Thermidistat Control<br />
Visit www.carrier.com<br />
<strong>Low</strong> <strong>Voltage</strong> <strong>Wiring</strong> <strong>Diagrams</strong><br />
NOTE: Read the entire instruction manual before starting the<br />
installation.<br />
SAFETY CONSIDERATIONS<br />
Improper installation, adjustment, alteration, service, maintenance,<br />
or use can cause fire, electrical shock, or other conditions which<br />
may cause personal injury or property damage. Consult a qualified<br />
installer, for information or assistance. The qualified installer must<br />
use factory-authorized kits or accessories when modifying this<br />
product. Refer to the individual instructions packaged with the kits<br />
or accessories when installing.<br />
Follow all safety codes and wear safety glasses. Read these<br />
instructions thoroughly and follow all warnings or cautions attached<br />
to the unit. Consult local and state building codes and Sheet<br />
Metal and Air Conditioning National Association (SMACNA) for<br />
special installation requirements.<br />
Recognize safety information. This is the safety-alert symbol .<br />
When you see this symbol on the unit or in instructions and<br />
manuals, be alert to the potential for personal injury.<br />
Understand the signal words DANGER, WARNING, and CAU-<br />
TION. These words are used with the safety-alert symbol. DAN-<br />
GER identifies the most serious hazards which will result in severe<br />
personal injury or death. WARNING signifies hazards which<br />
could result in personal injury or death. CAUTION is used to<br />
identify unsafe practices which would result in minor personal<br />
injury or product and property damage.<br />
WIRING DIAGRAM NOTES<br />
1. Refer to Fan Coil Installation Instructions for features and<br />
additional wiring information<br />
2. To activate dehumidify function on FK or FV series, remove<br />
J1 jumper at fan coil control board.<br />
3. Heat pump must have a high pressure switch for dual fuel<br />
applications.<br />
4. Refer to outdoor equipment Installation Instructions for proper<br />
setup.<br />
5. Select the ″zone″ position on the 2-speed heat pump control<br />
board. This applies only to 38YDA (R-22 units).<br />
6. As an option O/W2 can be used to allow Thermidistat to<br />
control second-stage heat. Refer to indoor unit Installation<br />
Instructions for proper setup.<br />
7. As an option, Y1/W2 can be used to allow Thermidistat to<br />
control third-stage heat. Refer to indoor unit Installation<br />
Instructions for proper setup.<br />
8. Furnace must control its own second-stage heat operation via<br />
furnace control algorithm.<br />
9. Outdoor air sensor must be attached in all dual fuel applications.<br />
10. Refer to indoor equipment Installation Instructions for proper<br />
setup.<br />
EQUIPMENT<br />
SELECTOR<br />
Typical<br />
Fan<br />
Coil<br />
FK/FV<br />
Series<br />
Fan<br />
Coil<br />
1–Stage<br />
Furnace<br />
2–Stage<br />
Furnace<br />
Variable<br />
Speed<br />
2–Stage<br />
Non-Condensing<br />
Furnace<br />
Variable<br />
Speed<br />
2–Stage<br />
Condensing<br />
Furnace<br />
With DE<br />
Connection<br />
<strong>Wiring</strong> Diagram Refrence Chart<br />
SINGLE<br />
SPEED<br />
AIR<br />
CONDITIONER<br />
TWO<br />
SPEED<br />
AIR<br />
CONDITIONER<br />
SINGLE<br />
SPEED<br />
HEAT<br />
PUMP<br />
11. To activate dehumidify feature on older style variable-speed<br />
