X - Fachgebiet Hochspannungstechnik
X - Fachgebiet Hochspannungstechnik
X - Fachgebiet Hochspannungstechnik
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Generating High Alternating Voltages<br />
Tests at alternating voltage are performed as<br />
• Design Test (which is not defined acc. to IEC)<br />
• Type test<br />
• Routine Test<br />
• Acceptance Test<br />
• Commissioning Test, On-Site-Test<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 1 -
Generating High Alternating Voltages<br />
Required test voltage levels up to 2 MV (extreme value: 3 MV)<br />
Example 1:<br />
Standard short-duration power-frequency withstand voltage up to 3·U m<br />
• for type, routine and acceptance tests: factor of 1.1 required<br />
• for design tests at least factor of 1.4 recommended<br />
(U m = 245 kV ⇒<br />
Standard short-duration power-frequency withstand voltage<br />
max. 460 kV factor of 1.4 644 kV)<br />
Example 2:<br />
Line-to-earth voltage at U m = 800 kV: U LE = 462 kV<br />
factor of 1.1: 508 kV<br />
Line-to-earth voltage at U m = 1200 kV: U LE = 693 kV<br />
factor of 1.1: 762 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 2 -
Generating High Alternating Voltages<br />
Root mean square value of a voltage:<br />
T<br />
1 2<br />
Urms<br />
u()<br />
t dt<br />
= ∫<br />
T<br />
0<br />
(root mean square value)<br />
• Usually the voltage shape is not ideally sinusoidal.<br />
• In high-voltage technology in most cases only the peak value is of interest.<br />
⇒ Specification of a test voltage:<br />
û<br />
U<br />
rms<br />
= (IEC 60060-1, 1989-11)<br />
2<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 3 -
Generating High Alternating Voltages<br />
Requirements (IEC 60060-1):<br />
Deviation from sinusoidal shape:<br />
û<br />
2 5%<br />
U = ±<br />
(which is more or less the same as a requirement for a<br />
harmonics content < 5%)<br />
rms<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 4 -
Generating High Alternating Voltages<br />
Requirements (IEC 60060-1):<br />
Differences in peak values of two<br />
subsequent periods
Generating High Alternating Voltages<br />
Requirements (IEC 60060-1):<br />
Voltage dips (even if transient)<br />
Generating High Alternating Voltages<br />
Requirements (IEC 60060-1):<br />
Usually, the requirements are fulfilled automatically if the transformer<br />
short-circuit current is:<br />
For material investigations<br />
0.1 A for tests under dry conditions<br />
on just small test samples of solid or liquid insulation or<br />
a combination of both<br />
For tests on high-voltage equipment<br />
• at least 0.1 A for tests on self-restoring, external insulation<br />
under dry conditions<br />
• 0.5 A to 1 A under rain<br />
For tests under artificial pollution<br />
15 A or more (!!)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 7 -
Generating High Alternating Voltages<br />
Requirements (IEC 60060-1):<br />
Further possible means to fulfill the requirements:<br />
Connection of a supporting capacitor<br />
C >= 1 nF to the high-voltage terminals<br />
Damping resistance R = 1 kΩ ... 100 kΩ<br />
(or value such that τ = 10 µs)<br />
(avoidance of resonant oscillations,<br />
limiting of du/dt)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 8 -
Generating High Alternating Voltages<br />
Absolutely forbidden!<br />
Sudden connection of the transformer to the test sample<br />
at more than 50% of rated output voltage<br />
(else: resonant oscillations)<br />
⇒ Increase voltage slowly from zero!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 9 -
Differences Power Transformator – Test Transformator<br />
Power transformers:<br />
• mostly of three phase design (but also single phase)<br />
