at</strong>ely following the pool swell transient, an air/steam mixture<br />

will flow into the PSP. Early in this process, when the mass flow r<strong>at</strong>e is<br />

high, the injected steam condenses <strong>at</strong> an unsteady r<strong>at</strong>e causing periodic<br />

oscill<strong>at</strong>ions in the pressure and flow. However, since the mass flux is<br />

high enough to maintain the steam/w<strong>at</strong>er interface outside the downcomer,<br />

the overall condens<strong>at</strong>ion proceeds <strong>at</strong> a regular r<strong>at</strong>e. This phenomenon is<br />

known as condens<strong>at</strong>ion oscill<strong>at</strong>ion. It is characterized by a steady, peri<br />

odic vari<strong>at</strong>ion in the pressure which forces local structures within the<br />

torus to vibr<strong>at</strong>e in phase with the oscill<strong>at</strong>ions. Condens<strong>at</strong>ion oscill<strong>at</strong>ion<br />

has been studied experimentally36»37 and analytically;37>38 however,<br />

the basic driving mechanism for the pressure resonance has not been iden<br />

tified.39<br />

When the air/steam flow through the downcomer decreases to the point<br />

where the condens<strong>at</strong>ion r<strong>at</strong>e outside the pipe exceeds the steam flow exit<br />

ing the pipe, the steam bubble collapses very rapidly. This results in a<br />

large drop in the steam pressure and the steam-w<strong>at</strong>er interface rushes up<br />

into the downcomer. Once there, the interface is warmed by condensing<br />

steam and the condens<strong>at</strong>ion r<strong>at</strong>e begins to decrease. At some point, the<br />

steam pressure will rise, and the interface is pushed out of the downcomer<br />

to form an irregularly shaped bubble <strong>at</strong> the pipe exit. The bubble begins<br />

to collapse; and the entire process, known as chugging, repe<strong>at</strong>s. Chugg<br />

ing is characterized by rapid, irregular interface acceler<strong>at</strong>ions and pres<br />

sure oscill<strong>at</strong>ions th<strong>at</strong> cause large loads on the torus structure.<br />

The chugging phenomenon is very similar to the condens<strong>at</strong>ion oscilla<br />

tion problem. It has also been studied in detail, with analysis methods<br />

which range from manometer-like models th<strong>at</strong> <strong>at</strong>tempt to predict the gross<br />

motion of the interface, to probabilistic models th<strong>at</strong> <strong>at</strong>tempt to predict<br />

internal chugging."40"1*2 The central problems which plague analysis of<br />

the chugging phenomenon are (1) high uncertainty in the basic condens<strong>at</strong>ion<br />

r<strong>at</strong>es involved and (2) lack of understanding of the triggering mechanism<br />

for bubble collapse.<br />

Both of the condens<strong>at</strong>ion phenomena (chugging and condens<strong>at</strong>ion oscil<br />

l<strong>at</strong>ion) involve transient, stochastic, turbulent, two phase flow. Because


210<br />

of the complexity of these problems, no accur<strong>at</strong>e assessment has been made<br />

of the loads involved.30 Consequently, the analysis of PSP response to<br />

condens<strong>at</strong>ion oscill<strong>at</strong>ions must rely on d<strong>at</strong>a from experiments which model<br />

plant behavior. Thus, there is a need for improvement of the analysis<br />

capability in this area.<br />

B. SRV — Discharge Phenomena<br />

When a SRV actu<strong>at</strong>es, w<strong>at</strong>er and air initially in the discharge line<br />

are immedi<strong>at</strong>ely acceler<strong>at</strong>ed into the PSP. This results in air-clearing<br />

loads much the same as the pool swell loads discussed earlier. These<br />

loads are of no major consequence because they can be adequ<strong>at</strong>ely "scaled"<br />

from the results of labor<strong>at</strong>ory experiments.<br />

Following the air-clearing phase, steam is injected <strong>at</strong> high velocity<br />

into the PSP. Experience has shown th<strong>at</strong>, depending on the discharge de<br />

vice used, condens<strong>at</strong>ion oscill<strong>at</strong>ions can occur as steam bubbles exit the<br />

pipe and collapse in the bulk fluid. As the steam bubbles collapse,<br />

severe pressure oscill<strong>at</strong>ions are induced on the surrounding structures.<br />

Current practice is to limit the severity of these oscill<strong>at</strong>ions by using a<br />

T-quencher device.^3 The T-quencher is a section of pipe (in the form<br />

of a "T") with holes str<strong>at</strong>egically drilled in the arms to enhance local<br />

mixing. The T-quencher has been shown to be very effective in elimin<strong>at</strong>ing<br />

the severity of the pressure pulses, provided the local bulk fluid temper<br />

<strong>at</strong>ure is sufficiently low.<br />

This is the factor th<strong>at</strong> establishes a limit on the effectiveness of<br />

the T-quencher — the local fluid temper<strong>at</strong>ure. If it becomes too high,<br />

the PSP will not be able to rapidly condense all the steam. Some of it<br />

will escape into the air space above the pool and pressurize the torus.<br />

When the suppression pool pressure becomes 3447 Pa (0.5 psi) gre<strong>at</strong>er than<br />

the drywell, the vacuum breakers will open and steam will escape into the<br />

drywell (forcing the temper<strong>at</strong>ure and pressure up). As more steam is dis<br />

charged to the PSP, the drywell and torus pressure will continue to in<br />

crease.<br />

It is concern for this increase in drywell pressure (possibly result<br />

ing in overpressuriz<strong>at</strong>ion) th<strong>at</strong> has led to the establishment of strict<br />

procedures for the sequential ordering of SRV blowdowns to the PSP. Cur<br />

rent practice involves sequentially venting SRVs on opposite sides of the<br />

torus; this prevents excessive local temper<strong>at</strong>ures near any discharge<br />

point.<br />

More recently, concern has been expressed over the long term response<br />

of the PSP during a prelonged <strong>St<strong>at</strong>ion</strong> Blackout. During part of this<br />

scenario, the oper<strong>at</strong>or loses manual control of the SRVs. The long term<br />

result is th<strong>at</strong> a single SRV will continually open into the PSP. The local<br />

fluid temper<strong>at</strong>ure will monotonically rise, resulting in pressuriz<strong>at</strong>ion of<br />

the torus and possible condens<strong>at</strong>ion oscill<strong>at</strong>ions. The potential exists<br />

for rupture of the torus due to overpressure coupled with violent pressure<br />

oscill<strong>at</strong>ions.<br />

For example, this potential exists in the particular case of a Sta<br />

tion Blackout with loss of the HPCI and RCIC systems. At about 100 min<br />

into the transient, local pool temper<strong>at</strong>ures <strong>at</strong> the discharge bay are post<br />

ul<strong>at</strong>ed (c.f. Section 9) to be gre<strong>at</strong>er than 149°C (300°F). At th<strong>at</strong> time,


211<br />

steam condens<strong>at</strong>ion oscill<strong>at</strong>ions are expected to acceler<strong>at</strong>e due to the ex<br />

cessive temper<strong>at</strong>ure and the continuous discharge of superhe<strong>at</strong>ed, non-condensible<br />

gases (from hydrogen gener<strong>at</strong>ed in the melting core) into the PSP.<br />

These extreme conditions in the PSP yield a high probability for rupture<br />

of the torus.<br />

Along with the temper<strong>at</strong>ure rise assoc<strong>at</strong>ed with SRV discharge comes a<br />

gravity induced thermal str<strong>at</strong>ific<strong>at</strong>ion of the pool. This phenomenon is of<br />

interest because the layering tends to remain long after SRV discharge is<br />

complete. Since the str<strong>at</strong>ific<strong>at</strong>ion remains for a significant period of<br />

time, the validity of the current design basis for Mark I PSPs becomes<br />

questionable. This is because a fundamental assumption in virtually all<br />

the transient analyses is th<strong>at</strong> the pool is thoroughly mixed and <strong>at</strong> a uni<br />

form temper<strong>at</strong>ure following SRV blowdown. The impact of thermal str<strong>at</strong>ifi<br />

c<strong>at</strong>ion on the performance of the PSP remains to be evalu<strong>at</strong>ed.<br />

Thermal str<strong>at</strong>ific<strong>at</strong>ion is also of interest because the temper<strong>at</strong>ure<br />

distribution in the PSP affects the fission product distribution in the<br />

torus. Should a breach of primary containment occur, transport of the fis<br />

sion products to the environment will depend, to some extent, on the the<br />

rmal str<strong>at</strong>ific<strong>at</strong>ion in the torus. Thus, an analysis of fission product<br />

transport is coupled with the thermal str<strong>at</strong>ific<strong>at</strong>ion problem.<br />

