general & performance data<br />

General Data - W (45 - 80)<br />

Model W45 & W45P W60 & W60P W80 & W80P<br />

Flow connection BSP R1 1 ⁄4”<br />

Return connection BSP R1 1 ⁄4”<br />

Maximum static water head<br />

Maximum pressure<br />

Performance Data - W (45 - 80)<br />

Model W45 W45P W60 W60P W80 W80P<br />

Boiler output (<strong>condensing</strong>)<br />

max<br />

kW<br />

Btu/h<br />

46.9<br />

160,000<br />

45.9<br />

156,000<br />

62.3<br />

212,560<br />

60.6<br />

206,750<br />

82.7<br />

282,170<br />

80.0<br />

272,950<br />

50/30˚C<br />

min<br />

kW<br />

Btu/h<br />

13.9<br />

47,600<br />

13.7<br />

46,600<br />

13.9<br />

47,600<br />

13.6<br />

46,400<br />

21.3<br />

72,700<br />

20.7<br />

70,600<br />

Boiler output (non-<strong>condensing</strong>)<br />

max<br />

kW<br />

Btu/h<br />

43.7<br />

149,000<br />

58.9<br />

200,960<br />

78.2<br />

266,800<br />

80/60˚C<br />

min<br />

kW<br />

Btu/h<br />

12.6<br />

43,000<br />

12.6<br />

43,000<br />

19.5<br />

66,500<br />

Boiler input (Nett)<br />

Boiler input (Gross)<br />

max<br />

min<br />

max<br />

min<br />

Gas rate Natural Gas<br />

Gas rate Propane<br />

m 40.79<br />

ft 133.83<br />

Bar 4.0<br />

psi 58<br />

Gas inlet connection mm 22<br />

Pressure required at the boiler inlet mbar 17.5<br />

for the rated input (Natural Gas) in. w.g. 7.0<br />

Electricity supply 230V 50Hz<br />

Nominal flue size / concentric mm 80 / 125 80 / 125 100 / 150<br />

Nominal flue size / twin pipe mm 80 / 80 80 / 80 100 / 100<br />

Condensate drain mm 25<br />

NOx emissions<br />

Water content<br />

mg / kW / hr 45 55 60<br />

ppm (0% O 2 ) 26 31 34<br />

l 8 8 10<br />

gal 1.76 1.76 2.20<br />

Weight<br />

kg<br />

lb<br />

87<br />

191<br />

88<br />

194<br />

101<br />

222<br />

Power consumption W 51 84 120<br />

kW 45 60 80<br />

Btu/h 153,540 204,720 272,960<br />

kW 13 13 20<br />

Btu/h 44,350 44,350 68,240<br />

kW 49.9 48.9 66.5 65.1 88.7 86.9<br />

Btu/h 170,250 166,850 227,000 222,300 302,700 296,350<br />

kW 14.4 14.1 14.4 14.1 22.2 21.7<br />

Btu/h 49,150 48,150 49,150 48,150 75,650 74,100<br />

m 3 /h 4.76 6.35 8.46<br />

ft 3 /h 166 222 296<br />

m 3 /h 1.84 2.45 3.27<br />

ft 3 /h 65 86 115<br />

Approx flue gas volume<br />

Natural Gas<br />

m 3 (non <strong>condensing</strong>) max rate<br />

/s<br />

ft<br />

0.02 0.027 0.036<br />

3 /min 42.33 57.67 77<br />

Approx flue gas volume<br />

Propane<br />

m 3 (non <strong>condensing</strong>) max rate<br />

/s<br />

ft<br />

0.019 0.026 0.034<br />

3 /min 40 54.67 72.33<br />

Seasonal efficiency *(SEDBUK) % 90.4 91.3 90.4 92.1 90.2 91.6<br />

Note: Gas rates are calculated using a C.V. of 37.8 MJ/m 3 gross (34 MJ/m 3 nett) for Natural Gas or 95.7 MJ/m 3 for Propane.<br />

* The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings.<br />