Service Access and Clearance Requirements<br />

The <strong>Datawave</strong> magnetic synthesizer is designed to require minimal servicing. Access areas and recommended<br />

minimum clearances of each module are described below.<br />

15-20-30 kVA Sizes<br />

50-75 kVA Sizes<br />

Recommended minimum<br />

service clearances should<br />

exist at the front and one<br />

other side or rear as<br />

shown.<br />

Service clearance<br />

extends 42 inches<br />

(1067 mm) from the unit<br />

in accordance with the<br />

National Electrical Code.<br />

Model SC units require<br />

at least 6 inches<br />

(143 mm) at the bottom<br />

of the unit for cable routing.<br />

If the unit is not<br />

installed on a raised<br />

floor, floor pedestals<br />

must be provided.<br />

(Non-raised floor<br />

applications are not<br />

CSA-approved.)<br />

There should be<br />

18 inches (457 mm)<br />

above the unit for cooling<br />

air exhaust.<br />

Recommended minimum<br />

service clearances for the<br />

50 and 75 kVA sizes<br />

should exist at the front<br />

and left side. Where possible,<br />

service clearance is<br />

recommended at the<br />

front and rear. Service<br />

clearance extends 42<br />

inches (1067 mm) from<br />

the unit in accordance<br />

with the National Electrical<br />

Code.<br />

Model SC units require<br />

at least 6 inches<br />

(143 mm) clearance at<br />

the bottom of the unit for<br />

cable exit. (NOTE: If bottom<br />

cable exit or distribution<br />

cables are used,<br />

the unit must be<br />

installed on a raised<br />

floor, or floor pedestals<br />

must be provided.<br />

Non-raised floor applications<br />

are not<br />

CSA-approved.)<br />

There should be<br />

18 inches (457 mm)<br />

above the unit for cooling<br />

air flow.<br />

18"<br />

(457mm)<br />

42"<br />

(1067mm)<br />

42"<br />

(1067mm)<br />

18"<br />

(457mm)<br />

42"<br />

(1067mm)<br />

42"<br />

(1067mm)<br />

(required, plus<br />

one other side<br />

or back)<br />

15-20-30 kVA<br />

6"<br />

(152mm)<br />

(min. for bottom<br />

cable entrance)<br />

42"<br />

(1067mm)<br />

42"<br />

(1067mm)<br />

(required, plus one<br />

other side or back)<br />

50-75 kVA<br />

6"<br />

(152mm)<br />

(min. for bottom<br />

cable entrance)<br />

18