furnaces (<strong>Carrier</strong> 58MVP) that do not have a DE connection,<br />
a pilot duty 24-vac relay must be used.<br />
12. To activate dehumidify feature on current style variable-speed<br />
80 percent non-condensing furnace, disconnect green (DE-<br />
HUM) wire from G on furnace control board and connect to<br />
dehumidify terminal on Thermidistat Control.<br />
13. Dip switch No. 1 should be set in OFFposition for air<br />
conditioner installations. This is factory default.<br />
14. Dip switch No. 1 should be set in ON position for heat pump<br />
installations.<br />
15. Dip switch No. 2 should be set in OFF position for singlespeed<br />
compressor operation. This is factory default.<br />
16. Dip switch No. 2 should be set in ON position for 2-speed<br />
compressor operation.<br />
17. Configuration Option No. 10 ″Dual Fuel Selection″ must be<br />
turned ON in all dual fuel applications.<br />
18. Remove DE jumper to enable DEHUM input on furnace<br />
control board.<br />
19. No connection should be made to the furnace HUM terminal.<br />
TWO<br />
SPEED<br />
HEAT<br />
PUMP<br />
Fig. 1 Fig. 2 Fig. 3 Fig. 4<br />
Fig. 5 Fig. 6 Fig. 7 Fig. 8<br />
Fig. 9 Fig. 10 Fig. 11 Fig. 12<br />
Fig. 13 Fig. 14 Fig. 15 Fig. 16<br />
Fig. 17 Fig. 18 Fig. 19 Fig. 20<br />
Fig. 21 Fig. 22 Fig. 23 Fig. 24<br />
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.<br />
Book 1 4 PC 101 Catalog No. 03TS-TA38 Printed in U.S.A. Form TSTAT–3W Pg 1 2–02 Replaces: TSTAT-2W<br />
Tab 3a 2a
THERMIDISTAT<br />
TYPICAL<br />
FAN COIL<br />
1-SPEED<br />
AIR CONDITIONER<br />
THERMIDISTAT<br />
TYPICAL<br />
FAN COIL<br />
2-SPEED<br />
AIR CONDITIONER<br />
HEAT STAGE 2<br />
O/W2<br />
E<br />
COOL STAGE 1<br />
Y1/W2<br />
E<br />
Y1<br />
N/A<br />
Y1/W2<br />
W3<br />
HEAT STAGE 2<br />
O/W2<br />
W3<br />
HEAT STAGE 1<br />
W/W1<br />
W2<br />
HEAT STAGE 1<br />
W/W1<br />
W2<br />
COOL STAGE 1<br />
Y/Y2<br />
Y<br />
Y<br />
COOL STAGE 2<br />
Y/Y2<br />
Y<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
N/A<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 6, 13, and 15<br />
Fig. 1—Typical Fan Coil With<br />
1–Speed Air Conditioner<br />
A99184<br />
See notes 1, 6, 13, and 16<br />
Fig. 2—Typical Fan Coil With<br />
2–Speed Air Conditioner<br />
A99185<br />
THERMIDISTAT<br />
TYPICAL<br />
FAN COIL<br />
1-SPEED<br />
HEAT PUMP<br />
THERMIDISTAT<br />
TYPICAL<br />
FAN COIL<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
HEAT STAGE 3<br />
HEAT STAGE 2<br />
HEAT/COOL<br />
STAGE 1<br />
FAN<br />
24 VAC HOT<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
E<br />
W3<br />
W2<br />
Y<br />
G<br />
R<br />
O<br />
W2<br />
Y<br />
R<br />
RVS COOLING<br />
HEAT/COOL<br />
STAGE 1<br />
HEAT STAGE 3<br />
HEAT/COOL<br />
STAGE 2<br />
FAN<br />
24 VAC HOT<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
E<br />
W3<br />
W2<br />
Y<br />
G<br />
R<br />
O<br />
Y1<br />
W1<br />
Y2<br />
R<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
HUMIDIFY<br />
RVS HEATING<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 7, 14, and 15<br />
Fig. 3—Typical Fan Coil With<br />
1–Speed Heat Pump<br />
A99186<br />
N/A<br />
HUMIDIFY<br />
RVS HEAT<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 4, 5, 14, and 16<br />
Fig. 4—Typical Fan Coil With<br />
2–Speed Heat Pump<br />
A02007<br />
2
THERMIDISTAT<br />
FK AND FV<br />
SERIES<br />
FAN COIL<br />
1-SPEED<br />
AIR CONDITIONER<br />