To the best of our knowledge, no inform<strong>at</strong>ion is available in the open<br />

liter<strong>at</strong>ure concerning system<strong>at</strong>ic analysis of the thermal str<strong>at</strong>ific<strong>at</strong>ion<br />

problem. There is therefore the need for research in this area.<br />

Model requirements<br />

D.5 Pool Modeling Consider<strong>at</strong>ions<br />

The prediction of suppression pool system behavior during the course<br />

of a Severe Accident is an exceedingly difficult task. The previously de<br />

scribed phenomena comprise a complex set of physical processes for which<br />

few detailed analytical models currently exist. These phenomena can be<br />

roughly divided into two types, i.e., thermal hydraulic phenomena and<br />

fluid-structure interaction phenomena. The initial efforts <strong>at</strong> ORNL are<br />

directed toward the development of the thermal hydraulic model. A brief<br />

survey was conducted to identify existing multi-dimensional thermal hy<br />

draulic analysis codes which might be applied to the problem. The re<br />

sults of the survey are shown in Table Dl which presents a brief summary<br />

of the candid<strong>at</strong>e codes.<br />

Due to the n<strong>at</strong>ure of the previously described phenomena, it was felt<br />

th<strong>at</strong> any model employed for suppression pool analysis should possess the<br />

following characteristics:<br />

1. Appropri<strong>at</strong>e hydrodynamics<br />

a. two phase<br />

b. non-equilibrium<br />

c. free field form<strong>at</strong> (equ<strong>at</strong>ions and constitutive rel<strong>at</strong>ionships<br />

independent of hydraulic diameter)<br />

d. incorpor<strong>at</strong>e a non-condensable gas field<br />

e. employ multi-dimensional geometry (3 dimensions desirable)<br />

2. Employ appropri<strong>at</strong>e constitutive rel<strong>at</strong>ionships<br />

3. Utilize efficient solution techniques<br />

4. Readily accessable to ORNL staff.


212<br />

Table Dl. Candid<strong>at</strong>e suppression pool analysis codes<br />

Code Developer Geometry T-H characteristics<br />

TRAC LANL 3D cylindrical 2 fluid<br />

(PIA, PD2) nonequilibrium<br />

COBRA-TF BPNL 3D cartesian 3 field<br />

nonequlibrium<br />

CCMMIX-2 ANL 3D 2 fluid<br />

BEAC0N/Mod2 INEL 2D cartesian<br />

cylindrical<br />

spherical<br />

nonequilibrium<br />

2 component vapor<br />

2 phase<br />

nonequilibrium<br />

Requirements l.a and l.b are imposed by the complex n<strong>at</strong>ure of the conden<br />

s<strong>at</strong>ion processes involved in SRV discharge and LOCA blowdown transients.<br />

Requirement l.c is a result not only of the n<strong>at</strong>ure of the SRV discharge<br />

process, but of the geometric dimensions of the suppression pool. The en<br />

ormous size and complex structural design of the suppression pool system<br />

virtually mand<strong>at</strong>es th<strong>at</strong> free field hydrodynamics be employed. Requirement<br />

l.d is imposed because significant amounts of non-condensable gases will<br />

be released from the fuel and gener<strong>at</strong>ed in metal-w<strong>at</strong>er reactions during<br />

Severe Accidents. Requirement I.e. is imposed by the n<strong>at</strong>ure of the hydrodynamic<br />

phenomena and the complex structural rel<strong>at</strong>ionship of the SRV<br />

discharge lines, vent downcomers, and ring header suction system. Appro<br />

pri<strong>at</strong>e constitutive rel<strong>at</strong>ionships (requirement 2) are needed for closure<br />

of the hydrodynamic field equ<strong>at</strong>ions. Many of the rel<strong>at</strong>ionships employed<br />

in existing thermo-hydraulic codes may be invalid for use in the present<br />

problem. Requirement 3 is imposed by the fact th<strong>at</strong> it will be necessary<br />

to predict the behavior of the suppression pool for periods of time rang<br />

ing from a few minutes to several hours. It is, therefore, important th<strong>at</strong><br />

all codes employ fast solution techniques in order to minimize computing<br />

costs. The fourth characteristic is desired because the computer code<br />

selected for the analysis will require local modific<strong>at</strong>ion as necessary to<br />

reflect the unique characteristics of the suppression pool problem.<br />

We are unaware of any existing computer code or model which pos<br />

sesses all of the desirable characteristics outlined above. The initial<br />

effort <strong>at</strong> ORNL is directed toward development of a pool model utilizing<br />

the TRAC-PIA"*1* vessel module. TRAC (Transient Reactor Analysis Code)<br />

— PIA is a best estim<strong>at</strong>e computer code developed <strong>at</strong> Los Alamos Na<br />

tional Labor<strong>at</strong>ory for analysis of large break PWR loss of coolant acci<br />

dents. Although more recent versions of TRAC are available (i.e., PD2,<br />

PF1, and BD1), TRAC-PIA was chosen for this applic<strong>at</strong>ion because it is in<br />

stalled and oper<strong>at</strong>ional on ORNL's computer system.<br />

While TRAC-PIA does employ a full three dimensional, two fluid, non<br />

equlibrium approach to reactor vessel hydrodynamics, it does not account<br />

for free flow or non-condensable gas fields. Additionally, the constitu<br />

tive rel<strong>at</strong>ionships employed In TRAC-PIA are based upon d<strong>at</strong>a which was


213<br />

originally developed for vertical pipe flow and may not be valid for ap<br />

plic<strong>at</strong>ion to steam jet discharge phenomena.1*5 Though these limit<strong>at</strong>ions<br />

are significant, it is felt th<strong>at</strong> our access to TRAC-PIA will allow us to<br />

implement any changes in the constitutive rel<strong>at</strong>ionship package which might<br />

be necessary to reflect the characteristics of the suppression pool<br />

phenomena. LANL is currently modifying TRAC to include non-condensable<br />

gas field hydrodynamics (TRAC-PF1). ORNL's utiliz<strong>at</strong>ion of TRAC-PIA will<br />

allow us to quickly implement this modified version when it becomes avail<br />

able.<br />

We have tent<strong>at</strong>ively chosen the PELE-IC1*6 code for future use in an<br />

alysis of the fluid-structure interaction within the suppression pool.<br />

PELE-IC (developed by LLL) couples a two dimensional Eulerian fluid dy<br />

namics algorithm to a Lagrangian finite element shell algorithm. The code<br />

can couple either a one dimensional or a lumped parameter description of<br />

compressible gases, and can employ either cartesian or cylindrical coordi<br />

n<strong>at</strong>es. PELE-IC employs the basic semi-implicit solution algorithm con<br />

tained in the SOLA code.1*7 The movement of free surfaces is tre<strong>at</strong>ed in<br />

a full donar cell fashion based on a combin<strong>at</strong>ion of void fractions and<br />

interface orient<strong>at</strong>ion. The structural motion is calcul<strong>at</strong>ed by a finite<br />

element method, from the applied fluid pressure <strong>at</strong> the fluid structure in<br />

terface. The finite element shell structure algorithm uses conventional<br />

thin shell theory with transverse shear and provides the fluid module with<br />

the resultant position and velocity of the interface. The code is capable<br />

of analyzing both vent clearing and condens<strong>at</strong>ion rel<strong>at</strong>ed phenomena.<br />

TRAC suppression pool model description<br />

A block diagram of the ORNL-TRAC suppression pool model is shown in<br />

Fig. D-3. The model is comprised of the TRAC VESSEL module which repre<br />

sents the pool hydrodynamics, and two FILL and PIPE modules, which repre<br />

sent the SRV discharge flow and T-quencher assembly. A detailed view of<br />

ORNL-DWG 81-8150 ETD<br />

FILL<br />

PIPE PIPE<br />

1<br />

VESSEL<br />

Fig. D.3 Suppression pool model block diagram.<br />

1


214<br />

the pool model is shown in Figs. D-4 and D-5. The pool is represented as<br />

112 cells in cylindrical geometry, loc<strong>at</strong>ed <strong>at</strong> five axial, four azimuthal,<br />

and eight radial regions. SRV discharge is assumed to occur as shown in<br />

Figs. D-4 and D-5. Half of the SRV discharge flow is directed radially<br />

inward from the fifth radial zone, while the other half is directed ra<br />

dially outward. It should be noted th<strong>at</strong> the T-quencher is not modeled in<br />

a strictly physical fashion, since the discharge is assumed to occur<br />

through a single open ended pipe with a flow area approxim<strong>at</strong>ely equal to<br />

th<strong>at</strong> of the T-quencher device. This approach was chosen for the initial<br />

model due to the significant reduction in input prepar<strong>at</strong>ion time and<br />

model complexity associ<strong>at</strong>ed with this approach. The initial w<strong>at</strong>er level<br />

is assumed to be 4.47 meters above the pool bottom (i.e., <strong>at</strong> level 4 in<br />

0, = 0.0165689 rad<br />

62 = 2.1053743 rad<br />

03 = 4.1942798 rad<br />

04 = 6.2831853 rad<br />

Fig. D.4 Suppression pool model top view.<br />

ORNL-DWG 81-8151 ETD<br />

TOP VIEW<br />

R, = 12.3901 m<br />

R2 = 12.9311 m<br />

R3 = 13.5239 m<br />

R4 = 14.7035 m<br />

16.9926 m<br />

19.2877 m<br />

R7 = 20.4643 m<br />

R8 = 21.0601 m<br />

R9 = 21.6011 m


VESSEL<br />

CENTER<br />

R6 R7 R8 Rg<br />

Fig. D.5 Suppression pool model cross section.<br />

ORNL-DWG 81-8152 ETD<br />

HALF CROSS SECTION VIEW AT AA<br />

B8 NO FLOW REGION<br />

INITIAL FLUID CELLS<br />

M INITIAL VAPOR CELLS<br />

|S3<br />

H


216<br />

Fig. D-5) with all cells in level 5 occupied by vapor. Internal struc<br />

tures (vent header, down comers, etc.) are not modeled.<br />

Current st<strong>at</strong>us of suppression pool model<br />

Several preliminary computer runs have been made in which TRAC d<strong>at</strong>a<br />

base errors have been identified and elimin<strong>at</strong>ed. We are currently exper<br />

iencing problems rel<strong>at</strong>ed to the limit<strong>at</strong>ions of TRAC-PIA in accounting for<br />

the simultaneous existence of steam (vapor) and perfect gas (nitrogen)<br />

within the vessel. The TRAC user must specify th<strong>at</strong> either vapor or air<br />

properties be used everywhere within the code. In terms of the pressure<br />

suppression pool, this means th<strong>at</strong> the nitrogen gas (which is loc<strong>at</strong>ed in<br />

the space above the pool) must be tre<strong>at</strong>ed as subcooled vapor if one is to<br />

inject steam into the pool. It is also possible th<strong>at</strong> the constitutive re<br />

l<strong>at</strong>ionships within TRAC are producing instabilities in the solution due to<br />

their dependence upon hydraulic diameter and fluid property inform<strong>at</strong>ion.<br />

We are currently working closely with the TRAC User Liaison Section <strong>at</strong><br />

LANL in an effort to determine whether these problems can be overcome. In<br />

the event these problems prove to be insurmountable, we will re-evalu<strong>at</strong>e<br />

the remaining code candid<strong>at</strong>es and select an altern<strong>at</strong>ive program for the<br />

suppression pool thermal hydraulic analysis.


