6<br />
The thermoregulation system<br />
Boilers VICTRIX <strong>50</strong> and VICTRIX 75 are provided with new generation electronics, offering the best performances thanks to their regulation<br />
flexibility.<br />
In case of zones systems or cascade systems, it will be necessary to pre-arrange an adequate thermoregulation device able to manage<br />
every single appliance and elaborate the information from the system, in order to meet the most var<strong>ie</strong>d operating requirements.<br />
Immergas thermoregulation system is composed of:<br />
Cascade and zones regulator<br />
Zone manager<br />
Modulating room thermostat<br />
Cascade and zones regulator<br />
It is the central unit of the thermoregulation system. It allows to control, monitor and program<br />
the operating sequence of a maximum of 8 generators in cascade. The regulator controls<br />
the boiler’s delivery temperature adjusting it to the system requirements.<br />
The regulator can manage up to 3 different zones (2 of which at high/low temperature)<br />
and a sanitary circuit for a separate storage tank. It is also possible to install up to 5 regulators<br />
in parallel (of which only one, called master, will be connected to the generators) to<br />
control up to a maximum of 15 heating zones and 5 storage tanks for the domestic hot<br />
water production.<br />
Zone manager<br />
Connected to the cascade and zones regulator, it allows to keep the operating appliance<br />
and the heating system information handy and under control. This means that the previously<br />
set functioning parameters (turn on/off, temperatures, etc.) can be easily modif<strong>ie</strong>d by<br />
the user, without having to operate on the central regulator.<br />
Modulating room thermostat<br />
Connected to the cascade and zones regulator, it allows the user to regulate the room<br />
temperature of the single zones into which the system is divided.<br />
External probe<br />
Connected to the boiler, it allows to optimize the energy consumptions automatically<br />
adjusting the system delivery temperature to suit the outdoor temperature variations.<br />
System delivery probe<br />
It allows the cascade and zones regulator to manage the system temperature.<br />
Separate storage tank probe<br />
It allows the cascade and zones regulator to control the temperature of a separate storage<br />