Power Supply Units Section 2-7<br />

2-7 Power Supply Units<br />

2-7-1 Duplex Power Supply Units<br />

82<br />

In a <strong>CS1D</strong> Duplex System, a duplex power supply can be configured by<br />

mounting a pair of <strong>CS1D</strong> Power Supply Units on the <strong>CPU</strong> Rack, an Expansion<br />

Rack, or Long-distance Expansion Rack.<br />

With a duplex power supply, the Backplane’s 5-V DC/26-V DC power supply is<br />

provided from the two <strong>CS1D</strong> Power Supply Units. Therefore the load per<br />

<strong>CS1D</strong> Power Supply Unit is approximately 50%.<br />

If there is a breakdown at one of the <strong>CS1D</strong> Power Supply Units, operation is<br />

continued by using only the other one. In that event, the load at the one<br />

remaining <strong>CS1D</strong> Power Supply Unit will increase to 100%. (See note 1.) At<br />

the same time, A31602 (duplex power supply error) will turn ON.<br />

Errors at Power Supply Units mounted on any Rack can be checked by means<br />

of A31900 to A31915 (for 5-V/26-V output errors) or A32000 to A32015 (for<br />

primary-side input voltage errors).<br />

Note Even if duplex Power Supply Units are to be used, take into account the<br />

effects if an error occurs at one of the Power Supply Units and calculate the<br />

current consumption under the condition of one Power Supply Unit. If two different<br />

kinds of Power Supply Units are to be used, calculate the current consumption<br />

using the output of the smaller-capacity Power Supply Unit.<br />

2-7-2 <strong>CS1D</strong> Power Supply Unit Models<br />

Power supply<br />

voltage<br />

100 to 120 V AC, or<br />

200 to 240 V AC<br />

(Switched with short<br />

bar for voltage<br />

switching terminals.)<br />

Power supply<br />

output capacity<br />

5 V DC, 7 A<br />

26 V DC, 1.3 A<br />

Total: 35 W<br />

24 V DC 5 V DC, 4.3 A<br />

26 V DC, 0.56 A<br />

Total: 28 W<br />

24 V DC 5 V DC, 5.3 A<br />

26 V DC, 1.3 A<br />

Total: 40 W<br />

Power supply<br />

output terminals<br />

RUN output Model Weight<br />

No Yes <strong>CS1D</strong>-PA207R 1,000 g max.<br />

No No <strong>CS1D</strong>-PD024 550 g max.<br />

No No <strong>CS1D</strong>-PD025 630 g max.<br />

Note Use the above Duplex Power Supply Units in a <strong>CS1D</strong> System. The C200HW-<br />

P@@@@ is for the CS Series and C200H, and cannot be used with the <strong>CS1D</strong>.