Overview<br />
32 Relays<br />
TRIATEK’s <strong>LP</strong>-<strong>25</strong>00 Series UL<br />
Listed, FCC approved Lighting<br />
Control Panel provides the capability<br />
to control high voltage lighting<br />
circuits via two wire RS-485 network<br />
maintained contact signals<br />
from an automation or control system,<br />
and momentary contacts from<br />
override switches.<br />
The <strong>LP</strong>-<strong>25</strong>00 Series Lighting<br />
Control Panel accepts up to 24<br />
site programmable switch inputs.<br />
These inputs can be either momentary<br />
or maintained. The unit provides<br />
the capability to assign any of<br />
its inputs to any of 60 zones via<br />
easy-to-use pushbuttons on the<br />
unit or from a laptop or PC. The<br />
high voltage latching contactors in<br />
the unit can be easily assigned to<br />
any of the units 60 zones through<br />
“soft-wiring”, eliminating all low<br />
voltage zone to relay wiring. These<br />
features provide the capability to<br />
easily and quickly group or re-group<br />
Lighting Control Products<br />
48 Relays<br />
60 Relays<br />
16 Relays<br />
the high voltage contactors or operate<br />
independently via a momentary<br />
override switch.<br />
MICROPROCESSOR-BASED<br />
DESIGN<br />
The heart of the system is a<br />
Microprocessor (CPU) module<br />
which provides hardware for up to<br />
24 inputs (120 with optional modules),<br />
pushbuttons for selecting features<br />
and changing parameters at<br />
the unit, bar chart style LEDs for<br />
displaying system parameters and<br />
to indicate status of each zone and<br />
relay, and connector for interfacing<br />
to each high voltage contactor.<br />
SERIAL COMMUNICATION<br />
An advanced option of the unit<br />
is it’s capability to be addressed via<br />
an optional two wire RS-485 serial<br />
communication network. This eliminates<br />
the need for dedicated outputs<br />
to drive each zone. TRIATEK<br />
can design a protocol converter to<br />
make the unit compatible with most<br />
systems<br />
LED DISPLAY<br />
This feature provides visual<br />
indication of zone and contactor<br />
status through the use of bar chart<br />
style LEDs on the unit’s CPU.<br />
SEAMLESS INTEGRATION:<br />
• Alerton Technologies / Ibex 3500<br />
• Andover Controls • Teletrol Systems<br />
• Automated Logic / SuperVision<br />
• Johnson Controls / Metasys<br />
• Landis & Staefa / System 600<br />
• Johnson Controls / Facilitator<br />
• Johnson Controls / Companion<br />
Others in Development<br />
Features &<br />
Benefits<br />
• UL Listed,CSA Certified, FCC<br />
Approved<br />
• 4 Panel Sizes, Up to 60 Relays<br />
• 24 Programmable Inputs per Unit<br />
• Serial Communication Option<br />
• Programmable Flash Warning<br />
• Programmable On-Time After<br />
Flash<br />
• 60 Programmable Zones per Unit<br />
• Manual Override Standard<br />
• Low Per Point Cost<br />
Applications<br />
• Energy Management<br />
• Building Automation<br />
• Low Voltage Switching<br />
• Lighting Control / Override<br />
Related Products<br />
• <strong>LP</strong>-<strong>25</strong>00-TIB/ <strong>LP</strong>-<strong>25</strong>00-EXP for<br />
adding 32 inputs.<br />
• TRIATEK’s TI-4000 Series<br />
Telephone Override System for<br />
override from any touch-tone telephone.<br />
• <strong>LP</strong>-RS485 for RS-485 communication.<br />
• <strong>LP</strong>-<strong>25</strong>00 / <strong>2600</strong> upgrade kit<br />
• TRIATEK’s Central Station<br />
Console for networking multiple<br />
<strong>LP</strong>-<strong>25</strong>00’s to a Central Computer.<br />
• RCS-1000 Programmable Circuit<br />
Breaker Panel for a complete<br />
factory assembled circuit breaker<br />
panel with remote control circuit<br />
breakers.<br />