• tank and core always earthed<br />
• voltage regulation stepwise by tap changer<br />
• optimized for high power, high continuous and high short-circuit currents<br />
⇒ mechanical stress! (dynamic short-circuit current forces)<br />
⇒ thermal stress! (cooling ducts between winding layers;<br />
cooling by forced circulation; Buchholz relay)<br />
• insulated for high overvoltages<br />
Bilder Leistungstransformatoren<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 10 -
Differences Power Transformator – Test Transformator<br />
Test transformers:<br />
• only of single phase design<br />
• tank either earthed or on potential<br />
• tank often made from insulating material<br />
•coreeither earthed or on potential<br />
• very precise (nearly stepless) voltage regulation on the lv side<br />
by help of a regulation transformer; no regulation on the hv side<br />
• optimized for short-time duty<br />
• very high rated voltages, but not insulated against<br />
high overvoltages<br />
• mainly capacitive loading<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 11 -
Capacitive Loading<br />
Kind of equipment<br />
Station posts, line insulators<br />
Bushings<br />
Inductive instrument transformers<br />
Power transformers < 1 MVA<br />
Power transformers > 1 MVA<br />
Cables<br />
Gas-insulated lines (GIL)<br />
Gas-insulated switchgear (GIS)<br />
Capacitance (estimated)<br />
20 pF<br />
100 pF ... 500 pF<br />
200 pF ... 500 pF<br />
1 nF ... 3 nF<br />
1 nF ...25 nF<br />
200 pF/m ... 700 pF/m (300 pF/m)<br />
60 pF/m<br />
1 nF ... 10 nF<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 12 -
Capacitive Loading<br />
• Test voltage 1 MV<br />
• Capacitive load 3,2 nF<br />
Current<br />
I = U⋅ω⋅ C = ⋅ ⋅ ⋅ ⋅ ⋅ =<br />
6 −9<br />
110 V 2π<br />
50Hz 3,210 F 1A<br />
Power (leading reactive power)<br />
S U C<br />
( ) 2<br />
2 6 −9<br />
= ⋅ω⋅ = ⋅ ⋅ π ⋅ ⋅ ⋅ =<br />
110 V 2 50Hz 3,210 F 1MVA<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 13 -
Capacitive Loading<br />
Additional capacitive loading by<br />
• shielding electrodes<br />
• high voltage connections<br />
• voltage measurement<br />
(e. g. capacitive divider)<br />
<br />
Up to 100 kV test voltage ⇒<br />
100 pF<br />
Up to 1000 kV test voltage ⇒ 1000 pF<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 14 -
Capacitive Loading by Shielding Electrodes<br />
Sphere electrode for 1 MV alternating voltage<br />
Goal: to chose the radius<br />
such that there are no<br />
partial discharges.<br />
Maximum electrical field stress<br />
on the electrode surface:<br />
E<br />
max<br />
U<br />
=<br />
r<br />
K<br />
K<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 15 -
Capacitive Loading by Shielding Electrodes<br />
Maximum allowed electrical field<br />
stress in air to achieve freedom<br />
from partial discharges:<br />
E max = 25 kV/cm<br />
Required sphere radius:<br />
r<br />
K<br />
U<br />
1,4 MV<br />
K<br />
= = =<br />
Emax<br />
25 kV/cm<br />
56 cm<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 16 -
Capacitive Loading by Shielding Electrodes<br />
Capacitance of a sphere to ground<br />
(ground in infinite distance):<br />
C K = 4 πε 0 ε r r k<br />
ε 0 = 8,86 pF/m<br />
C K / pF = 1,11 r K / cm = 62 pF<br />
⇒ capacitive current: 20 mA<br />
⇒ reactive power: 20 kVA<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 17 -
Basic Design of Test Transformers<br />
Grading electrodes for field stress reduction<br />
High-voltage winding<br />
Energizing winding<br />
Core<br />
Optimal capacitive voltage distribution by close winding<br />
and approximately trapezoidal shape of high-voltage winding<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 18 -