217<br />

APPENDIX E<br />

A COMPENDIUM OF INFORMATION CONCERNING THE BROWNS FERRY<br />

UNIT 1 HIGH-PRESSURE COOLANT INJECTION SYSTEM<br />

E.1 Purpose<br />

The High-Pressure Coolant Injection (HPCI) System is designed to en<br />

sure adequ<strong>at</strong>e core cooling to prevent damage to fuel in the event of a<br />

loss of coolant accident th<strong>at</strong> does not result in rapid depressuriz<strong>at</strong>ion of<br />

the reactor vessel. The HPCI System provides w<strong>at</strong>er to make up for th<strong>at</strong><br />

which is lost through steam gener<strong>at</strong>ed by decay he<strong>at</strong>.1*8<br />

E.2 System Description<br />

The HPCI System (Fig. E-l) consists of a steam turbine driven booster<br />

pump — main pump combin<strong>at</strong>ion and the associ<strong>at</strong>ed piping and valves.<br />

The booster pump can take suction from either the condens<strong>at</strong>e storage tank<br />

or the pressure suppression pool. The HPCI pumped flow enters the reactor<br />

vessel feedw<strong>at</strong>er line "A" via a thermal sleeve connection. A test line<br />

permits testing of the HPCI System <strong>at</strong> full flow while the reactor is <strong>at</strong><br />

power, with the main pump discharge routed to the condens<strong>at</strong>e storage tank.<br />

A minimum flow line connects the main pump discharge to the pressure sup<br />

pression pool, as a means of ensuring a flow of <strong>at</strong> least 0.038 m3/s (600<br />

GPM) through the pumps. The normal setpoint for HPCI pumped flow is<br />

18.93 m3/s (5000 GPM).<br />

The HPCI turbine is driven by steam extracted from main steam line<br />

"B" upstream of the main steam line isol<strong>at</strong>ion valves. The two primary<br />

containment isol<strong>at</strong>ion valves in the steam line to the HPCI turbine are<br />

normally open to keep the piping to the turbine <strong>at</strong> elev<strong>at</strong>ed temper<strong>at</strong>ures<br />

to permit rapid system startup (within 25 s of receipt of an initi<strong>at</strong>ion<br />

signal). The normally closed DC-motor-oper<strong>at</strong>ed steam supply valves up<br />

stream of the HPCI turbine will open against full system pressure within<br />

20 s after receipt of a system initi<strong>at</strong>ion signal. Signals from the con<br />

trol system open or close the turbine stop valve. The turbine control<br />

valve is physically <strong>at</strong>tached to the HPCI turbine and is positioned by the<br />

turbine governor as necessary to maintain the pumped flow <strong>at</strong> the level set<br />

by the oper<strong>at</strong>or, normally 0.315 m3/s (5000 GPM). The turbine exhaust<br />

steam is discharged to the pressure suppression pool. The turbine gland<br />

seals are vented to a gland seal condenser. A small w<strong>at</strong>er flow diverted<br />

from the booster pump discharge is used to cool both the turbine lubric<strong>at</strong><br />

ing oil cooler and the gland seal condenser. This cooling flow is re<br />

turned, together with the gland seal condens<strong>at</strong>e, to the booster pump suc<br />

tion. Noncondensible gases from the gland seal condenser are removed via<br />

a DC-motor-oper<strong>at</strong>ed blower to the Standby Gas Tre<strong>at</strong>ment System.<br />

A vacuum breaker line (not shown on Fig. E-l) is installed between<br />

the torus airspace and the HPCI turbine exhaust line. Its purpose is to<br />

prevent w<strong>at</strong>er from the pressure suppression pool from being drawn up into<br />

the turbine exhaust line as the steam condenses in this line following<br />

turbine oper<strong>at</strong>ion.


ELEVATION 577 ft<br />

6<br />

CONDENSATE<br />

RETURN<br />

HEADER<br />

SUPPRESSION<br />

POOL<br />

SUPPRESSION<br />

CHAMBER<br />

HEADER<br />

CONDENSATE<br />

STORAGE<br />

TANK<br />

CONDENSATE<br />

SUPPLY O<br />

HEADER ^<br />

WATER<br />

LEVEL<br />

ELEVATION<br />

536 ft<br />

•hJvi-<br />

PUMP


219<br />

E.3 HPCI Pump Suction<br />

The HPCI pump can take suction either from the condens<strong>at</strong>e storage<br />

header or from the pressure suppression pool via the suppression pool ring<br />

header. The normal lineup is for suction of the reactor-grade w<strong>at</strong>er in<br />

the condens<strong>at</strong>e storage header.<br />

Each <strong>Browns</strong> <strong>Ferry</strong> unit is provided with a 1419.4 m3 (375,000 gal<br />

lon) condens<strong>at</strong>e storage tank, which provides a w<strong>at</strong>er head to the storage<br />

header for th<strong>at</strong> unit. The storage header, which taps into the bottom of<br />

the storage tank, feeds the suctions of the high-pressure ECCS Systems,<br />

specifically, the pumps for the HPCI and the RCIC systems. The core spray<br />

pumps and the RHR pumps can be fed from this source, but are not normally<br />

aligned to it. All other demand for condens<strong>at</strong>e storage tank w<strong>at</strong>er is fed<br />

via a standpipe within the tank; the standpipe height is such th<strong>at</strong> 511.0<br />

m3 (135,000 gallons) of w<strong>at</strong>er is reserved for the ECCS Systems.<br />

It is important to note th<strong>at</strong> the local-manual opening of one normally<br />

locked-shut valve will cross-connect the <strong>Unit</strong> 3 and the <strong>Unit</strong> 1 condens<strong>at</strong>e<br />

storage header; the opening of a second such valve will cross-connect all<br />

three condens<strong>at</strong>e storage headers.1*9 Thus the <strong>Unit</strong> 1 ECCS Systems have a<br />

minimum of 511.0 and a maximum of 1419.4 m3 (135,000 to 375,000 gallons)<br />

available through normally open valves from the <strong>Unit</strong> 1 storage tank and<br />

these limits can be increased three-fold by manually opening two normally<br />

locked-closed valves. Two additional condens<strong>at</strong>e storage tanks, each of<br />

1892.5 m3 (500,000 gallon) capacity, have recently been installed <strong>at</strong> the<br />

<strong>Browns</strong> <strong>Ferry</strong> Nuclear Plant. Thus it is unlikely th<strong>at</strong> HPCI System opera<br />

tion will ever be limited by the availability of condens<strong>at</strong>e storage header<br />

w<strong>at</strong>er.<br />

The HPCI booster pump suction will be autom<strong>at</strong>ically shifted from the<br />

condens<strong>at</strong>e storage header to the suppression pool ring header if either:<br />

1. The w<strong>at</strong>er level above the booster pump suction falls to an elev<strong>at</strong>ion<br />

of 168.4 m (551 ft). This would mean th<strong>at</strong> the condens<strong>at</strong>e storage tank<br />

had completely drained and there remained just sufficient w<strong>at</strong>er in the<br />

condens<strong>at</strong>e storage header to effect a transfer before losing net posi<br />

tive suction head (NPSH).<br />

or<br />

2. The pressure suppression pool level increases to an indic<strong>at</strong>ed level of<br />

0.18 m (+7 in). Since the normal pool level is maintained between<br />

0.05 and 0.15 m ( 2 and 6 in.),50 this implies the addition of<br />

between 257.4 and 371.0 m3 (68,000 and 98,000 gallons) of w<strong>at</strong>er to<br />

the pool.<br />

The 0.76 m (30 in.) diameter suppression pool ring header lies parallel to<br />

and bene<strong>at</strong>h the suppression pool. W<strong>at</strong>er flow from the suppression pool to<br />

the ring header is via four 0.76 m (30 in.) diameter downcomer pipes<br />

spaced <strong>at</strong> irregular intervals around the torus. Each downcomer is capped<br />

with strainers <strong>at</strong> the torus end.<br />

The change in HPCI pump suction lineup is accomplished by the opening<br />

of two DC-motor-oper<strong>at</strong>ed valves in the line from the pressure suppression<br />

pool to the HPCI booster pump suction followed by the closing of the DCmotor-oper<strong>at</strong>ed<br />

valve in the suction line from the condens<strong>at</strong>e storage<br />

header. A check valve in the line from the suppression pool prevents<br />

backflow from the condens<strong>at</strong>e storage tank into the suppression pool during<br />

the change.


