24.08.2013 Views

Download the project report.

Download the project report.

Download the project report.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

For <strong>the</strong> AirTap A7, <strong>the</strong> test results agree very well with <strong>the</strong> test result provided with <strong>the</strong> unit. However,<br />

<strong>the</strong> results are suspect because <strong>the</strong> recovery rate of <strong>the</strong> system was insufficient to return <strong>the</strong> tank to its<br />

initial temperature in <strong>the</strong> time following each draw, so <strong>the</strong> average tank temperature was less than what<br />

<strong>the</strong> system should have had. With a lower average tank temperature, <strong>the</strong> efficiency of <strong>the</strong> system is<br />

higher than it would be if <strong>the</strong> temperature stayed close to <strong>the</strong> tank temperature setpoint. The CR Profile<br />

test allowed more time for recovery between draws, and included two draw events that caused <strong>the</strong> upper<br />

tank heating element to activate, and thus produced a lower EF.<br />

The lower than rated Energy Factor numbers seen for <strong>the</strong> Rheem in <strong>the</strong> first tests is directly a result of <strong>the</strong><br />

system switching over to electric resistance heat once <strong>the</strong> tank temperature reached about 130°F. As seen<br />

in <strong>the</strong> later test results, <strong>the</strong> unit certainly can meet and exceed <strong>the</strong>ir published rating so long as <strong>the</strong> system<br />

only uses <strong>the</strong> heat pump. Most consumers will likely leave <strong>the</strong> temperature setpoint at “Normal” where<br />

<strong>the</strong> electric resistance elements will likely not be activated in <strong>the</strong> Energy Saver mode. Consumers should<br />

also be actively advised to operate <strong>the</strong> system in <strong>the</strong> Energy Saver mode over <strong>the</strong> Normal mode to achieve<br />

consistently high performance. Ano<strong>the</strong>r concerning result from <strong>the</strong>se tests are <strong>the</strong> low numbers for <strong>the</strong><br />

operation with electric resistance heat only, with numbers significantly lower than what would be<br />

expected from a typical electric water heater. Some of this can be attributed to a standby power draw of<br />

at around 5½-Watts that is present even when <strong>the</strong> system is not actively heating, which may primarily be<br />

due to <strong>the</strong> indicator lights. (The AirTap indicated no measurable standby power.) Ano<strong>the</strong>r factor is <strong>the</strong><br />

external pipe for circulating water through <strong>the</strong> heat pump, which even though insulated still creates<br />

additional surface area for heat loss.<br />

Several sample charts of <strong>the</strong> start of an Energy Factor test are included in <strong>the</strong> Appendix. Figure 12 shows<br />

<strong>the</strong> general DOE standard draw profile in terms of when <strong>the</strong> flow draws occur and <strong>the</strong> quantity of each.<br />

While this chart shows <strong>the</strong> full 24-hours of <strong>the</strong> test window, <strong>the</strong> subsequent figures in this group only<br />

show <strong>the</strong> first 8-hours or <strong>the</strong> first third of <strong>the</strong> test. Figure 13 shows <strong>the</strong> test for <strong>the</strong> AirTap unit in heat<br />

pump only mode, and it can be seen that <strong>the</strong> heat pump was on continuously throughout <strong>the</strong> test and<br />

continued to run for more than two hours following <strong>the</strong> last draw until <strong>the</strong> <strong>the</strong>rmostat was satisfied. It<br />

also indicates a decreasing trend in <strong>the</strong> maximum water outlet temperature for each draw. In contrast, <strong>the</strong><br />

charts for <strong>the</strong> Rheem HP50 unit in Energy Saver (Figure 15) or Normal mode (Figure 14) show that in<br />

both modes <strong>the</strong> system was able to heat <strong>the</strong> water back up to <strong>the</strong> setpoint following <strong>the</strong> standard draw, and<br />

<strong>the</strong> outlet water temperature was consistent.<br />

Temperature Sensitivity<br />

Determining <strong>the</strong> sensitivity of <strong>the</strong> system performance (in particular power consumption) as a function of<br />

<strong>the</strong> water temperature and <strong>the</strong> ambient air temperature is subjective to <strong>the</strong> ability to control and measure<br />

<strong>the</strong>se parameters and <strong>the</strong> ability of <strong>the</strong> test unit to react consistently to <strong>the</strong>m. The results obtained from<br />

this test program are not completely clear and are open for interpretation, and could use a more rigorous<br />

examination than was included in this program.<br />

The sensitivity of power consumption to <strong>the</strong> average tank temperature was apparent in <strong>the</strong> test results<br />

shown in <strong>the</strong> charts for Energy Factor and especially First Hour Rating (because of <strong>the</strong> larger draw<br />

quantity and <strong>the</strong> resultant large range in tank temperature). As <strong>the</strong>se tests were all done while keeping <strong>the</strong><br />

room temperature relatively constant, <strong>the</strong> ambient conditions have little impact. Data were consolidated<br />

from <strong>the</strong> various standard tests and extracted from <strong>the</strong> periods when only <strong>the</strong> heat pump was operating (no<br />

electric resistance heat) and no draw was occurring. Curves were fitted to <strong>the</strong> consolidated data set, and<br />

<strong>the</strong>se are shown in Figure 16 without <strong>the</strong> underlying data. Bounding parallel curves indicating one<br />

standard error of <strong>the</strong> estimate (SEE) are drawn with dashed lines to signify <strong>the</strong> tightness of <strong>the</strong> data set to<br />

<strong>the</strong> curve. The curves for <strong>the</strong> Rheem are cut off below 105°F because no data were collected below this<br />

temperature. The important point to ga<strong>the</strong>r from <strong>the</strong>se curves is <strong>the</strong> rise in power consumption as a<br />

function of <strong>the</strong> tank temperature, which is set by <strong>the</strong> system <strong>the</strong>rmostat. Lowering <strong>the</strong> <strong>the</strong>rmostat thus has<br />

<strong>the</strong> effect of capping <strong>the</strong> maximum amount of power that <strong>the</strong> heat pump will draw when heating water.<br />

491-09.17.doc 18

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!