Service Access and Clearance Requirements<br />
The <strong>Datawave</strong> magnetic synthesizer is designed to require minimal servicing. Access areas and recommended<br />
minimum clearances of each module are described below.<br />
15-20-30 kVA Sizes<br />
50-75 kVA Sizes<br />
Recommended minimum<br />
service clearances should<br />
exist at the front and one<br />
other side or rear as<br />
shown.<br />
Service clearance<br />
extends 42 inches<br />
(1067 mm) from the unit<br />
in accordance with the<br />
National Electrical Code.<br />
Model SC units require<br />
at least 6 inches<br />
(143 mm) at the bottom<br />
of the unit for cable routing.<br />
If the unit is not<br />
installed on a raised<br />
floor, floor pedestals<br />
must be provided.<br />
(Non-raised floor<br />
applications are not<br />
CSA-approved.)<br />
There should be<br />
18 inches (457 mm)<br />
above the unit for cooling<br />
air exhaust.<br />
Recommended minimum<br />
service clearances for the<br />
50 and 75 kVA sizes<br />
should exist at the front<br />
and left side. Where possible,<br />
service clearance is<br />
recommended at the<br />
front and rear. Service<br />
clearance extends 42<br />
inches (1067 mm) from<br />
the unit in accordance<br />
with the National Electrical<br />
Code.<br />
Model SC units require<br />
at least 6 inches<br />
(143 mm) clearance at<br />
the bottom of the unit for<br />
cable exit. (NOTE: If bottom<br />
cable exit or distribution<br />
cables are used,<br />
the unit must be<br />
installed on a raised<br />
floor, or floor pedestals<br />
must be provided.<br />
Non-raised floor applications<br />
are not<br />
CSA-approved.)<br />
There should be<br />
18 inches (457 mm)<br />
above the unit for cooling<br />
air flow.<br />
18"<br />
(457mm)<br />
42"<br />
(1067mm)<br />
42"<br />
(1067mm)<br />
18"<br />
(457mm)<br />
42"<br />
(1067mm)<br />
42"<br />
(1067mm)<br />
(required, plus<br />
one other side<br />
or back)<br />
15-20-30 kVA<br />
6"<br />
(152mm)<br />
(min. for bottom<br />
cable entrance)<br />
42"<br />
(1067mm)<br />
42"<br />
(1067mm)<br />
(required, plus one<br />
other side or back)<br />
50-75 kVA<br />
6"<br />
(152mm)<br />
(min. for bottom<br />
cable entrance)<br />
18