220<br />

Two pressure switches are used to determine the w<strong>at</strong>er head from the<br />

condens<strong>at</strong>e storage tank above the booster pump suction and two level<br />

switches monitor the suppression pool level. In either case, just one of<br />

the two available signals is sufficient to initi<strong>at</strong>e the shift in HPCI<br />

booster pump suction. Once the booster pump suction has been autom<strong>at</strong>i<br />

cally shifted to the pressure suppression pool, the oper<strong>at</strong>or cannot re<br />

position the valves back to the condens<strong>at</strong>e header suction lineup.<br />

The minimum required net positive suction head (NPSH) for the HPCI<br />

booster pump is 6.40 m (21 ft). This requirement is easily s<strong>at</strong>isfied when<br />

suction is taken from the condens<strong>at</strong>e storage header which is <strong>at</strong> an eleva<br />

tion of approxim<strong>at</strong>ely 8.69 m (28 1/2 ft) above the booster pump centerline.<br />

When the HPCI booster pump suction is shifted to the pressure sup<br />

pression pool due to a high indic<strong>at</strong>ed pool level of 0.18 m (+7 in.), the<br />

pool w<strong>at</strong>er level is 4.04 m (13.25 ft) above the booster pump centerline.<br />

Therefore, the NPSH requirement of 6.40 m (21 ft) can be met as long as<br />

the temper<strong>at</strong>ure of the pumped w<strong>at</strong>er is below 85.0°C (185°F), assuming no<br />

containment back pressure.<br />

E.4 System Initi<strong>at</strong>ion<br />

Either of two signals will cause an autom<strong>at</strong>ic start of the HPCI Sys<br />

tem. These are:<br />

1. Low reactor w<strong>at</strong>er level [12.09 m (476 in.) above vessel zero].<br />

2. High drywell pressure [0.12 MPa (2 psig)].<br />

With either of these conditions, both the suction valve to the con<br />

dens<strong>at</strong>e storage header and the minimum flow bypass valve will open if they<br />

were closed. The pump discharge valve between the main HPCI pump and<br />

feedw<strong>at</strong>er header "A" will open, and the two test line isol<strong>at</strong>ion valves<br />

will close if they were open. The steam supply valve to the turbine will<br />

open.*<br />

The DC-motor-driven auxiliary oil pump starts and as the oil pressure<br />

increases, the turbine stop and control valves open. Above 1800 rpm, the<br />

main oil pump which is driven on the turbine shaft takes over and main<br />

tains the oil pressure while the auxiliary oil pump shuts down. The mini<br />

mum flow bypass valve closes autom<strong>at</strong>ically when the increasing HPCI System<br />

pump flow exceeds 0.076 m3/s (1200 GPM).<br />

The time from actu<strong>at</strong>ing signal to full flow is less than 25 seconds.<br />

The turbine control system will act to maintain a pumped flow of 0.315<br />

m /s (5000 GPM) into the feedw<strong>at</strong>er line over a reactor pressure range of<br />

from 1.14 to 7.83 MPa (150 to 1120 psig). If desired, the oper<strong>at</strong>or in the<br />

Control Room can oper<strong>at</strong>e the system in the manual or autom<strong>at</strong>ic mode <strong>at</strong> a<br />

different controlled flow.<br />

The HPCI turbine oper<strong>at</strong>es <strong>at</strong> between 0.746 to 3.356 MW, (1000 and<br />

4500 horsepower) with a steam demand of between 6.17 to 23.18 kg/s (49,000<br />

and 184,000 lbs/h). System steam and pumped w<strong>at</strong>er flows <strong>at</strong> oper<strong>at</strong>ing con<br />

ditions are given in tabular form on Fig. 6.4.1 of the <strong>Browns</strong> <strong>Ferry</strong> FSAR.<br />

*The two normally-open primary containment isol<strong>at</strong>ion valves in the<br />

steam supply line will not reopen, if closed.


221<br />

E.5 Turbine Trips<br />

On an HPCI turbine trip, the turbine stop valve closes and the mini<br />

mum flow bypass valve to the pressure suppression pool closes to preclude<br />

drainage from the condens<strong>at</strong>e storage header into the suppression pool.<br />

The following conditions will cause turbine trip:<br />

1. High reactor vessel w<strong>at</strong>er level [14.78 m (582 in.) above vessel zero].<br />

2. High HPCI turbine exhaust pressure [1.14 MPa (150 psig)].<br />

3. Low HPCI booster pump suction pressure [—0.381 m (—15 in.) Hg].<br />

4. HPCI turbine mechanical overspeed (5000 rpm).<br />

5. Any HPCI isol<strong>at</strong>ion signal.<br />

6. Remote manual trip from Control Room.<br />

7. Manual trip lever on the HPCI turbine.<br />

All turbine trips except high reactor w<strong>at</strong>er level and HPCI isol<strong>at</strong>ion will<br />

reset autom<strong>at</strong>ically when the initi<strong>at</strong>ing condition clears. The high reac<br />

tor w<strong>at</strong>er level signal can be reset manually, or will reset autom<strong>at</strong>ically<br />

when the reactor w<strong>at</strong>er level decreases to the low reactor w<strong>at</strong>er level HPCI<br />

initi<strong>at</strong>ion point, 12.09 m (476 in.) above vessel zero. The HPCI isol<strong>at</strong>ion<br />

signal must be manually reset.<br />

E.6 System Isol<strong>at</strong>ion<br />

The Primary Containment and Reactor Vessel Isol<strong>at</strong>ion Control System<br />

initi<strong>at</strong>es autom<strong>at</strong>ic isol<strong>at</strong>ion of appropri<strong>at</strong>e pipelines which penetr<strong>at</strong>e the<br />

primary containment whenever certain monitored variables exceed their pre<br />

selected oper<strong>at</strong>ional limits. The system is designed so th<strong>at</strong>, once initi<br />

<strong>at</strong>ed, autom<strong>at</strong>ic isol<strong>at</strong>ion continues to completion. Return to normal oper<br />

<strong>at</strong>ion after isol<strong>at</strong>ion requires deliber<strong>at</strong>e oper<strong>at</strong>or action.<br />

An autom<strong>at</strong>ic isol<strong>at</strong>ion signal for the HPCI System causes the inboard<br />

and outboard HPCI steam line isol<strong>at</strong>ion valves to close, trips the HPCI<br />

turbine, and closes the two motor-oper<strong>at</strong>ed valves in the suction line from<br />

the pressure suppression pool. The inboard steam line isol<strong>at</strong>ion valve is<br />

AC-motor-oper<strong>at</strong>ed, the outboard DC-motor-oper<strong>at</strong>ed. The maximum closing<br />

time for these valves is 20 s.<br />

The following conditions cause a HPCI System isol<strong>at</strong>ion signal:52<br />

1. HPCI System equipment space high temper<strong>at</strong>ure. Since high temper<strong>at</strong>ure<br />

in the vicinity of the steam supply line or other HPCI equipment could<br />

indic<strong>at</strong>e a break in the turbine steam supply line, an isol<strong>at</strong>ion signal<br />

is gener<strong>at</strong>ed if this temper<strong>at</strong>ure exceeds 93.3°C (200°F). This temper<br />

<strong>at</strong>ure is sensed by four sets of four bimetallic temper<strong>at</strong>ure switches.<br />

These 16 temper<strong>at</strong>ure switches are arranged in four trip systems with<br />

four temper<strong>at</strong>ure switches in each trip system. The four temper<strong>at</strong>ure<br />

switches in each trip system are arranged in one-out-of-two taken<br />

twice logic.<br />

2. HPCI turbine high steam flow. Since high steam flow could indic<strong>at</strong>e a<br />

break in the turbine steam supply line, an isol<strong>at</strong>ion signal is gener<br />

<strong>at</strong>ed if the measured steam flow exceeds 150% of design maximum steady<br />

st<strong>at</strong>e flow. The steam line flow is sensed by two differential pres<br />

sure switches which monitor the differential pressure across a mechan<br />

ical element installed in the HPCI turbine steam pipeline. The trip<br />

ping of either switch <strong>at</strong> a differential pressure of 0.62 MPa (90 psi)<br />

initi<strong>at</strong>es HPCI System isol<strong>at</strong>ion.


222<br />

3. Low reactor pressure. After steam pressure has decreased to such a<br />

low value th<strong>at</strong> the HPCI turbine cannot be oper<strong>at</strong>ed, the steam line is<br />

isol<strong>at</strong>ed so th<strong>at</strong> steam and radioactive gases will not escape from the<br />

HPCI turbine shaft seals into the reactor building. The steam pres<br />

sure is sensed by four pressure switches from the HPCI turbine steam<br />

line upstream of the isol<strong>at</strong>ion valves. The switches are arranged in a<br />

one-out-of-two taken twice logic. The set point for this isol<strong>at</strong>ion<br />

signal is 0.793 MPa (100 psig).<br />

4. High turbine exhaust diaphragm pressure. A line tapping off the tur<br />

bine exhaust line contains two rupture diaphrams in series, with the<br />

space between vented to the HPCI equipment space through a flow re<br />

stricting orifice. The diaphrams are designed for 1.138 MPa (150<br />

psig). If the pressure in the space between the diaphrams exceeds<br />

0.172 MPa (10 psig), a system isol<strong>at</strong>ion signal is gener<strong>at</strong>ed.<br />

5. Manual Isol<strong>at</strong>ion. If a HPCI initi<strong>at</strong>ion signal is present, the opera<br />

tor can cause HPCI system isol<strong>at</strong>ion by pushing a control panel push<br />

button.<br />

The low reactor pressure isol<strong>at</strong>ion will be autom<strong>at</strong>ically reset if re<br />

actor pressure is restored; all other isol<strong>at</strong>ion signals seal in and the<br />

oper<strong>at</strong>or must push the HPCI auto isol<strong>at</strong>ion circuit reset push-button after<br />

the condition has cleared.<br />

E.7 Technical Specific<strong>at</strong>ions<br />

1. The HPCI System shall be operable<br />

a. Prior to startup from cold condition<br />

b. Whenever there is irradi<strong>at</strong>ed fuel in the reactor vessel and the<br />

reactor vessel pressure is gre<strong>at</strong>er than 0.945 MPa (122 psig), ex<br />

cept<br />

c. If the HPCI System is inoperable the reactor may remain in opera<br />

tion for a period not to exceed 7 days provided ADS, core spray,<br />

LPCI mode of RHR and RCIC are all operable.<br />

If these conditions are not met, an orderly shutdown shall be initi<br />

<strong>at</strong>ed and the reactor vessel pressure reduced to 0.945 MPa (122 psig)<br />

or less within 24 hours.<br />

2. HPCI testing shall be performed as follows:<br />

a. Simul<strong>at</strong>ed autom<strong>at</strong>ic actu<strong>at</strong>ion test — once per oper<strong>at</strong>ing cycle<br />

b. Pump operability — once per month<br />

c. Motor oper<strong>at</strong>ed valve operability — once per month<br />

d. Flow r<strong>at</strong>e <strong>at</strong> normal reactor oper<strong>at</strong>ing pressure — once per<br />

three months<br />

e. Flow r<strong>at</strong>e <strong>at</strong> 1.138 MPa (150 psig) — once per oper<strong>at</strong>ing cycle<br />

3. Whenever HPCI is required to be operable the piping from the pump dis<br />

charge to the last flow blocking valve shall be filled. W<strong>at</strong>er flow<br />

from the high point vent must be observed monthly. (Purpose is to<br />

prevent w<strong>at</strong>er hammer when the system is started.)


