C/CPS<br />

Control panels for one or two pumps.<br />

DOL or star delta start, level control with contacts.<br />

Application<br />

These panels are used in standard application<br />

for pumps > 4kW.<br />

Two types are available:<br />

C: for level measuring with float switches<br />

CPS: for level measuring with air preassure<br />

tube<br />

Electronic control panels for controlling<br />

pumps depending of the water level in the<br />

pit.<br />

Both panels are suitable for protection and<br />

controlling of explosion proof pumps.<br />

ATTENTION: never install control box in<br />

Ex-hazardous areas !<br />

The level in the pit is actuated by float<br />

switches or electronic pressure sensor<br />

and an air tube in the pit.<br />

By using the diagnose unit ServCom (see<br />

accessories) it is possible to make settings<br />

and readout the internal memory. Delay<br />

time and counter reset for running hours<br />

and number of starts.<br />

Two pump operation:<br />

automatic changeover between both<br />

pumps<br />

if one pump failed the other pump will<br />

start<br />

peak load operation, second pump<br />

starts, if level 2 is crossing the limit value<br />

wired ready for connection<br />

C15 (one pump)<br />

opreating voltage 400V/N/PE 50 Hz<br />

control voltage 230VAC/12VDC<br />

insulated housing IP65<br />

main switch<br />

contactor or star delta combination<br />

motor protection switch<br />

manual – automatic – switch<br />

indication LED’s for run, failures and<br />

alarm<br />

sequence indicator<br />

dry contact for general alarm<br />

alarm system (not battey backed) with<br />

buzzer<br />

optional: 9V reachargeable battery block<br />

for battery backed alarm system<br />

inputs for thermocontact of motor winding<br />

(only pumps with themocontact)<br />

inputs for three float switches (off, on,<br />

alarm) on air tube<br />

optional: ex-barriers for intrinsically safe<br />

circutis<br />

plug in terminal for diagnose unit Serv-<br />

Com (see accessories)<br />

C25 (two pumps)<br />

same as C15/CPS15, additional:<br />

automatic change over between both<br />

pumps<br />

the second pump starts, if level 2 is<br />

crossing the limit value<br />

if one pump failed, the other pump will<br />

start<br />

C15-D10<br />

Pump Start Control box Part. No. Control box Part. No.<br />

nominal current for 1 pump for 2 Pumps<br />

(A) 1) Type Type<br />

1,6 - 2,4 DOL C15-D3 8235482 C25-D3 8235542<br />

2,4 - 4,0 DOL C15-D4 8235484 C25-D4 8235544<br />

4,0 - 6,3 DOL C15-D6 8235486 C25-D6 8235546<br />

6,3 - 10,0 DOL C15-D10 8235488 C25-D10 8235548<br />

6,0 - 10,0 DOL C15-D10S 8235489 C25-D10S 8235549<br />

10,0 - 16,0 DOL C15-D16 8235490 C25-D16 8235550<br />

6,0 - 10,0 Sar-Delta C15-Y10 8235500 C25-Y10 8235560<br />

10,0 - 16,0 Sar-Delta C15-Y16 8235502 C25-Y16 8235562<br />

16,0 - 20,0 Sar-Delta C15-Y20 8235504 C25-Y20 8235564<br />

20,0 - 25,0 Sar-Delta C15-Y25 8235505 C25-Y25 8235565<br />

25,0 - 32,0 Sar-Delta C15-Y32 8235506 C25-Y32 8235566<br />

32,0 - 40,0 Sar-Delta C15-Y40 8235508 C25-Y40 8235568<br />

40,0 - 50,0 Sar-Delta C15-Y50 8235510 C25-Y50 8235570<br />

50,0 - 58,0 Sar-Delta C15-Y58 8235512<br />

58,0 - 63,0 Sar-Delta C15-Y63 8235514<br />

63,0 - 80,0 Sar-Delta C15-Y80 8235516<br />

Factory settings:<br />

delay time after reaching the pumps off<br />

limit 3 sec.<br />

other settings on demand<br />

CPS25-Y16<br />

12<br />