2976 Pacific Drive, Norcross GA 30071 • phone 770-242-1922 fax 770-242-1944 • http://www.ttk.com<br />
C-5<br />
<strong>LP</strong>-<strong>25</strong>/<strong>2600</strong><br />
Lighting Control<br />
Panels<br />
Due to continuous product improvement, TRIATEK reserves the right to change product specifications without notice.<br />
<strong>LP</strong><strong>25</strong>00 - 2.0 -103096 C5
NETWORK DIAGRAM<br />
TI - 4500 Telephone Override System<br />
DESIGN FEATURES<br />
C6<br />
USER INTERFACE<br />
The unit provides four pushbuttons<br />
labeled “CH”, “TG”, “BK” and<br />
“MD”. These pushbuttons enable<br />
the user to select and set all of the<br />
unit’s features much like that of a<br />
keyboard, thus eliminating the<br />
need for special hand-held programmers<br />
or PCs for parameter<br />
set-up or modification. However<br />
Set-Up Software is available that<br />
runs on a lap top or PC.<br />
SECURITY SWITCH<br />
This is a software switch which<br />
prevents accidental override of the<br />
unit’s parameters.<br />
ZONE AND CONTACTOR<br />
ASSIGNMENT<br />
This software feature provides the<br />
capability to group any or all of the<br />
unit’s contactors to any zone. In a<br />
matter of seconds, contactors<br />
can be added or deleted from a<br />
zone. Due to this unique software<br />
feature no tools or electricians are<br />
required to hardware contactors<br />
to zones.<br />
Central Computer<br />
SWITCH INPUT TIME-OUT<br />
This software feature provides the<br />
capability to have any of the lights<br />
associated with a momentary<br />
switch turn OFF after a programmable<br />
amount of time has elapsed.<br />
ZONE PRIORITY<br />
This software feature provides the<br />
capability to set-up priorities for<br />
each of the zones because multiple<br />
inputs can be assigned to the<br />
same zone so an order of priority<br />
may need to be established.<br />
FLASH MODE<br />
This software feature provides the<br />
capability to flash the lights<br />
(latch/unlatch) associated with an<br />
input. The purpose of this feature<br />
is to warn people so that they will<br />
exit the area or override the lights<br />
before the unit automatically turns<br />
the lights off.<br />
ON-TIME AFTER FLASH<br />
WARNING<br />
This software feature provides the<br />
capability to set the length of time<br />
the lights will be on after the lights<br />
have been flashed.<br />
BAS<br />
Digital Inputs<br />
Multiple <strong>LP</strong>-<strong>25</strong>00’s on 2 wire RS485 network<br />
FLASH WARNING TIME<br />
This software feature provides the<br />
capability to set the length of the<br />
flash off time during the Flash<br />
Warning.<br />
CONTACTOR (RELAY)<br />
ENERGIZE TIME<br />
This software feature provides the<br />
capability to set the length of time<br />
the contactor coil is energized by<br />
the unit.<br />
MAXIMUM CONTACTORS<br />
IN SYSTEM<br />
This feature provides the capability<br />
to set the maximum number of<br />
contactors in the unit which can<br />
be activated. For instance, a<br />
forty-eight contactor unit may only<br />
have twenty-two contactors<br />
installed. This feature will provide<br />
a way to set the maximum number<br />
of contactors in software to<br />
match the number of contactors<br />
installed in the unit. As contactors<br />
are added during expansion, then<br />
the maximum number in software<br />
can also be increased.<br />
AUTOMATIC OUTPUT<br />
SEQUENCING<br />
This software feature automatically<br />
sequences each output rather<br />
than energizing all relays in a<br />
group at once.<br />
MAXIMUM INPUTS<br />
IN SYSTEM<br />
This feature provides the capability<br />
to select the maximum number<br />
of inputs the unit will monitor. The<br />