223<br />

APPENDIX F<br />

A COMPENDIUM OF INFORMATION CONCERNING THE BROWNS FERRY<br />

UNIT 1 REACTOR CORE ISOLATION COOLING SYSTEM<br />

F.1 Purpose<br />

The Reactor Core Isol<strong>at</strong>ion Cooling (RCIC) System is designed to en<br />

sure th<strong>at</strong> the core is not uncovered in the event of loss of all AC power.<br />

The RCIC System provides w<strong>at</strong>er to make up for th<strong>at</strong> lost through steam gen<br />

er<strong>at</strong>ed by decay he<strong>at</strong> during reactor isol<strong>at</strong>ion.53 RCIC is a consequence<br />

limiting system r<strong>at</strong>her than an ECCS System; the system design is not pred<br />

ic<strong>at</strong>ed on any loss of structure accident.51*<br />

F.2 System Description<br />

The RCIC System (Fig. F-l) consists of a steam-turbine driven pump<br />

unit and the associ<strong>at</strong>ed piping and valves. The RCIC pump can take suction<br />

from either the condens<strong>at</strong>e storage tank or the pressure suppression pool<br />

and discharges to the reactor vessel feedw<strong>at</strong>er line "B" via a thermal<br />

sleeve connection. A full flow system test line permits testing of the<br />

RCIC System while the reactor is <strong>at</strong> power, with the pump discharge routed<br />

to the condens<strong>at</strong>e storage tank. A minimum flow line connects the RCIC<br />

pump discharge to the pressure suppression pool, as a means of ensuring a<br />

flow of <strong>at</strong> least 0.004 m3/s (60 GPM) through the pump. The minimum flow<br />

bypass valve closes <strong>at</strong> a system flow of gre<strong>at</strong>er than 0.008 m3/s (120<br />

GPM). The normal setpoint for RCIC pumped flow is 0.038 m3/s (600 GPM).<br />

The RCIC turbine is driven by steam extracted from main steam line<br />

"C" upstream of the main steam line isol<strong>at</strong>ion valve. The two primary con<br />

tainment isol<strong>at</strong>ion valves in the steam line to the RCIC turbine are nor<br />

mally open to keep the piping to the turbine <strong>at</strong> elev<strong>at</strong>ed temper<strong>at</strong>ures so<br />

as to permit rapid system startup (within 30 seconds of an initi<strong>at</strong>ion sig<br />

nal). The normally closed DC-motor-oper<strong>at</strong>ed steam supply valve just up<br />

stream of the RCIC turbine will open against full system pressure within<br />

15 seconds after receipt of a system initi<strong>at</strong>ion signal.<br />

The RCIC turbine exhaust steam is discharged to the pressure suppres<br />

sion pool. The turbine gland seals are drained to a barometric condenser,<br />

in which the steam is condensed by a w<strong>at</strong>er spray. The w<strong>at</strong>er spray is pro<br />

vided by a flow diverted from the RCIC pump discharge to pass through the<br />

turbine lube oil cooler and subsequently form the spray. The condens<strong>at</strong>e<br />

from the barometric condenser is pumped back to the RCIC pump suction. A<br />

vacuum pump removes the non-condensibles from the barometric condenser and<br />

inserts them into the pressure suppression pool.<br />

A vacuum breaker line (not shown on Fig. F-l) is installed between<br />

the torus airspace and the RCIC turbine exhaust line. Its purpose is to<br />

prevent pressure suppression pool w<strong>at</strong>er from being drawn up into the tur<br />

bine exhaust line when the remaining exhaust steam condenses after turbine<br />

oper<strong>at</strong>ion and shutdown.<br />

All components normally required for initi<strong>at</strong>ing oper<strong>at</strong>ion of the RCIC<br />

System are completely independent of AC power, plant service air, and ex<br />

ternal cooling w<strong>at</strong>er systems, requiring only DC power from a unit b<strong>at</strong>tery


224<br />

TO SUPPRESSION POOL


225<br />

normally open AC-motor-oper<strong>at</strong>ed RCIC inboard steam line isol<strong>at</strong>ion valve,<br />

which will remain open on loss of power.<br />

F.3 RCIC Pump Suction<br />

The RCIC pump can take suction either from the condens<strong>at</strong>e storage<br />

header through a single normally-open DC-motor-oper<strong>at</strong>ed valve or from the<br />

pressure suppression pool via the suppression pool ring header.<br />

Each <strong>Browns</strong> <strong>Ferry</strong> <strong>Unit</strong> is provided with a 1419.4 m3 (375,000 gal<br />

lon) condens<strong>at</strong>e storage tank, which provides a w<strong>at</strong>er head to the storage<br />

header for th<strong>at</strong> unit. The storage header, which taps into the bottom of<br />

the storage tank, feeds the suctions of the high-pressure ECCS Systems,<br />

specifically, the pumps for the HPCI and the RCIC systems. The core spray<br />

pumps and the RHR pumps can be fed from this source, but are not normally<br />

aligned to it. All other demand for condens<strong>at</strong>e storage tank w<strong>at</strong>er is fed<br />

via a standpipe within the tank; the standpipe height is such th<strong>at</strong> 511.0<br />

m3 (135,000 gallons) of w<strong>at</strong>er is reserved for the ECCS Systems.<br />

There is no provision for an autom<strong>at</strong>ic shifting of the RCIC pump suc<br />

tion from the condens<strong>at</strong>e storage header to the pressure suppression pool.<br />

However, if condens<strong>at</strong>e storage tank w<strong>at</strong>er is unavailable for any reason,<br />

the control room oper<strong>at</strong>or can shift the RCIC pump suction to the pressure<br />

suppression pool ring header. This is done by remote-manually opening the<br />

two DC-motor-oper<strong>at</strong>ed suction valves to the pool ring header; when these<br />

two valves are fully open, the suction valve to the condens<strong>at</strong>e storage<br />

header will autom<strong>at</strong>ically close.<br />

The minimum required net positive suction head (NPSH) for the RCIC<br />

System is 6.10 m (20 ft), which is readily available with suction taken<br />

from the condens<strong>at</strong>e storage tank. With suction from the pressure suppres<br />

sion pool, the required NPSH is available for suppression pool tempera<br />

tures up to 85.0°C (185°F) with no containment back pressure.<br />

F.4 System Initi<strong>at</strong>ion<br />

An autom<strong>at</strong>ic start of the RCIC System is initi<strong>at</strong>ed by low reactor<br />

vessel w<strong>at</strong>er level <strong>at</strong> 12.10 m (476.5 in.) above vessel zero. The single<br />

normally-closed valve in the steam supply line opens, and steam is ad<br />

mitted to the turbine. (The turbine stop valve and control valve are nor<br />

mally open when the RCIC System is in standby.) The barometric condenser<br />

vacuum pump starts, and the condens<strong>at</strong>e pump will act to autom<strong>at</strong>ically con<br />

trol the w<strong>at</strong>er level in the condenser. The RCIC turbine speed and pump<br />

flow are autom<strong>at</strong>ically maintained by the steam flow controller. Turbine<br />

lube oil is supplied by a shaft-driven oil pump. The single .normallyclosed<br />

valve in the pump discharge line to feedw<strong>at</strong>er header "B" autom<strong>at</strong>i<br />

cally opens, and the minimum flow bypass valve closes autom<strong>at</strong>ically when<br />

pump flow exceeds 0.008 m3/s (120 GPM).<br />

If the RCIC System is in an abnormal lineup when an initi<strong>at</strong>ion signal<br />

is received, the system will realign:<br />

a. If the normally open pump discharge valve is closed, it will open.<br />

b. If the normally open pump suction valve from the condens<strong>at</strong>e storage<br />

header Is closed, it will open provided <strong>at</strong> least one of the suppres<br />

sion pool suction valves is not fully open.


o<br />

ro<br />

On<br />

a rt rt 3 O to rt 00 00 ~>l O Ul -p- OJ ro P rt Hi rt O o rt O CT /-v 03 -c<br />

c<br />

/-v CD B Hi rt<br />

£5f H Oh o<br />

•<br />

O XT o O 3 1 P- p- ID 3d 3 p. H Hi P- ro TJ p. On TJ P 3"T] CO ^ o ID * H XT O ID C O O "S _,<br />

o CO i-l i-J On 3 r1<br />

M X) o O rt 00 o (D 3* c7p. f?<br />

%<br />

£<br />

W rH 3=<br />

frt p-<br />

i-H<br />

O o<br />

O- XT O B rt P M<br />

H $3 03 nOQ o S to M O- O rt O H P^ - 3 O ID 0 Pje h,<br />

a Gr o.<br />

o I-J M<br />

TJ ID Hi<br />

i-h fD pj o M P- XT o B •^ « 00 o to 0Q XT H- rt M • 3 XT rt 3 o> fD O p- XT TJ O p n ID rt<br />