Basic Design of Test Transformers<br />
How to get even capacitances between the individual layers?<br />
Length l<br />
Radius r<br />
Distance d<br />
Capacitance between two layers:<br />
A 2π<br />
r⋅l<br />
C ≈εε<br />
0 r⋅ = εε<br />
0 r⋅ (for d
Transformer Equivalent Electric Circuits<br />
Φ h<br />
I 1 I 2<br />
U 1<br />
U 2<br />
Φ 1σ<br />
Φ 2σ<br />
Electrical circuit<br />
U<br />
I<br />
R<br />
G = 1/R<br />
Magnetical circuit<br />
N·I<br />
Φ<br />
l m<br />
/µA<br />
Λ = µA/l m<br />
Φ nσ ... Stray flux of winding n<br />
Φ h ... Common working flux<br />
N·I ... magnetic potential, ampere-turns<br />
Φ ... magnetic flux<br />
µ= µ 0·µ r<br />
µ 0 ... Permeability of the vacuum<br />
4π·10 -7 = 1,256·10 -6 Vs/Am<br />
µ r ... relative Permeability<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 20 -
Transformer Equivalent Electric Circuits<br />
I Φ h<br />
1<br />
I 2<br />
X 2σ<br />
R 1 X 1σ<br />
R 2<br />
U 1<br />
U 2<br />
X σ = ωL σ (with: L σ = N 2 Λ σ )<br />
X σ ..."Stray reactance"<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 21 -
Transformer Equivalent Electric Circuits<br />
I' 1<br />
I 2<br />
X 2σ<br />
R' 1 X' 1σ<br />
R 2<br />
U' 1<br />
U 2<br />
I µ<br />
X h<br />
R Fe<br />
I Fe<br />
X h ..."Magnetizing reactance"<br />
X σ ..."Stray reactance"<br />
Conversion of dashed values:<br />
U<br />
N<br />
N<br />
' 2<br />
1 = ⋅U1<br />
1<br />
I<br />
N<br />
N<br />
' 1<br />
1 = ⋅ I 1<br />
2<br />
R<br />
2<br />
⎛N<br />
⎞<br />
= ⋅ R<br />
⎝ ⎠<br />
' 2<br />
1 ⎜<br />
1<br />
N<br />
⎟<br />
1<br />
X<br />
' 2<br />
1σ<br />
⎜<br />
1σ<br />
N<br />
⎟<br />
1<br />
2<br />
⎛N<br />
⎞<br />
= ⋅ X<br />
⎝ ⎠<br />
Magnitudes:<br />
• R<br />
≈<br />
R<br />
'<br />
1 2<br />
X<br />
≈<br />
X<br />
'<br />
1σ<br />
2σ<br />
• for big transformers:<br />
3 4<br />
• X<br />
h, RFe<br />
≈10 ...10 ⋅X σ<br />
X<br />
≈ 1,2<br />
20...30 ⋅<br />
σ<br />
R1,2<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 22 -
Transformer Equivalent Electric Circuits<br />
Simplified transformer equivalent electric circuit<br />
I<br />
R k<br />
X k<br />
U' 1 U 2<br />
reduced to short - circuit impedance Z = R + X = R + jωL<br />
k k k k k<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 23 -
Performance at Capacitive Loading<br />
I<br />
I<br />
R k X k R k X k<br />
U' 1 C T U 2<br />
C a U' 1 U 2<br />
C<br />
R k·I<br />
jωL k·I<br />
C = C T + C a<br />
U 2<br />
U' 1<br />
X k = ωL k<br />
I<br />
U' 1 = R k·I + jωL k·I + U 2<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 24 -
Performance at Capacitive Loading<br />
The mainly capacitive loading of test transformers<br />
(as virtually always the case)<br />
results in a<br />
Magnification of the secondary voltage!<br />
⇒ The secondary voltage can only roughly be estimated from the<br />
transformer ratio.<br />
⇒ The measurement of the high-voltage has to be performed<br />
directly on the hv side of the transformer.<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 25 -
Performance at Capacitive Loading<br />
Calculation of capacitive voltage magnification<br />
at loading with rated voltage and current<br />
1 st step: further simplification of the equivalent electrical circuit by<br />
neglecting the ohmic losses ....<br />
I<br />
X k<br />
U' 1 U 2<br />
C<br />
10<br />
8<br />
6<br />
y = 1/(1-0,1x)<br />
y<br />
U<br />
U′<br />
2<br />
1<br />
=<br />
1<br />
2<br />
1−ω<br />
LC<br />
k<br />
4<br />
2<br />
0<br />
0 2 4 6 8 10<br />
x<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 26 -
Performance at Capacitive Loading<br />
Calculation of capacitive voltage magnification<br />
at loading with rated voltage and current<br />
