22<br />
dimensional data<br />
W Boiler Dimensions<br />
W Boiler House Clearances<br />
The following minimum clearances must be maintained for operation and servicing:<br />
• Front of boiler - 450mm • Sides of boiler - 50mm<br />
• Above boiler - dependent upon the flue system • Below boiler - 300mm<br />
W Multiple Frame Kit<br />
A B C D E F G<br />
2 Boiler, Frame & Header Kit W45/60 1648 1130 403.5 372 460 DN50 PN6 32NB<br />
3 Boiler, Frame & Header Kit W45/60 2238 1720 403.5 372 460 DN50 PN6 32NB<br />
2 Boiler, Frame & Header Kit W80 1868 1350 395 372 460 DN50 PN6 32NB<br />