Correction factor; ambient temperature k u<br />
The influence of the ambient temperature on the permissible load of<br />
the SITOR fuse links is taken into account using the correction factor<br />
k u as shown in the following graph.<br />
u<br />
Correction factor<br />
<br />
<br />
<br />
'<br />
&<br />
" " $ &<br />
Ambient temperature +<br />
Correction factor; conductor cross-section k q<br />
The rated current of the SITOR fuse links applies to operation with<br />
conductor cross-sections that correspond to the respective test<br />
cross-section (see the table on page 5/54).<br />
In the case of reduced conductor cross-sections, the correction<br />
factor k q , must be used as shown in the following graph.<br />
k q<br />
Correction factor<br />
1,00<br />
0,95<br />
0,90<br />
0,85<br />
0,80<br />
0,75<br />
0,70<br />
0,65<br />
100 80 60 50 40 30 20 15 10<br />
% Connection cross-section<br />
(as a % of the test cross-section)<br />
a = Reduction of cross-section of one connection<br />
b = Reduction of cross-section of both connections<br />
b<br />
a<br />
1 $ ! $<br />
I2_12639<br />
© Siemens AG 2007<br />
<strong>BETA</strong> Protecting<br />
SITOR Semiconductor Fuses<br />
Siemens ET B1 AO · 2008, Characteristic curves<br />
Configuration<br />
Correction factor; conduction angle k λ<br />
The rated current of the SITOR fuse links is based on a sinusoidal<br />
alternating current (45 Hz to 62 Hz). However, in converter operation,<br />
the arm fuses are loaded with an intermittent current, whereby the<br />
conduction angle is generally 180 °el or 120 °el. With this load current<br />
wave form, the fuse link can still carry the full rated current. In the<br />
case of smaller conduction angles, the current must be reduced in<br />
accordance with the following graph.<br />
Correction factor <br />
'<br />
&<br />
%<br />
$<br />
#<br />
! " # $ ' & "<br />
Valve conducting period<br />
Correction factor; forced-air cooling k l<br />
In the case of increased air cooling, the current carrying capacity of<br />
the fuse link increases with the air speed, air speeds > 5 m/s do not<br />
effect any significant further increase of current carrying capacity.<br />
Correction factor <br />
<br />
<br />
"<br />
!<br />
<br />
<br />
<br />
"<br />
Air velocity<br />
! $<br />
A <br />
$<br />
I<br />
1 $ ! &<br />
1 $ ! %<br />
4/55<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13<br />
14<br />
15<br />
16<br />
17