THERMIDISTAT<br />
FK AND FV<br />
SERIES<br />
FAN COIL<br />
2-SPEED<br />
AIR CONDITIONER<br />
HEAT STAGE 2<br />
N/A<br />
O/W2<br />
Y1/W2<br />
W2<br />
Y1<br />
REMOVE J2 JUMPER<br />
FOR HEAT STAGING<br />
HEAT STAGE 2<br />
HEAT STAGE 1<br />
O/W2<br />
W/W1<br />
W2<br />
W1<br />
REMOVE J2 JUMPER<br />
FOR HEAT STAGING<br />
HEAT STAGE 1<br />
W/W1<br />
W1<br />
COOL STAGE 1<br />
Y1/W2<br />
Y1<br />
Y1<br />
COOL STAGE 1<br />
Y/Y2<br />
Y/Y2<br />
Y<br />
COOL STAGE 2<br />
Y/Y2<br />
Y/Y2<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
R<br />
DHUM<br />
R<br />
O<br />
DH<br />
REMOVE<br />
J1 JUMPER<br />
FOR<br />
DEHUMIDIFY<br />
MODES<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
R<br />
DHUM<br />
R<br />
O<br />
DH<br />
R<br />
REMOVE<br />
J1 JUMPER<br />
FOR<br />
DEHUMIDIFY<br />
MODES<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 2, 6, 13, and 15<br />
See notes 1, 2, 6, 13, and 16<br />
Fig. 5—FK and FV Series Fan Coil With<br />
1–Speed Air Conditioner<br />
A99188<br />
Fig. 6—FK and FV Series Fan Coil With<br />
2–Speed Air Conditioner<br />
A99189<br />
THERMIDISTAT<br />
FK AND FV<br />
SERIES<br />
FAN COIL<br />
1-SPEED<br />
HEAT PUMP<br />
THERMIDISTAT<br />
FK AND FV<br />
SERIES<br />
FAN COIL<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
HEAT STAGE 3<br />
O/W2<br />
Y1/W2<br />
O<br />
W2<br />
O<br />
REMOVE J2 JUMPER<br />
FOR HEAT STAGING<br />
RVS COOLING<br />
HEAT/COOL<br />
STAGE 1<br />
O/W2<br />
Y1/W2<br />
O<br />
Y1<br />
O<br />
Y1<br />
HEAT STAGE 2<br />
HEAT/COOL<br />
STAGE 1<br />
W/W1<br />
Y/Y2<br />
W1<br />
Y/Y2<br />
W2<br />
Y<br />
HEAT STAGE 3<br />
HEAT/COOL<br />
STAGE 2<br />
W/W1<br />
Y/Y2<br />
W1<br />
W2<br />
W1<br />
J2 JUMPER<br />
FOR HEAT STAGING<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
Y/Y2<br />
Y2<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
24 VAC COMM<br />
R<br />
DHUM<br />
C<br />
R<br />
Y1<br />
DH<br />
COM<br />
R<br />
REMOVE<br />
J1 JUMPER<br />
FOR<br />
DEHUMIDIFY<br />
MODES<br />
C<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
24 VAC COMM<br />
R<br />
DHUM<br />
C<br />
G<br />
R<br />
DH<br />
COM<br />
REMOVE J1<br />
JUMPER<br />
FOR<br />
DEHUMIDIFY<br />
MODES<br />
R<br />
C<br />
HUMIDIFY<br />
RVS HEATING<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 2, 7, 14, and 15<br />
Fig. 7—FK and FV Series Fan Coil With<br />
1–Speed Heat Pump<br />
A99190<br />
HUMIDIFY<br />
RVS HEATING<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 1, 2, 4, 5, 14, and 16<br />
Fig. 8—FK and FV Series Fan Coil WIth<br />
2–Speed Heat Pump<br />
A02008<br />
3
THERMIDISTAT<br />
1-STAGE<br />
FURNACE<br />
1-SPEED<br />
AIR CONDITIONER<br />
THERMIDISTAT<br />
1-STAGE<br />
FURNACE<br />
2-SPEED<br />
AIR CONDITIONER<br />
N/A<br />
O/W2<br />
N/A<br />
O/W2<br />
N/A<br />
Y1/W2<br />
COOL STAGE 1<br />
Y1/W2<br />
Y1<br />
HEAT STAGE 1<br />
W/W1<br />
W<br />
HEAT STAGE 1<br />
W/W1<br />
W<br />
COOL STAGE 1<br />
Y/Y2<br />
Y<br />
Y<br />
COOL STAGE 2<br />
Y/Y2<br />
Y<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
HUM<br />
HUM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
DHUM<br />
N/A<br />
DHUM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 13, 15, and 19<br />
See notes 13, 16, and 19<br />
Fig. 9—Single-Stage Furnace With<br />
1–Speed Air Conditioner<br />
A99192<br />
Fig. 10—Single-Stage Furnace With<br />
2–Speed Air Conditioner<br />
