Correction factor; ambient temperature k u<br />

The influence of the ambient temperature on the permissible load of<br />

the SITOR fuse links is taken into account using the correction factor<br />

k u as shown in the following graph.<br />

u<br />

Correction factor<br />

<br />

<br />

<br />

'<br />

&<br />

" " $ &<br />

Ambient temperature +<br />

Correction factor; conductor cross-section k q<br />

The rated current of the SITOR fuse links applies to operation with<br />

conductor cross-sections that correspond to the respective test<br />

cross-section (see the table on page 5/54).<br />

In the case of reduced conductor cross-sections, the correction<br />

factor k q , must be used as shown in the following graph.<br />

k q<br />

Correction factor<br />

1,00<br />

0,95<br />

0,90<br />

0,85<br />

0,80<br />

0,75<br />

0,70<br />

0,65<br />

100 80 60 50 40 30 20 15 10<br />

% Connection cross-section<br />

(as a % of the test cross-section)<br />

a = Reduction of cross-section of one connection<br />

b = Reduction of cross-section of both connections<br />

b<br />

a<br />

1 $ ! $<br />

I2_12639<br />

© Siemens AG 2007<br />

<strong>BETA</strong> Protecting<br />

SITOR Semiconductor Fuses<br />

Siemens ET B1 AO · 2008, Characteristic curves<br />

Configuration<br />

Correction factor; conduction angle k λ<br />

The rated current of the SITOR fuse links is based on a sinusoidal<br />

alternating current (45 Hz to 62 Hz). However, in converter operation,<br />

the arm fuses are loaded with an intermittent current, whereby the<br />

conduction angle is generally 180 °el or 120 °el. With this load current<br />

wave form, the fuse link can still carry the full rated current. In the<br />

case of smaller conduction angles, the current must be reduced in<br />

accordance with the following graph.<br />

Correction factor <br />

'<br />

&<br />

%<br />

$<br />

#<br />

! " # $ ' & "<br />

Valve conducting period<br />

Correction factor; forced-air cooling k l<br />

In the case of increased air cooling, the current carrying capacity of<br />

the fuse link increases with the air speed, air speeds > 5 m/s do not<br />

effect any significant further increase of current carrying capacity.<br />

Correction factor <br />

<br />

<br />

"<br />

!<br />

<br />

<br />

<br />

"<br />

Air velocity<br />

! $<br />

A <br />

$<br />

I<br />

1 $ ! &<br />

1 $ ! %<br />

4/55<br />