Cypress Duprex
Cypress Duprex
Cypress Duprex
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Supervised contacts and programming resistors:<br />
One of the features of the <strong>Duprex</strong> is that it supports the use of supervised contacts. By setting<br />
programming resistors on the Central unit, the status of contacts and end of line resistors on the<br />
Remote unit can be monitored.<br />
Two of the inputs support supervised contacts. The Alarm and Digital I/O #3 can operate in<br />
supervised mode.<br />
Supervised mode uses the programming resistors on the Central unit to determine what value of end<br />
of line resistor it should sense on the Remote unit. If the value of the programming resistor and the<br />
end of line resistor is equal, the output is not activated. If they are not equal, the output is activated.<br />
End of line resistors from 1K (1000 ohms) to 20K (20,000 ohms) can be used. The resistor for the<br />
end of line should match the value of its associated programming resistor.<br />
C<br />
R<br />
Ground<br />
Digital I/O<br />
programming<br />
resistor<br />
Ground<br />
Alarm<br />
programming<br />
resistor<br />
Digital I/O #3 Alarm<br />
Contact and end Contact and end<br />
of line resistor of line resistor<br />
©2005 <strong>Cypress</strong> Computer Systems,Inc. • www.cypressworld.com 11/21/05 Page 25