2 nd step: Calculation of relative short-circuit voltage<br />
for the particular case ....<br />
U k = I n ·Z k = I n · ωL k<br />
Short-circuit voltage = voltage that must be applied to the primary side<br />
in order to drive nominal current in case of a shorted secondary side<br />
u<br />
k<br />
U In<br />
⋅ωL<br />
U U<br />
k<br />
= =<br />
2, n 2, n<br />
k<br />
I = U ⋅ωC<br />
n<br />
2, n<br />
(Assumption that the current through C<br />
at rated voltage just equals rated current.)<br />
u<br />
k<br />
2<br />
= ω L C<br />
k<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 27 -
Performance at Capacitive Loading<br />
Calculation of capacitive voltage magnification<br />
at loading with rated voltage and current<br />
3 rd step: insert the relative short-circuit voltage ....<br />
U<br />
U<br />
U<br />
U<br />
2<br />
′<br />
1<br />
2<br />
′<br />
1<br />
= 1<br />
2<br />
1 − ω LC<br />
1<br />
=<br />
1 − u<br />
k<br />
k<br />
u<br />
k<br />
2<br />
= ω L C<br />
k<br />
Relative short-circuit voltage u k = 20%<br />
⇒ Voltage magnification at capacitive loading<br />
with rated current: 25%!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 28 -
Design Variants of Test Transformers<br />
2 different circuit variants:<br />
x<br />
HW<br />
U isol<br />
One pole insulated<br />
K<br />
EW<br />
x<br />
x<br />
Fully insulated<br />
K<br />
HW<br />
U isol<br />
x<br />
Center tap earthed<br />
⇒ balanced-to-earth voltage<br />
EW<br />
One of the external terminals earthed<br />
⇒ non balanced-to-earth voltage<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 29 -
Design Variants of Test Transformers<br />
Design variants<br />
Epoxy resin insulated<br />
Oil insulated<br />
SF 6 -insulated<br />
Tank type<br />
Insulated enclosure type<br />
Single stage<br />
or<br />
Multi-stage (cascading)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 30 -
Design Variants of Test Transformers<br />
Test transformer with epoxy resin insulation<br />
(very simplified depiction)<br />
1 High-voltage winding<br />
2 Energizing winding<br />
3 Iron core<br />
4 Base<br />
5 High-voltage terminal<br />
6 Epoxy resin insulation<br />
Up to rated voltages of about 100 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 31 -
Design Variants of Test Transformers<br />
Test transformer with epoxy resin insulation<br />
(very simplified depiction)<br />
MWB test transformer 2 x 50 kV<br />
"piglet"<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 32 -
Design Variants of Test Transformers<br />
Oil insulated tank type test transformer<br />
1 High-voltage winding<br />
2 Energizing winding<br />
3 Iron core<br />
4 Base<br />
5 High-voltage terminal<br />
6 Bushing<br />
7 Metal tank<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 33 -
Design Variants of Test Transformers<br />
Oil insulated tank type test transformer<br />
Rated voltages up to about 400 kV (800 kV)<br />
• good cooling (metal tank!)<br />
• high power<br />
• comparatively small oil volume<br />
• expensive bushing<br />
• expensive shielding electrode<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 34 -
Design Variants of Test Transformers<br />
Oil insulated tank type test transformer<br />
Aktive parts 550 kV (MWB)<br />
• aufwendige Durchführung<br />
• aufwendige Schirmelektrode<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 35 -
Design Variants of Test Transformers<br />
Oil insulated tank type test transformer<br />
TuR, 600 kV, 3.33 A<br />
• aufwendige Durchführung<br />
• aufwendige Schirmelektrode<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 36 -
Design Variants of Test Transformers<br />
Oil insulated enclosure<br />
type test transformer<br />
1 High-voltage winding<br />