3 ro XI CO l-l 03 rH<br />

rt :<br />

£ o 3d XT n XT to rt ID O to \-h B to S ID ID g rt p 3 CD cr ID O rt 3 G rt<br />

B<br />

3 to l-j o rt 03 ?3 03 rt XT n h- 03 3 p. pj "T P- P" 03 N-X 3 o XT H rt 3 p- 3 3-<br />

03<br />

t* i-J XT<br />

XT • o I-J o l-l rt CO rt to G O "» 3 rt i-J Hi P. ^H- 3 CD Oj 00 *• rt 11 CD rt ID *~\ O CD "3 O 11<br />

pJ i-( X3 fD < o 3 03 G rt 3 It O C ID<br />

f? 03 CO O n O O -~1 03 • O o ID CO P- XT < o rt rt 3 Hi Hi rt p- M 3<br />

.<br />

"-< O H rt to i-( 03 H- fD pJ 03 P- B G O o i-J H- X l-l rt ID o 3 ON TJ H p VJ 00 to p Hi . p rt rj M ID i-H O p<br />

rt XT O n OQ rH Cu I-1 O TJ l-l < < 3 n p- CD It 3 i-1 OTJ OJ O CD 3 n O tl O O 3 i-H M<br />

rt rr to 03 p. O B ro ID fD 3d TJ CO rr rt SB to O. O O rt rt CD rt ID M 3 00 XT i-H cT rt XT CD<br />

3 (D XT XT 3<br />

e t-1 I-1 B ^a Oj O. B fD B CD . rj P- O rH M 3- G O • rt O ID to P CO P- ID rt<br />

CD ry l-j CO • CD O >-^ on . . rt Oj C P- TJ s3 CD l—> rt . P P- TJ Hi 3 3 fD<br />

.<br />

"-< i-j o rt<br />

o h-J s~\ rt XT n O TJ TJ CO 3 to ID • 03 to ~J O O Hi CO CO ID P* CD P- TJ 3<br />

(/ 1<br />

to rt 3 P- < On g UI i-i n ID ID TJ o TJ p »* • Hi B OJ P- TJ TJ ID O P" 11<br />

~0 O i-j rH rt cr do 3 fD h3 00 H- o B CO rH rt TJ O O OJ CO 00 G ID 00 O ID ID Oj S IB P ID Hi<br />

XT e 03 pJ fD OQ l-l<br />

p. fu roTj rt 03 •xJ XT 03 3 "S oo rt rt ro rH rt SI ID ID TJ CO c<br />

03 3 rr fD rt CO 3 rt H- rt H 3 - ID ID XT on rH ID B Oj Oh O P- ID P CD M<br />

3 3 a o XT 0> TJ . •-s. H- rt i-H 3 3d M O ID •-J S S to n u>rt O CD to G G i-H<br />

p. p. XT


227<br />

F.6 System Isol<strong>at</strong>ion<br />

The Primary Containment and Reactor Vessel Isol<strong>at</strong>ion Control System<br />

initi<strong>at</strong>es autom<strong>at</strong>ic isol<strong>at</strong>ion of appropri<strong>at</strong>e pipelines which penetr<strong>at</strong>e the<br />

primary containment whenever certain monitored variables exceed their pre<br />

determined oper<strong>at</strong>ional limits. The system is designed so th<strong>at</strong> once initi<br />

<strong>at</strong>ed, autom<strong>at</strong>ic isol<strong>at</strong>ion goes to completion. Return to normal oper<strong>at</strong>ion<br />

after isol<strong>at</strong>ion requires deliber<strong>at</strong>e oper<strong>at</strong>or action.<br />

An autom<strong>at</strong>ic isol<strong>at</strong>ion for the RCIC System causes the normally-open<br />

inboard and outboard steam supply isol<strong>at</strong>ion valves to close, the turbine<br />

to trip, and the two RCIC suction valves from the pressure suppression<br />

pool to close (if they were open). The minimum flow bypass valve to the<br />

suppression pool is interlocked to close whenever the turbine is tripped.<br />

The following conditions cause a RCIC system isol<strong>at</strong>ion signal:<br />

!• RCIC System equipment space high temper<strong>at</strong>ure. Since high temper<strong>at</strong>ure<br />

in the vicinity of the RCIC equipment could indic<strong>at</strong>e a break in the<br />

turbine steam supply line, an isol<strong>at</strong>ion signal is gener<strong>at</strong>ed if this<br />

temper<strong>at</strong>ure exceeds 93.3°C (200°F). This setpoint is based on the<br />

calcul<strong>at</strong>ed AT with a 0.001 m3/s (15 GPM) steam leak in the space.<br />

There are 16 temper<strong>at</strong>ure sensors arranged in four trip logics with<br />

four sensors in each logic. The 16 sensors are physically arranged in<br />

four groups with four sensors in each group. <strong>One</strong> sensor in each group<br />

is in each of the four one-out-of-two taken twice trip logics.<br />

2. RCIC System high steam flow. Since high steam flow could indic<strong>at</strong>e a<br />

leak in the turbine steam supply line, an isol<strong>at</strong>ion signal is gener<br />

<strong>at</strong>ed if the measured steam flow exceeds 150% of design maximum steady<br />

st<strong>at</strong>e flow. The steamline flow is sensed by two differential pressure<br />

switches which monitor the differential pressure across an elbow in<br />

stalled in the RCIC turbine steam supply pipeline. The tripping of<br />

either trip channel <strong>at</strong> a differential pressure of 11.43 m (450 in.)<br />

H20 initi<strong>at</strong>es RCIC System isol<strong>at</strong>ion.<br />

3. Low reactor pressure. After steam pressure has decreased to such a low<br />

value th<strong>at</strong> the RCIC turbine cannot be oper<strong>at</strong>ed, and there is no cool<br />

ant spray to the barometric condenser, the steam line is isol<strong>at</strong>ed to<br />

protect against continuous gland seal leakage to the RCIC equipment<br />

space. The set point for this isol<strong>at</strong>ion signal is a reactor vessel<br />

pressure of 0.345 MPa (50 psig). The pressure is sensed by four pres<br />

sure switches <strong>at</strong> the RCIC turbine steam line upstream of the isol<strong>at</strong>ion<br />

valves. The switches are arranged in a one-out-of-two taken twice<br />

logic.<br />

4. High turbine exhaust diaphragm pressure. A line tapping off the tur<br />

bine exhaust line contains two rupture diaphrams in series, with the<br />

space between vented to the RCIC equipment space through a flow re<br />

stricting orifice. The diaphrams are designed for 1.138 MPa (150<br />

psig). If the pressure in the space between the diaphragms exceeds<br />

0.172 MPa (10 psig), a system isol<strong>at</strong>ion signal is gener<strong>at</strong>ed.<br />

5. Manual Isol<strong>at</strong>ion. If an RCIC initi<strong>at</strong>ion signal is present, the oper<br />

<strong>at</strong>or can cause RCIC System isol<strong>at</strong>ion by pushing a control panel push<br />

button.<br />

All isol<strong>at</strong>ion signals are sealed in and must be manually reset after<br />

the condition causing them has cleared. A control panel pushbutton is<br />

provided for this purpose.


228<br />

F.7 Technical Specific<strong>at</strong>ions<br />

1. The RCIC System must be operable prior to startup from a cold condi<br />

tion or whenever there is irradi<strong>at</strong>ed fuel in the reactor and the re<br />

actor vessel pressure is above 0.945 MPa (122 psig).<br />

If the RCIC System is inoperable, the reactor may remain in oper<strong>at</strong>ion<br />

for a period not to exceed seven days if the HPCI System is operable<br />

during such time.<br />

If these conditions are not met, an orderly shutdown of the reactor<br />

must be initi<strong>at</strong>ed and the reactor depressurized to less than 0.945 MPa<br />

(122 psig) within 24 hours.<br />

2. RCIC testing shall be performed as follows<br />

a. Simul<strong>at</strong>ed autom<strong>at</strong>ic actu<strong>at</strong>ion test — once per oper<strong>at</strong>ing cycle<br />

b. Pump operability — once per month<br />

c. Motor oper<strong>at</strong>ed valve operability — once per month<br />

d. Flow r<strong>at</strong>e <strong>at</strong> normal reactor oper<strong>at</strong>ing pressure — once per three<br />

months<br />

e. Flow r<strong>at</strong>e <strong>at</strong> 1.138 MPa (150 psig) — once per oper<strong>at</strong>ing cycle<br />

3. Whenever RCIC is required to be operable the piping from the pump dis<br />

charge to the last flow blocking valve shall be filled. W<strong>at</strong>er flow<br />

from the high point vent must be observed monthly. (Purpose is to<br />

prevent w<strong>at</strong>er hammer when the system is started.)