A99193<br />
THERMIDISTAT<br />
1-STAGE<br />
FURNACE<br />
1-SPEED<br />
HEAT PUMP<br />
THERMIDISTAT<br />
1-STAGE<br />
FURNACE<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
HEAT STAGE 2<br />
(FURNACE)<br />
HEAT/COOL<br />
STAGE 1<br />
(COMPRESSOR)<br />
O/W2<br />
N/A Y1/W2<br />
FAN<br />
W/W1<br />
Y/Y2<br />
G<br />
W<br />
Y<br />
G<br />
O<br />
W2<br />
Y<br />
RVS COOLING<br />
HEAT/COOL<br />
STAGE 1<br />
(COMPRESSOR LO)<br />
HEAT STAGE 3<br />
(FURNACE)<br />
HEAT/COOL<br />
STAGE 2<br />
(COMPRESSOR HI)<br />
FAN<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
W<br />
Y<br />
G<br />
O<br />
Y1<br />
W1<br />
Y2<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
HUM<br />
HUM<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
DHUM<br />
N/A<br />
DHUM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 3, 9, 14, 15, 17, and 19<br />
Fig. 11—Single-Stage Furnace With<br />
1–Speed Heat Pump (Dual Fuel)<br />
A99194<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 3, 4, 5, 9, 14, 16, 17, and 19<br />
Fig. 12—Single-Stage Furnace With<br />
2–Speed Heat Pump (Dual Fuel)<br />
A02009<br />
4
THERMIDISTAT<br />
2-STAGE<br />
FURNACE<br />
1-SPEED<br />
AIR CONDITIONER<br />
THERMIDISTAT<br />
2-STAGE<br />
FURNACE<br />
2-SPEED<br />
AIR CONDITIONER<br />
HEAT STAGE 2<br />
O/W2<br />
W2<br />
HEAT STAGE 2<br />
O/W2<br />
W2<br />
N/A<br />
Y1/W2<br />
COOL STAGE 1<br />
Y1/W2<br />
Y1<br />
HEAT STAGE 1<br />
W/W1<br />
W/W1<br />
HEAT STAGE 1<br />
W/W1<br />
W/W1<br />
COOL STAGE 1<br />
Y/Y2<br />
Y/Y2<br />
Y<br />
COOL STAGE 2<br />
Y/Y2<br />
Y/Y2<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
HUM<br />
HUM<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
DHUM<br />
N/A<br />
DHUM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 6, 13, 15, and 19<br />
See notes 6, 13, 16, and 19<br />
Fig. 13—Two-Stage Furance With<br />
1–Speed Air Conditioner<br />
A99196<br />
Fig. 14—Two-Stage Furance With<br />
2–Speed Air Conditioner<br />
A99197<br />
THERMIDISTAT<br />
2-STAGE<br />
FURNACE<br />
1-SPEED<br />
HEAT PUMP<br />
THERMIDISTAT<br />
2-STAGE<br />
FURNACE<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
HEAT STAGE 3<br />
(FURNACE HI)<br />
HEAT STAGE 2<br />
(FURNACE LO)<br />
HEAT/COOL<br />
STAGE 1<br />
(COMPRESSOR)<br />
FAN<br />
24 VAC HOT<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
O<br />
W2<br />
Y<br />
R<br />
RVS COOLING<br />
HEAT/COOL<br />
STAGE 1<br />
(COMPRESSOR LO)<br />
HEAT STAGE 3<br />
(FURNACE)<br />
HEAT/COOL<br />
STAGE 2<br />
(COMPRESSOR HI)<br />
FAN<br />
24 VAC HOT<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
O<br />
Y1<br />
W1<br />
Y2<br />
R<br />
HUM<br />
HUM<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
N/A<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 3, 7, 9, 10, 14, 15, 17, and 19<br />
A99198<br />
Fig. 15—Two-Stage Furnace With<br />
1–Speed Heat Pump (Dual Fuel)<br />
N/A<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 3, 4, 5, 8, 9, 10, 14, 16, 17, and 19<br />
Fig. 16—Two-Stage Furnace With<br />
2–Speed Heat Pump (Dual Fuel)<br />
A02010<br />
5
VARIABLE SPEED 80% NON-CONDENSING FURNACE<br />
THERMIDISTAT<br />
HEAT STAGE 2<br />
N/A<br />
HEAT STAGE 1<br />
COOL STAGE 1<br />
FAN<br />
24 VAC HOT<br />
24 VAC COM<br />
DEHUMIDIFY<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTIONS<br />
O/W2<br />
Y1/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