unit is capable of one-hundredtwenty<br />
inputs so only the number<br />
of inputs in use need to be set up<br />
in software. The unit comes standard<br />
with twenty-four inputs.<br />
INPUT POLARITY<br />
This software feature provides the<br />
capability to set each input for<br />
either normally open or normally<br />
closed contacts.<br />
CHECKING INPUT STATUS<br />
This software feature provides the<br />
capability to display the status of<br />
each of the unit’s inputs.<br />
2976 Pacific Drive, Norcross GA 30071 • phone 770-242-1922 fax 770-242-1944 • http://www.ttk.com<br />
Due to continuous product improvement, TRIATEK reserves the right to change product specifications without notice.<br />
<strong>LP</strong><strong>25</strong>00 - 2.0 -103096
DESIGN FEATURES<br />
PROGRAMMABLE INPUT<br />
This software feature provides the<br />
flexibility to select zones controlled<br />
by input, type of input (maintained,<br />
momentary on, momentary off, 3level,<br />
momentary toggle contact,<br />
or linked switch for multi-level<br />
lighting control), timer associated<br />
with input, flash warning and polarity<br />
of input.<br />
LED TIME OUT<br />
This feature prolongs the LED life<br />
and reduces heat build-up in the<br />
unit by putting LEDs to “sleep”<br />
after 10 minutes of no pushbutton<br />
use. To “wake” up the LEDs, simply<br />
press any pushbutton.<br />
MANUAL OVERRIDE<br />
This feature provides the capability to<br />
manually override any of the unit’s<br />
thirty zones. This feature is ideal for<br />
the testing of the panel during instal-<br />
lation or if the device controlling the<br />
panel fails.<br />
EPROM AND EEPROM<br />
DIAGNOSTIC AND<br />
SOFTWARE VERSION<br />
This feature verifies integrity of<br />
the unit’s EPROM (Electrically<br />
Programmable-Read Only<br />
Memory) and EEPRO(Electrically<br />
Erasable Programmable Read<br />
Only Memory) and displays the unit’s<br />
software version number. If the unit<br />
detects any problem with its memory<br />
after power up it will indicate a problem<br />
exists by flashing a warning LED.<br />
This feature can be activated at any<br />
time so a technician can check the<br />
software version number or force an<br />
integrity verification on the EPROM<br />
and EEPROM.<br />
CONSTRUCTION MATERIALS<br />
The units enclosure is constructed of<br />
16 gauge steel (14 gauge for 60 relay<br />
<strong>LP</strong>-<strong>25</strong>00 Lighting<br />
Control Panels<br />
unit) coated with polyurethane<br />
enamel with textured hinged door<br />
and cylinder lock. Standoffs are provided<br />
for the factory mounted microprocessor<br />
module and relay interface<br />
board. The relay interface board connects<br />
each high voltage contactor to<br />
the microprocessor via ribbon<br />
cables. Each high voltage latching<br />
contactor is rated for 227V, 20 Amp<br />
(347V, 20 Amp for Canadian use). A<br />
barrier is provided for snap in mounting<br />
of the high voltage contactors and<br />
separation of the low voltage and<br />
high voltage wiring. A dual primary<br />
277/120 to 24VAC transformer is<br />
factory mounted in the unit and supplies<br />
all necessary power. A replaceable<br />
fuse is provided on the primary<br />
side of the transformer. A<br />
removable cover for the high voltage<br />
side of the enclosure is provided<br />
to protect against accidental<br />
shock from high voltage circuits. All<br />
<strong>LP</strong>-<strong>2600</strong> Lighting<br />
Control Panels<br />
assembly and testing of these<br />
components is completed at the<br />
factory prior to shipment. No<br />
assembly of the unit is required in<br />
the field other than typical installation<br />
of inputs, outputs and power.<br />