2 Energizing winding<br />
3 Iron core<br />
4 Base<br />
5 High-voltage terminal<br />
8 Insulated enclosure<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 37 -
Design Variants of Test Transformers<br />
Oil insulated enclosure<br />
type test transformer<br />
• no bushing required<br />
• simple shielding electrode<br />
• large oil volume<br />
• bad cooling<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 38 -
Design Variants of Test Transformers<br />
Oil insulated enclosure<br />
type test transformer<br />
HighVolt, 100 kV<br />
MWB, 100 kV<br />
HAEFELY, 100 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 39 -
Design Variants of Test Transformers<br />
Oil insulated enclosure<br />
type test transformer<br />
MWB, 550 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 40 -
Design Variants of Test Transformers<br />
9<br />
3 2<br />
1<br />
5<br />
SF 6 -insulated test transformer<br />
1 High-voltage winding<br />
2 Energizing winding<br />
3 Iron core<br />
5 High-voltage terminal<br />
9 Pressure resistant vessel (Steel, Aluminum)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 41 -
Design Variants of Test Transformers<br />
9<br />
3 2<br />
1<br />
5<br />
SF 6 -insulated test transformer<br />
• compact, lightweight<br />
• direct connection to GIS/GIL<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 42 -
Design Variants of Test Transformers<br />
SF 6 -insulated test transformer<br />
Direct coupling of an SF 6 -insulated<br />
test transformer to the GIS in order to<br />
avoid mounting of an open air test bushing<br />
alternatively…<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 43 -
Design Variants of Test Transformers<br />
SF 6 -insulated test transformer<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 44 -
Transformer Cascades<br />
Cascading of transformers usually above about 300 kV (latest above 800 kV)<br />
Energizing winding<br />
Coupling winding<br />
High-voltage winding<br />
⇒ Three-winding transformer<br />
max. 4 stages!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 45 -
Transformer Cascades<br />
With the exception of the bottom stage<br />
all stages must be installed insulated.<br />
U<br />
2/3 U<br />
1/3 U<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 46 -
Transformer Cascades<br />
First 1-MV test transformer<br />
cascade worldwide<br />
(year of manufacturing 1923)<br />
(2·500 kV in phase opposition)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 47 -
Transformer Cascades<br />
Two stage transformer cascade (2·600 kV, 2 A continuous duty)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 48 -
Transformer Cascades<br />
2-stage cascade<br />
1.8 MV<br />
HVTS<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 49 -
Transformer Cascades<br />
TU Darmstadt<br />
1.2 MV (2·2·300 kV)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 50 -
Transformer Cascades<br />
Top transformer<br />
Intermediate transformer<br />
U<br />
Siemens Berlin<br />
1.8 MV (3·600 kV)<br />
TuR<br />
Base transformer<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 51 -
Transformer Cascades<br />
Power requirements<br />
Energizing winding base stage: 300%<br />
Coupling winding base stage: 200%<br />
Energizing winding top stage: 100%<br />
Energizing winding intermed. stage: 200 %<br />
Coupling winding intermed. stage: 100%<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 52 -
Transformer Cascades<br />
Compensation of capacitive reactive power by reactors<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 53 -
Transformer Cascades<br />
... also as insulated enclosure type<br />
3·100 kV<br />
2·100 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 54 -
