Akva Vita TD - Danfoss.com
Akva Vita TD - Danfoss.com
Akva Vita TD - Danfoss.com
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong><br />
Direct substation for one-family, semi-detached and terraced houses as well<br />
as apartments<br />
District heating substation for direct heating and instantaneous domestic hot water. Designed for<br />
wall-mounting.<br />
Application<br />
The <strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong> is a substation featuring high<br />
performance and simple operation. <strong>Akva</strong> <strong>Vita</strong><br />
<strong>TD</strong> is especially suitable for two-pipe systems<br />
and for decentralized systems in large apart-<br />
ment houses.<br />
District heating (DH)<br />
The substation is prefabricated with intercon-<br />
necting <strong>com</strong>ponents such as differential pres-<br />
sure control, fitting piece and sensor pockets<br />
for insertion of a heat meter as well as strainers,<br />
ball valves and pockets for pressure gauges.<br />
Heating (HE)<br />
The heating side is designed for direct genera-<br />
tion of heat in a 2-pipe system. The differential<br />
pressure control sets the optimum operation<br />
conditions for radiator thermostatic valves in<br />
order to enable individual temperature con-<br />
trol in each room. In order to enable a time-<br />
depending temperature control program, a<br />
zone valve with actuator and a room thermo-<br />
stat can be included as an option.<br />
VC.LA.H1.02 © <strong>Danfoss</strong> 11/2004<br />
Domestic hot water (DHW)<br />
The DHW is prepared in the heat exchanger<br />
based on the flow principle. Supreme ease of<br />
operation is obtained via hydraulic regulation<br />
of DHW through a proportional valve - the PM<br />
controller, thereby guaranteeing a constant<br />
DHW temperature at all times. The use of<br />
hydraulic regulation largely prevents the for-<br />
mation of lime scale and bacteria, due to the<br />
fact that the valve closes immediately when<br />
tapping is ended. A thermostatic by-pass en-<br />
ables tapping of hot water without any delay,<br />
- ensuring the best possible efficiency and<br />
economy. The cold water connection includes<br />
a <strong>com</strong>bined ball valve/non-return valve and<br />
safety valves.<br />
Domestic hot water circulation<br />
The <strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong> is equipped with by-pass<br />
function as a standard, but it is prepared for<br />
DHW circulation. Switching to DHW circula-<br />
tion is possible from a constructional point of<br />
view, requiring no extra <strong>com</strong>ponents.<br />
Construction<br />
All pipes are made of stainless steel. The con-<br />
nections are made by nuts and gaskets. The<br />
<strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong> can be delivered with anthracite<br />
grey-lacquered frame and with slightly curved<br />
front panel in either brushed or white-lac-<br />
quered stainless steel.<br />
FEATURES AND BENEFITS<br />
• Substation for district heating<br />
• Direct heating, DHW heating based on<br />
flow principle<br />
• Capacity: 20 kW heating, 35 kW domestic<br />
hot water<br />
• Maximum hot water <strong>com</strong>fort supply<br />
• Minimum space required for installation<br />
• Pipes and plate heat exchanger made<br />
of stainless steel<br />
• Minimized risk of lime scale and bacteria<br />
formation
<strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong><br />
Circuit diagram - example<br />
Technical parameters:<br />
Nominal pressure: PN 16<br />
DH supply temperature: T max = 120°C*<br />
DCW static pressure: p min = 2,5 bar<br />
Chloride <strong>com</strong>pounds: Max. 300 mg/l<br />
*At DH supply temp. above 90°C it is re<strong>com</strong>mended to<br />
order the <strong>Akva</strong> <strong>Vita</strong> <strong>TD</strong> equipped with an additional thermostatic<br />
controller.<br />
Weight incl. cover: 27,0 kg<br />
(incl. packing)<br />
Cover: Brushed or whitelacquered<br />
stainless<br />
steel<br />
Dimensions (mm):<br />
Without frame and front panel:<br />
H 640 x W 450 x D 290<br />
DHW: Capacity examples, 10°C/50°C<br />
DHW<br />
Capacity<br />
kW<br />
Plate<br />
heat exchanger<br />
Supply<br />
flow<br />
Primary<br />
°C<br />
Return<br />
flow<br />
Primary<br />
°C<br />
With frame and front panel:<br />
H 640 x W 500 x D 330<br />
Connections:<br />
1 District heating (DH) supply<br />
2 District heating (DH) return<br />
3 Domestic cold water (DCW)<br />
4 Circulation<br />
5 Domestic hot water (DHW)<br />
6 Heating (HE) supply<br />
7 Heating (HE) return<br />
DHW<br />
Tap load<br />
l/min.<br />
Pressure<br />
loss<br />
Primary<br />
*bar<br />
Flow rate<br />
Primary<br />
l/h<br />
35 WP22-22 60 35 12,5 0,55 1220<br />
35 WP22-22 70 28 12,5 0,19 724<br />
35 WP22-22 80 24 12,5 0,11 540<br />
35 WP22-22 90 21 12,5 0,07 436<br />
* Heat meter not incl.<br />
2 Plate heat exchanger DHW<br />
4 Differential pressure controller<br />
5 Strainer<br />
5A Strainer (fitted in T-piece)<br />
6 Non-return valve<br />
7 Ball valve<br />
12 Safety valve DHW<br />
13 Thermometer<br />
14 Pocket for pressure gauge<br />
23 Sensor pocket for heat meter<br />
24 Flexible fitting piece for heat<br />
meter<br />
Heating: Capacity examples<br />
<strong>Danfoss</strong> Redan A/S · District Heating Controls · Sindalsvej 33-35 · DK-8240 Risskov · Denmark<br />
Phone: +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.<strong>com</strong> · www.redan.danfoss.dk<br />
24A Leak control<br />
38 PM controller<br />
40 Thermostat for by-pass/circulation<br />
43 Blind plate<br />
---------------<br />
62 Non-return valve (optional)<br />
64 Circulation pump DHW (optional)<br />
Connections sizes:<br />
DH: G ¾” (ext. thread)<br />
DCW + DHW + HE: G ¾” (int. thread)<br />
Circulation: R ½” (ext. thread)<br />
Options:<br />
• Flexible fitting piece for heat meter with<br />
1” instead of ¾” connections<br />
• Additional fitting piece for heat meter in<br />
primary flow<br />
• Circulation pump<br />
• Zone valve with actuator<br />
time-depending temperature control)<br />
• Room thermostat (time-depending temperature<br />
control)<br />
• Without cover, or frame and front panel<br />
• With white-lacquered steel sheet cover<br />
• With additional thermostatic controller<br />
Heating Heating circuit, ∆t Pressure loss Flow rate<br />
Capacity Primary Secondary Primary primary<br />
kW °C<br />
°C<br />
*bar<br />
l/h<br />
10 20 20 0,24 428<br />
10 30 30 0,16 288<br />
10 40 40 0,14 216<br />
15 20 20 0,44 644<br />
15 30 30 0,24 428<br />
15 40 40 0,18 324<br />
20 20 20 0,72 860<br />
20 30 30 0,36 572<br />
20 40 40 0,24 428<br />
* Heat meter not incl.<br />
VC.LA.H1.02 © <strong>Danfoss</strong> 11/2004 DH-SMT-PL