PRODUCT CERTIFICATION<br />
AND TESTING<br />
The unit is Listed by Underwriters<br />
Laboratories,Inc.(UL)and approved<br />
by FCC. In addition, our quality control<br />
technicians perform burn in testing<br />
of the unit. This test includes a<br />
minimum of a 24 hour period where<br />
all of the contactors in the unit are<br />
cycled continuously. After the burn<br />
period the unit is re-checked and<br />
any faulty components replaced.<br />
This minimizes product failures in the<br />
field and assures a higher quality<br />
product.<br />
2976 Pacific Drive, Norcross GA 30071 • phone 770-242-1922 fax 770-242-1944 • http://www.ttk.com<br />
Due to continuous product improvement, TRIATEK reserves the right to change product specifications without notice.<br />
<strong>LP</strong><strong>25</strong>00 - 2.0 -103096 C7
PANEL LAYOUT<br />
7<br />
9<br />
4<br />
8<br />
Specifications<br />
Electrical<br />
6 6<br />
5<br />
10<br />
Programmable inputs . . .24 standard, up to 120 (maintained or momentary)<br />
Output rating . . . . . . . . . . . . . . . . . . . .Lamp Load -20 amp Ballast 227VAC,<br />
(Tungsten 1<strong>25</strong> VAC)(UL Listed, CSA Cert)<br />
Resistive Load-20 amp 277 VAC<br />
Motor 1/2 Hp@110-1<strong>25</strong>VAC,1-1/2Hp@220-277VAC<br />
Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SPST maintained<br />
Output Terminals . . . . . . . . . . . .2 terminals, 2 back wiring holes for #14-10<br />
AWG solid or stranded wire, copper wire only<br />
Panel Power Supply . . . . . . . . . . . . . . . . . . . . . .115/277 VAC, 60Hz ± 10%<br />
Communications . . . . . . . . . . . . . . . . . . .Optional, two wire RS-485 module<br />
Ordering Instructions<br />
<strong>LP</strong>-<strong>2600</strong> Series <strong>LP</strong>-<strong>25</strong>00 Series<br />
3<br />
2<br />
1<br />
1= Power Supply and fuse, 2 = High Voltage Relays (<strong>LP</strong>-<strong>25</strong>00 = GE RR7) (<strong>LP</strong>-<strong>2600</strong> = GE RR9), 3 = High Voltage Section, 4 = CPU, 5 = 16 Relay Interface Board, 6<br />
= Low Voltage Section, 7 = Enclosure, 8 = Programmable Switch Inputs, 9 = Zone and Relay Status LEDs, 10 = High Voltage Barrier. Hinged Door and High Voltage<br />
Section Door not shown.<br />
<strong>LP</strong>-2 ❑❑❑ - ❑❑ - ❑<br />
9<br />
7<br />
4<br />
8<br />
Environmental<br />
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32˚ to 1<strong>25</strong>˚F<br />
Operating humidity . . . . . . . . . . . . . . . . . .20% - 95% RH, Non-condensing<br />
Certification<br />
Underwriters Laboratories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UL 916<br />
Canadian Standards Association . . . . . . . . . . . . . . . . . . . . . . . . .C 22.2-205<br />
Mechanical<br />
5<br />
16 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14" W x 17.5" H x 5" D<br />
32 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14" W x 30.5" H x 5" D<br />
48 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14" W x 43.0" H x 5" D<br />
60 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14" W x 54.0" H x 5" D<br />
RELAY TYPE RELAYS EQUIPPED IN PANEL* PANEL CAPACITY INPUTS**<br />
5 = GE RR7 00 = No Relays 16 = 16 Relays Maximum 0=24 dry contact or up to 24 VDC max<br />
6 = GE RR9 60 = 60 Relays 32 = 32 Relays Maximum 1=56 (32-24VAC Triac & 24 dry contact)<br />
48 = 48 Relays Maximum<br />
60 = 60 Relays Maximum<br />
2=56 dry contact up to 24 VDC max<br />
* Select any number between 0 & 60<br />
When interfacing to another manufacturer by 2 wire RS485<br />
in increments of 1 relay, but do not exceed panel capacity.<br />
serial communication, be sure to contact that manufacturer<br />
** VDC signals must have negative common.<br />
for all necessary interface software and/or hardware.<br />
C8<br />