Transformer Cascades<br />
... also as insulated enclosure type<br />
Siemens Berlin<br />
2·400 kV<br />
TuR<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 55 -
Transformer Cascades<br />
... also as insulated enclosure type<br />
EDF, Les Renardières<br />
MWB, 1.65 MV<br />
Lab closed!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 56 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
Core at 50% potential<br />
Lower requirements on hv<br />
winding insulation against<br />
core<br />
Requires two bushings<br />
One energizing winding<br />
used as energizing winding<br />
The other energizing<br />
winding used as coupling<br />
winding for the next stage<br />
Leakage suppressing<br />
windings to balance the<br />
magnetic flux<br />
⇒ reduced stray reactance<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 57 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... epoxy resin insolated<br />
MWB<br />
2 x 50 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 58 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... tank type<br />
TuR<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 59 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... tank type<br />
2-stage<br />
1.2 MV, 1.25 A<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 60 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... tank type<br />
2-stage<br />
TuR<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 61 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... tank type<br />
3-stage<br />
2.25 MV (3·2·375 kV), 1 A<br />
TuR<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 62 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... tank type<br />
TU Munich<br />
1.2 MV (3·2·200 kV)<br />
Siemens<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 63 -
Transformer Cascades<br />
Largest test tranformer cascade worldwide (3 MV, 12.6 MVA, Moscow 1991)<br />
Modell<br />
TuR<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 64 -
Transformer Cascades<br />
Largest test tranformer cascade worldwide (3 MV, 12.6 MVA, Moscow 1991)<br />
Siemens<br />
(TuR)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 65 -
Transformer Cascades<br />
Cascade arrangement with 2 stages on one core<br />
... insulated enclosure type<br />
2·400 kV CESI (Milano)<br />
2·400 kV<br />
2·400 kV<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 66 -
Short-Circuit Reactance of Transformer Cascades<br />
Electrical equivalent circuit diagram<br />
of a 3-stage cascade<br />
If losses are neglected and under the assumption<br />
of even winding ratios:<br />
N<br />
N<br />
Eν<br />
Hν<br />
=<br />
N<br />
N<br />
Kν<br />
Hν<br />
for ν = 1...3<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 67 -
Short-Circuit Reactance of Transformer Cascades<br />
Equivalence of power for both equivalent circuit diagrams:<br />
3<br />
2 '2 ' '2 ' 2<br />
H⋅ res<br />
= ∑ Eν ⋅<br />
Eν +<br />
Kν ⋅<br />
Kν +<br />
Hν ⋅<br />
Hν<br />
ν = 1<br />
( )<br />
I X I X I X I X<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 68 -
Short-Circuit Reactance of Transformer Cascades<br />
3<br />
∑( ν ν ν ν ν ν)<br />
I ⋅ X = I ⋅ X + I ⋅ X + I ⋅X<br />
2 '2 ' '2 ' 2<br />
H res E E K K H H<br />
ν = 1<br />
not present!<br />
I ⋅X I ⋅X I ⋅X I ⋅X I ⋅X I ⋅X<br />
X X X X<br />
'2 ' '2 ' '2 ' '2 ' '2 ' '2 '<br />
E1 E1 K1 K1 E2 E2 K2 K2 E3 E3 K3 K3<br />
res<br />
= + +<br />
2 2 H1 + + +<br />
2 2 H2<br />
+ + +<br />
2 2<br />
H3<br />
IH IH IH IH IH IH<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 69 -
Short-Circuit Reactance of Transformer Cascades<br />
I = I = I = I ⇒ I = I = I<br />
' ' '2 '2 2<br />
E3 K2 H E3 K2<br />
H<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 70 -
