Supervised contacts and programming resistors:<br />

One of the features of the <strong>Duprex</strong> is that it supports the use of supervised contacts. By setting<br />

programming resistors on the Central unit, the status of contacts and end of line resistors on the<br />

Remote unit can be monitored.<br />

Two of the inputs support supervised contacts. The Alarm and Digital I/O #3 can operate in<br />

supervised mode.<br />

Supervised mode uses the programming resistors on the Central unit to determine what value of end<br />

of line resistor it should sense on the Remote unit. If the value of the programming resistor and the<br />

end of line resistor is equal, the output is not activated. If they are not equal, the output is activated.<br />

End of line resistors from 1K (1000 ohms) to 20K (20,000 ohms) can be used. The resistor for the<br />

end of line should match the value of its associated programming resistor.<br />

C<br />

R<br />

Ground<br />

Digital I/O<br />

programming<br />

resistor<br />

Ground<br />

Alarm<br />

programming<br />

resistor<br />

Digital I/O #3 Alarm<br />

Contact and end Contact and end<br />

of line resistor of line resistor<br />

©2005 <strong>Cypress</strong> Computer Systems,Inc. • www.cypressworld.com 11/21/05 Page 25