229<br />

APPENDIX G<br />

EFFECT OF TVA-ESTIMATED SEVEN HOUR BATTERY LIFE ON<br />

NORMAL RECOVERY CALCULATIONS<br />

Section 7, Computer Prediction of Thermal Hydraulic Parameters for<br />

Normal Recovery, is based on the assumption th<strong>at</strong> the 250 vdc unit b<strong>at</strong>ter<br />

ies will fail in four hours under the conditions of <strong>St<strong>at</strong>ion</strong> Blackout.<br />

After review of the draft results presented in Sect. 7, the Electrical En<br />

gineering Branch <strong>at</strong> TVA performed a b<strong>at</strong>tery capacity calcul<strong>at</strong>ion to deter<br />

mine how long the <strong>Browns</strong> <strong>Ferry</strong> 250 vdc b<strong>at</strong>teries would last under these<br />

conditions, and arrived <strong>at</strong> an estim<strong>at</strong>e of seven hours. This appendix ex<br />

amines the impact of the newly estim<strong>at</strong>ed seven hour b<strong>at</strong>tery failure time<br />

on the results and conclusions of Sect. 7.<br />

Two basic conclusions are presented in Sect. 7.<br />

1. If AC power is recovered any time in the first five hours, then<br />

a normal recovery will be possible if the 250 vdc b<strong>at</strong>teries have<br />

not failed.<br />

2. If the 250 vdc b<strong>at</strong>teries fail <strong>at</strong> four hours and the AC power<br />

remains unavailable then the time between b<strong>at</strong>tery failure and<br />

first uncovering of fuel will be <strong>at</strong> least three hours if the re<br />

actor has been previously depressurized as recommended by this<br />

report.<br />

If the unit b<strong>at</strong>teries were to last seven instead of four hours, there<br />

would be a slight lengthening of the time interval from b<strong>at</strong>tery failure to<br />

core uncovery due to the slightly lower decay he<strong>at</strong>. The most important<br />

question to be answered regarding the extension of the estim<strong>at</strong>ed b<strong>at</strong>tery<br />

failure time from four to seven hours is whether there is some other sys<br />

tem failure caused by the increased temper<strong>at</strong>ures and/or pressures during<br />

this period th<strong>at</strong> would complic<strong>at</strong>e or make impossible a normal recovery if<br />

AC power were restored.<br />

To answer this question calcul<strong>at</strong>ions similar to those shown in Figs.<br />

7.1 through 7.9 of Sect. 7 were performed. These new calcul<strong>at</strong>ions start<br />

<strong>at</strong> an initial point four hours after st<strong>at</strong>ion <strong>blackout</strong> and extend to seven<br />

hours. The b<strong>at</strong>teries are assumed to last throughout this period and oper<br />

<strong>at</strong>or actions are the same as detailed in Sect. 7.3.1, Normal Recovery-<br />

Assumptions.<br />

Due to the elev<strong>at</strong>ed pool temper<strong>at</strong>ures experienced during the period<br />

from four to seven hours, it has been necessary to modify the calcul<strong>at</strong>ion<br />

of the fraction of relief valve (SRV) discharge th<strong>at</strong> is quenched in the<br />

suppression pool. When the pool temper<strong>at</strong>ure is within its normal opera<br />

tional range, the SRV discharge is completely condensed (quenched) in the<br />

cool w<strong>at</strong>er surrounding the submerged SRV discharge nozzle (T-quencher).<br />

However, if the temper<strong>at</strong>ure of the w<strong>at</strong>er around the T-quencher is suffi<br />

ciently close to s<strong>at</strong>ur<strong>at</strong>ion, then the condens<strong>at</strong>ion will be less than 100%<br />

and some of the steam will reach the suppression pool <strong>at</strong>mosphere. Monti<br />

cello tests58 showed th<strong>at</strong> an approxim<strong>at</strong>ely 28°C (50°F) difference be<br />

tween bulk and local pool temper<strong>at</strong>ure can exist during extended discharge<br />

through a single SRV. In this case, one would expect less than 100%<br />

quenching to begin <strong>at</strong> a bulk pool temper<strong>at</strong>ure of about 74°C (165°F), cor<br />

responding to 100°C (212°F) near the SRV discharge point (provided the


230<br />

pool is <strong>at</strong> <strong>at</strong>mospheric pressure). For the purposes of the calcul<strong>at</strong>ions<br />

reported in this appendix, the following provisions were made for the cal<br />

cul<strong>at</strong>ion of quench fraction in the pool:<br />

1. The temper<strong>at</strong>ure of the w<strong>at</strong>er surrounding the T-quencher during<br />

SRV discharge is assumed to be 28°C (50°F) higher than the bulk<br />

pool temper<strong>at</strong>ure.<br />

2. If the vapor pressure of the w<strong>at</strong>er surrounding the T-quencher is<br />

equal to or gre<strong>at</strong>er than the st<strong>at</strong>ic pressure then 0% of the SRV<br />

discharge is quenched; if the vapor pressure is 5.0 psi or more<br />

below the st<strong>at</strong>ic pressure then 100% of the discharge is<br />

quenched. Vari<strong>at</strong>ion of quench fraction is linear between these<br />

two points.<br />

This should provide a reasonable upper limit estim<strong>at</strong>e of containment pressuriz<strong>at</strong>ion<br />

due to non-quenched SRV discharge. Consider<strong>at</strong>ion of this ef<br />

fect was not necessary for the zero to five hour results reported in Sect.<br />

7 because bulk pool temper<strong>at</strong>ure does not exceed 82°C (180°F) during the<br />

first five hours of a <strong>St<strong>at</strong>ion</strong> Blackout.<br />

Results of the four to seven hours after <strong>blackout</strong> calcul<strong>at</strong>ions are<br />

shown in Figs. G.1 through G.9. From these results it is concluded th<strong>at</strong><br />

system parameters remain within acceptable ranges during this period:<br />

1. The 250 vdc b<strong>at</strong>teries by TVA estim<strong>at</strong>e last the full seven hours.<br />

2. Reactor vessel level is within the normal control range, about<br />

5.08 m (200 in.) above the top of active fuel.<br />

3. Reactor vessel pressure is being controlled by oper<strong>at</strong>or action<br />

<strong>at</strong> about 0.69 MPa (100 psia).<br />

4. At the seven-hour point, about 414 m3 (109,265 gal) of w<strong>at</strong>er<br />

have been pumped from the condens<strong>at</strong>e storage tank, which had an<br />

assured capacity of 511 m3 (135,000 gal) before the <strong>blackout</strong>.<br />

5. At the seven-hour point, average suppression pool temper<strong>at</strong>ure is<br />

about 92°C (198.2°F), but this should not be a problem for the<br />

T-quencher type of SRV discharge header piping.<br />

6. Containment pressures would be elev<strong>at</strong>ed to about 0.23 MPa (33<br />

psia), well below the 0.53 MPa (76.5 psia) design pressure.<br />

7. Drywell <strong>at</strong>mosphere temper<strong>at</strong>ure is about equal to the 138°C<br />

(281°F) design temper<strong>at</strong>ure.<br />

These results show th<strong>at</strong> if power were recovered within seven hours of<br />

the <strong>St<strong>at</strong>ion</strong> Blackout a normal recovery would be possible.* The 92°C<br />

(198°F) bulk pool temper<strong>at</strong>ure after seven hours may cause elev<strong>at</strong>ed air<br />

temper<strong>at</strong>ure in the RCIC and HPCI spaces, but this would not be expected to<br />

lead to failure of the HPCI or RCIC, because the lube oil of both units is<br />

cooled by the w<strong>at</strong>er being pumped — in this case, w<strong>at</strong>er from the conden<br />

s<strong>at</strong>e storage tank which would not exceed 32°C (90°F). The periods of RCIC<br />

oper<strong>at</strong>ion are very infrequent after the first four hours of <strong>St<strong>at</strong>ion</strong> Black<br />

out, with about an hour between actu<strong>at</strong>ions.<br />

The supply of control air for remote-manual oper<strong>at</strong>ion of the SRVs is<br />

sufficient for the full seven hours. As discussed in Chap. 3 of this re<br />

port, the accumul<strong>at</strong>ors provided for the six relief valves associ<strong>at</strong>ed with<br />

the ADS system are sized to permit five oper<strong>at</strong>ions or a total of 30 actua<br />

tions. As illustr<strong>at</strong>ed in Sect. 7 and this appendix, less than 30 actua<br />

tions are required during the first seven hours of the <strong>St<strong>at</strong>ion</strong> Blackout.<br />

*With the assumption of no independent secondary equipment failures.


a.<br />

2<br />

cr<br />

co n<br />

CO<br />

UJ<br />

oc<br />

a.<br />

<<br />

ui<br />

rco<br />

o<br />

o<br />

— 0<br />

o<br />

01<br />

0<br />

00<br />

UJ<br />

cr 8<br />

3 10<br />

co<br />

CO<br />

UJ<br />

OC 0<br />

in<br />

5<br />

<<br />

1— Sh<br />

co £<br />

0<br />

m<br />

a<br />

CN]<br />

0-<br />

1<br />

REACTOR PRESSURE CONTROLLED BY OPERATOR BETWEEN 90 AND 11! 5 psia<br />

I<br />

SRVSrHUT SRV OPENED SRV SHUT SRV OPENED<br />

i^- 1 ^<br />

"<br />

t Tn<br />

RCIC ON RCIC OFF RCIC ON RCIC OFF<br />

1 1<br />

240 270 300 330<br />

TIME (min)<br />

360 390<br />

Fig. G.l Reactor vessel pressure - four to seven hours after<br />

st<strong>at</strong>ion <strong>blackout</strong>.<br />

|<br />

"'<br />

ORNL-DWG 81-8593 ETD<br />

420<br />

ro<br />

OJ


-* o i =<br />

3<br />

O<br />

3i2<br />

<<br />

UJ<br />

8<br />

<br />

84<br />

i—RCIC TURBINE STEAM FLOW<br />

•NO STEAM FLOW FROM REACTOR VESSEL<br />

-1 SRV OPEN- 1 SRV OPEN-<br />

O-l o-<br />

-1-<br />

I<br />

240 270 300<br />

330<br />

360 390<br />

<strong>blackout</strong>.<br />

TIME (min)<br />

Fig. G.2 Vessel steam flow - four to seven hours after st<strong>at</strong>ion<br />