Short-Circuit Reactance of Transformer Cascades<br />
I = I = I<br />
'2 '2 2<br />
E3 K2 H<br />
3<br />
∑( ν ν ν ν ν ν)<br />
I ⋅ X = I ⋅ X + I ⋅ X + I ⋅X<br />
not present!<br />
2 '2 ' '2 ' 2<br />
H res E E K K H H<br />
ν = 1<br />
res<br />
'2 ' '2 ' '2 ' '2 ' '2 ' '2 '<br />
IE1 ⋅XE1 IK1 ⋅XK1 IE2 ⋅XE2 IK2 ⋅XK2 IE3 ⋅XE3 IK3 ⋅XK3<br />
= + +<br />
2 2 H1 + + +<br />
2 2 H2<br />
+ + +<br />
2 2<br />
IH IH IH IH IH IH<br />
H3<br />
X X X X<br />
I ⋅X I ⋅X I ⋅X<br />
X X X X X X<br />
'2 ' '2 ' '2 '<br />
E1 E1 K1 K1 E2 E2 '<br />
'<br />
res<br />
= + +<br />
H1+ +<br />
2 2 2<br />
K2<br />
+<br />
H2<br />
+<br />
E3+<br />
H3<br />
IH IH IH<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 71 -
Short-Circuit Reactance of Transformer Cascades<br />
I = I = 2⋅ I = 2⋅I ⇒ I = I = 4⋅I<br />
' ' '2 '2 2<br />
E 2 K1 H E2 K1<br />
H<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 72 -
Short-Circuit Reactance of Transformer Cascades<br />
I ⋅X I ⋅X I ⋅X<br />
X X X X X X<br />
'2 ' '2 ' '2 '<br />
E1 E1 K1 K1 E2 E2 '<br />
'<br />
res<br />
= + +<br />
H1+ +<br />
2 2 2<br />
K2<br />
+<br />
H2<br />
+<br />
E3+<br />
H3<br />
IH IH IH<br />
I = I = 4⋅I<br />
'2 '2 2<br />
E2 K1 H<br />
3<br />
∑( ν ν ν ν ν ν)<br />
I ⋅ X = I ⋅ X + I ⋅ X + I ⋅X<br />
I ⋅ X<br />
X X X X X X X X<br />
'2 '<br />
E1 E1 ' ' ' '<br />
res<br />
= + 4⋅ K1+ 2<br />
H1+ 4⋅ E2<br />
+<br />
K2<br />
+<br />
H2<br />
+<br />
E3+<br />
H3<br />
IH<br />
not present!<br />
2 '2 ' '2 ' 2<br />
H res E E K K H H<br />
ν = 1<br />
res<br />
'2 ' '2 ' '2 ' '2 ' '2 ' '2 '<br />
IE1 ⋅XE1 IK1 ⋅XK1 IE2 ⋅XE2 IK2 ⋅XK2 IE3 ⋅XE3 IK3 ⋅XK3<br />
= + +<br />
2 2 H1 + + +<br />
2 2 H2<br />
+ + +<br />
2 2<br />
IH IH IH IH IH IH<br />
H3<br />
X X X X<br />
I = I = I<br />
'2 '2 2<br />
E3 K2 H<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 73 -
Short-Circuit Reactance of Transformer Cascades<br />
I = 3⋅ I = 3⋅I ⇒ I = 9⋅I<br />
' '2 2<br />
E1 H E1<br />
H<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 74 -
Short-Circuit Reactance of Transformer Cascades<br />
I<br />
= 9⋅I<br />
'2 2<br />
E1 H<br />
3<br />
∑( ν ν ν ν ν ν)<br />
I ⋅ X = I ⋅ X + I ⋅ X + I ⋅X<br />
X = 9⋅ X + 4⋅ X + X + 4⋅ X + X + X + X + X<br />
' ' ' ' '<br />
res E1 K1 H1 E2 K2 H2 E3 H3<br />
( )<br />
X = X + X + X + X + X + 4⋅ X + X + 9⋅X<br />
' ' ' ' '<br />
res H1 H2 H3 K2 E3 K1 E2 E1<br />
not present!<br />
2 '2 ' '2 ' 2<br />
H res E E K K H H<br />
ν = 1<br />
res<br />
'2 ' '2 ' '2 ' '2 ' '2 ' '2 '<br />
IE1 ⋅XE1 IK1 ⋅XK1 IE2 ⋅XE2 IK 2<br />
⋅XK 2<br />
IE3 ⋅XE3 IK3 ⋅XK3<br />
= + +<br />
2 2 H1 + + +<br />
2 2 H2<br />
+ + +<br />
2 2<br />
IH IH IH IH IH IH<br />
H3<br />
X X X X<br />
I = I = I<br />
'2 '2 2<br />
E3 K2 H<br />
I ⋅X I ⋅X I ⋅X<br />
X X X X X X<br />
'2 ' '2 ' '2 '<br />
E1 E1 K1 K1 E2 E2 '<br />
'<br />
res<br />
= + +<br />
H1+ +<br />
2 2 2<br />
K2<br />
+<br />
H2<br />
+<br />
E3+<br />
H3<br />
IH IH IH<br />
I = I = 4⋅I<br />
'2 '2 2<br />
E2 K1 H<br />
I ⋅ X<br />
X X X X X X X X<br />
'2 '<br />
E1 E1 ' ' ' '<br />
res<br />
= + 4⋅ K1+ 2<br />
H1+ 4⋅ E2<br />
+<br />
K2<br />
+<br />
H2<br />
+<br />
E3+<br />
H3<br />
IH<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 75 -
Short-Circuit Reactance of Transformer Cascades<br />
( )<br />
X = X + X + X + X + X + 4⋅ X + X + 9⋅X<br />
' ' ' ' '<br />
res H1 H2 H3 K2 E3 K1 E2 E1<br />
The resulting short-circuit reactance of a multi-stage cascade<br />
is higher than the linear sum of the individual stage reactances!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 76 -
Series Resonant Circuits<br />
Resonant frequency<br />
f<br />
0<br />
=<br />
1<br />
2π<br />
LC<br />
jωL·I<br />
U 2<br />
U' 2<br />
Voltage magnification<br />
Q-factor<br />
Characteristic impedance<br />
U<br />
U<br />
Q<br />
Z<br />
2<br />
'<br />
2<br />
K<br />
=<br />
= Q<br />
ZK<br />
=<br />
R<br />
L<br />
C<br />
R T·I<br />
jωL T·I<br />
U' 1<br />
I<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 77 -
Series Resonant Circuits<br />
Drive<br />
core movement<br />
Lead screw (the core is actually in 100% position)<br />
Fixed part of the core<br />
Active part of a high-voltage reactor with variable core<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 78 -
Series Resonant Circuits<br />
Advantages:<br />
• Extremely low content of harmonics in high-voltage<br />
• Very low short-circuit power<br />
• Only low power requirements on transformer (just compensation of losses)<br />
• Weight of high-voltage reactor only one third of that of a comparable<br />
high-voltage transformer<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 79 -
Series Resonant Circuits<br />
1<br />
3<br />
4<br />
5<br />
Adjustable<br />
high-voltage reactor<br />
Q ≈ 50<br />
C max /C min ≈ 20 (because Lmax/Lmin ≈ 20)<br />
Specific weight 3...8 kg/kVA<br />
4<br />
2<br />
3<br />
Variable frequency<br />
5<br />
Q ≈ 100...200<br />
C max /C min = 225 (because f = 20...300 Hz)<br />
Specific weight 0,8...1,5 kg/kVA<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 80 -
Series Resonant Circuits<br />
Mobile series resonant test setup of variable frequency; 150 kV/90 A<br />
HighVolt<br />
Energizing transformer<br />
Reactor (tank type)<br />
Coupling capacitor for partial<br />
discharge measurement<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 81 -
Series Resonant Circuits<br />
On-site testing with a two stage series resonant test setup 700 kV<br />
HVTS<br />
Transformer!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 82 -
Series Resonant Circuits<br />
Three stage series resonant test setup 1200 kV/4 A<br />
with adjustable reactors<br />
HighVolt<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 83 -
Series Resonant Circuits<br />
On-site testing with a three stage series resonant test setup<br />
GIS 765 kV, ESKOM, South Africa<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 84 -
Series Resonant Circuits<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 85 -
Series Resonant Circuits<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 86 -
Series Resonant Circuits<br />
Research project at <strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong> of TUD<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 87 -
Power Supply of Test Transformers<br />
Most common:<br />
Regulation transformer fed from the line (low or medium voltage)<br />
But also:<br />
Motor-Generator set<br />
• Synchronous converter<br />
• Ward-Leonard converter<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 88 -
Protection Circuit<br />
Damping resistance R = 1 kΩ ... 100 kΩ<br />
(or value such that τ = 10 µs)<br />
(avoidance of resonant oscillations,<br />
limiting of du/dt)<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 89 -
Protection Circuit<br />
Current breaker and short-circuiter with power electronic devices<br />
Regulation -<br />
transformer<br />
Thyristor -<br />
short-circuiter<br />
Thyristor breaker<br />
Test -<br />
transformer<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 90 -
Basic Insulation Levels acc. to IEC 60071-1<br />
Range I:<br />
U m = 1 kV up to and including U m = 245 kV<br />
The standard voltage values are<br />
all the same for<br />
• Phase-to-earth-,<br />
• Phase-to-phase-,<br />
• Longitudinal<br />
insulation!<br />
<strong>Fachgebiet</strong><br />
<strong>Hochspannungstechnik</strong><br />
High-Voltage Technology / Chapter 2 - 91 -