ORNL-DWG 81-8594 ETD<br />

420<br />

ro<br />

OJ<br />

ro


t—<br />

> 2-<br />

UJ<br />

8 2-<br />

UJ<br />

><br />

CO<br />

CO<br />

UJ<br />

> o in<br />

o<br />

ORNL-DWG 81-8595 ETD<br />

TOP OF CONTROL ROOM INDICATION -OVERSHOOT DUE TO HEATUP OF SUBCOOLED<br />

WATER AFTER RCIC TURNED OFF<br />

BOTTOM OF CONTROL ROOM INDICATION<br />

to I<br />

240 270<br />

<strong>blackout</strong>.<br />

Fig. G.3<br />

OPERATOR CONTROLS LEVEL BY REMOTE-MANUAL<br />

ACTUATION OF RCIC SYSTEM<br />

300 330<br />

TIME (min)<br />

360 390<br />

Vessel level - four to seven hours after st<strong>at</strong>ion<br />

TOP OF ACTIVE FUEL<br />

420<br />

ro<br />

OJ<br />

U3


ID.<br />

CM<br />

-IS oj<br />

O (M. O<br />

_ CM<br />

»- OI<br />

s c<br />

LL<br />

O oj<br />

UJ —"<br />

UJ --<br />

<strong>blackout</strong>.<br />

Fig. G.4<br />

330<br />

TIME (min)<br />

Injected flow - four to seven hours after st<strong>at</strong>ion<br />

ORNL-DWG 81-8596 ETD<br />

420<br />

N3<br />

OJ


VOLUME(20000<br />

VOLUME D3501•._!_<br />

300<br />

INJECTED TOTAL 60000 40000<br />

TOTAL 200i<br />

150 120(14<br />

100000 800i1<br />

00<br />

o<br />

o<br />

o<br />

in-i<br />

«j<br />

gal)<br />

o-<br />

/<br />

/i\<br />

a<br />

(m3) INJECTE 250 100<br />

m<br />

o-" o-<br />

t<br />

LRCIC ON<br />

/i<br />

— RCIC OFF<br />

40 2 70 3 00 3 30<br />

TIME<br />

: (min)<br />

L- RCIC ON<br />

-RCIC OFF<br />

ORNL-DWG 81-8597 ETD<br />

360 390 42<br />

Fig. G.5 Total injected flow (pumped by RCIC from condens<strong>at</strong>e<br />

storage tank) - four to seven hours after st<strong>at</strong>ion <strong>blackout</strong>.<br />

y<br />

NJ<br />

OJ<br />

On


E<br />

"»•«* -~*<br />

o .£ n<br />

^<br />

X<br />

-J<br />

UJ<br />

_l ><br />

UJ UJ<br />

> CM-I _l<br />

UJ<br />

_l<br />

_l<br />

o<br />

-J<br />

O ?»<br />

O<br />

a.<br />

Z<br />

z<br />

o<br />

o -J to<br />

CO<br />

3<br />

UJ<br />

rr<br />

UJ<br />

rr<br />

0-<br />

a.<br />

a.<br />


O<br />

o_<br />

CO<br />

UJ<br />

cr<br />

r-<br />

<<br />

CC<br />

UJ<br />

a.<br />

m<br />

5<br />

< g-<br />

I ^<br />

O<br />

UJ<br />

rr<br />

a.<br />

a.<br />

CO o.<br />

in<br />

m<br />

5<br />

<<br />

X<br />

z 2<br />

o<br />

co<br />

CO<br />

UJ<br />

Is<br />

D<br />

CO<br />

240<br />

RAPID INCREASE DUE TO DIRECT<br />

MIXING WITH UNQUENCHED<br />

STEAM FROM SRV DISCHARGE<br />

LESS THAN 100%, QUENCHING—J<br />

OF SRV DISCHARGE BEGINS<br />

270 300 330<br />

TIME (min)<br />

ORNL-DWG 81-8599 ETD<br />

SUPPRESSION CHAMBER<br />

ATMOSPHERE<br />

CONDENSATION AND HEAT TRANSFER<br />

FROM ATMOSPHERE ARE DOMINANT<br />

WHEN SRV NOT DISCHARGING<br />

360 390 420<br />

Fig. G.7 Suppression chamber temper<strong>at</strong>ures - four to seven hours<br />

after st<strong>at</strong>ion <strong>blackout</strong>.<br />

ro<br />

OJ


O<br />

o_<br />

UJ<br />

cc<br />

< ~<br />

rr<br />

UJ<br />

a.<br />

5<br />

UJ<br />

o<br />

0-|<br />

OJ<br />

UJ<br />

cc<br />

UJ<br />

I<br />

a.<br />

co<br />

O<br />

H °<br />

5 2-<br />

UJ<br />

> rr<br />

a<br />

UJ<br />

rr<br />

D<br />

I-<br />

<<br />

cr<br />

UJ<br />

a.<br />

UJ<br />

X<br />

a.<br />

co<br />

O<br />

IS<br />

>tr<br />

Q<br />

»<<br />

o<br />

ro<br />

a<br />

oto<br />

o<br />

Ol<br />

o<br />

Ol<br />

o<br />

•-.<br />

o<br />

DRYWELL ATMOSPHERE TEMPERATURE —<br />

INCREASES GRADUALLY TOWARD<br />

REACTOR COOLANT TEMPERATURE SEE FIG. G.1)<br />

""^<br />

240 270 300 330<br />

TIME (min)<br />

<strong>blackout</strong>.<br />

DRYWELL DESIGN TEMPERATURE<br />

ft 1<br />

jL_<br />

ORNL-DWG 81-8600 ETD<br />

H^ -TEMPORARY DECREASE DUE TO DECREASE IN<br />

REACTOR COOLANT TEMPERATURE (CAUSED<br />

BY DECREASE IN REACTOR PRESSURE -<br />

360 390<br />

Fig. G.8 Drywell temper<strong>at</strong>ures - four to seven hours after st<strong>at</strong>ion<br />

420<br />

ro<br />

OJ<br />

OO


(T CM.<br />

§<br />

x<br />

CO<br />

UJ<br />

cc<br />

D<br />

UJ ts.<br />

tr -<br />

Ol<br />

H<br />

Z<br />

UJ<br />

2<br />

z<br />

o<br />

Z °<br />

o<br />

"—DRYWELL<br />

SUPPRESSION CHAMBER PRESSURE GOES<br />

DOWN BECAUSE OF CONDENSATION<br />

AND HEAT TRANSFER (SEE FIG. G.7)-<br />

240 270 300 330<br />

MORE RAPID PRESSURE BUILDUP BEGINS<br />

WHEN LESS THAN 100% OF QUENCHING<br />

OF SRV DISCHARGE BEGINS<br />

TIME (min)<br />

ORNL-DWG 81-8601 ETD<br />

360 390 420<br />

Fig. G.9 Containment pressures - four to seven hours after<br />

st<strong>at</strong>ion <strong>blackout</strong>.<br />

rO<br />

OJ<br />

VO


1. W. J. Armento<br />

2. T. E. Cole<br />

3. W. A. Condon<br />

4. D. H. Cook<br />

5. W. B. Cottrell<br />

6. W. G. Craddick<br />

7. G. F. Flanagan<br />

8. S. R. Greene<br />

9. R. M. Harrington<br />

10-14. S. A. Hodge<br />

15. T. S. Kress<br />

16. R. A. Lorenz<br />

241<br />

Internal Distribution<br />

NUREG/CR-2182, Vol. I<br />

ORNL/NUREG/TM-455/VI<br />

Dist. C<strong>at</strong>egory RX, IS<br />

17. A. L. Lotts<br />

18. T. W. Robinson, Jr.<br />

19. H. E. Trammell<br />

20. B. J. Veazie<br />

21. C. F. Weber<br />

22. R. P. Wichner<br />

23. D. D. Yue<br />

24. P<strong>at</strong>ent Office<br />

25. Central Research Library<br />

26. Document Reference Section<br />

27-28. Labor<strong>at</strong>ory Records Department<br />

29. Labor<strong>at</strong>ory Records (RC)<br />

External Distribution<br />

30-31. Director, Division of Accident Evalu<strong>at</strong>ion, Nuclear Regul<strong>at</strong>ory<br />

Commission, Washington, DC 20555<br />

32-33. Chief, Severe Accident Assessment Branch, Nuclear Regul<strong>at</strong>ory Com<br />

mission, Washington, DC 20555<br />

34. Director, Reactor Division, DOE, 0R0, <strong>Oak</strong> <strong>Ridge</strong>, TN 37830<br />

35. Office of Assistant Manager for Energy Research and Development,<br />

DOE, 0R0, <strong>Oak</strong> <strong>Ridge</strong>, TN 37830<br />

36-40. Director, Reactor Safety Research Coordin<strong>at</strong>ion Office, DOE,<br />

Washington, DC 20555<br />

41-42. D. B. Simpson, Tennessee Valley Authority, W10C126 C-K, 400 Com<br />

merce Avenue, Knoxville, TN 37902<br />

43-44. Wang Lau, Tennessee Valley Authority, W10C126 C-K, 400 Commerce<br />

Avenue, Knoxville, TN 37902<br />

45-46. R. F. Christie, Tennessee Valley Authority, W10C125 C-K, 400 Com<br />

merce Avenue, Knoxville, TN 37902<br />

47-48. J. A. Raulston, Tennessee Valley Authority, W10C126 C-K, 400 Com<br />

merce Avenue, Knoxville, TN 37902<br />

49-50. H. L. Jones, Tennessee Valley Authority, 253 HBB-K, 400 Commerce<br />

Avenue, Knoxville, TN 37902<br />

51-52. Technical Inform<strong>at</strong>ion Center, DOE, <strong>Oak</strong> <strong>Ridge</strong>, TN 37830<br />