C<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
O<br />
Y1<br />
FURNACE<br />
BOARD<br />
DEHUM<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
COM<br />
HUM<br />
PL9-10<br />
AIR FLOW<br />
SELECT<br />
BOARD<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
1-SPEED<br />
AIR CONDITIONER<br />
See notes 6, 10, 12, 13, 15, and 19<br />
A99200<br />
Fig. 17—Variable-Speed 2–Stage Non-Condensing<br />
Furnace With 1–Speed Air Conditioner<br />
Y<br />
C<br />
VARIABLE SPEED 80% NON-CONDENSING FURNACE<br />
THERMIDISTAT<br />
COOL STAGE 1<br />
HEAT STAGE 2<br />
HEAT STAGE 1<br />
COOL STAGE 2<br />
FAN<br />
24 VAC HOT<br />
24 VAC COM<br />
DEHUMIDIFY<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTIONS<br />
Y1/W2<br />
O/W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
C<br />
DHUM<br />
HUM<br />
B<br />
S1<br />
S2<br />
O<br />
Y1<br />
DEHUM<br />
FURNACE<br />
BOARD<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
COM<br />
HUM<br />
PL9-10<br />
AIR FLOW<br />
SELECT<br />
BOARD<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
2-SPEED<br />
AIR CONDITIONER<br />
See notes 6, 9, 10, 12, 13, 16, and 19<br />
A99201<br />
Fig. 18—Variable-Speed 2–Stage Non-Condensing<br />
Furnace With 2–Speed Air Conditioner<br />
Y1<br />
Y2<br />
R<br />
C<br />
VARIABLE SPEED 80% NON-CONDENSING FURNACE<br />
THERMIDISTAT<br />
O<br />
Y1<br />
AIR FLOW<br />
SELECT<br />
BOARD<br />
1-SPEED<br />
HEAT PUMP<br />
VARIABLE SPEED 80% NON-CONDENSING FURNACE<br />
THERMIDISTAT<br />
O<br />
Y1<br />
AIR FLOW<br />
SELECT<br />
BOARD<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
O/W2<br />
FURNACE<br />
BOARD<br />
O<br />
RVS COOLING<br />
O/W2<br />
FURNACE<br />
BOARD<br />
O<br />
HEAT STAGE 3<br />
Y1/W2<br />
W2<br />
HEAT/COOL<br />
STAGE 1<br />
Y1/W2<br />
W2<br />
Y1<br />
HEAT STAGE 2<br />
HEAT/COOL<br />
STAGE 1<br />
W/W1<br />
Y/Y2<br />
W/W1<br />
Y/Y2<br />
W2<br />
Y<br />
HEAT STAGE 3<br />
HEAT/COOL<br />
STAGE 2<br />
W/W1<br />
Y/Y2<br />
W/W1<br />
Y/Y2<br />
W1<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
24 VAC COM<br />
C<br />
COM<br />
C<br />
24 VAC COM<br />
C<br />
COM<br />
C<br />
DEHUMIDIFY<br />
DHUM<br />
HUM<br />
DEHUMIDIFY<br />
DHUM<br />
HUM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTIONS<br />
HUM<br />
B<br />
S1<br />
S2<br />
DEHUM<br />
PL9-10<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTIONS<br />
HUM<br />
B<br />
S1<br />
S2<br />
DEHUM<br />
PL9-10<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 3, 7, 9, 10, 12, 14, 15, 17, and 19<br />
A99202<br />
Fig. 19—Variable-Speed 2–Stage Non-Condensing<br />
Furnace With 1–Speed Heat Pump (Dual Fuel)<br />
See notes 3, 4, 5, 8, 9, 10, 12, 14, 16, 17, and 19<br />
A02011<br />
Fig. 20—Variable-Speed 2–Stage Non-Condensing<br />
Furnace With 2–Speed Heat Pump (Dual Fuel)<br />
6
THERMIDISTAT<br />
VARIABLE-SPEED<br />
CONDENSING<br />
FURNACE<br />
THERMIDISTAT<br />
VARIABLE-SPEED<br />
CONDENSING<br />
FURNACE<br />
2-SPEED<br />
AIR CONDITIONER<br />
HEAT STAGE 2<br />
N/A<br />
O/W2<br />
Y1/W2<br />
W2<br />
1-SPEED<br />
AIR CONDITIONER<br />
HEAT STAGE 2<br />
COOL STAGE 1<br />
O/W2<br />
Y1/W2<br />
W2<br />
Y1<br />
HEAT STAGE 1<br />
W/W1<br />
W/W1<br />
HEAT STAGE 1<br />
W/W1<br />
W/W1<br />
COOL STAGE 1<br />
Y/Y2<br />
Y/Y2<br />
Y<br />
COOL STAGE 2<br />
Y/Y2<br />
Y/Y2<br />
Y2<br />
FAN<br />
G<br />
G<br />
FAN<br />
G<br />
G<br />
24 VAC HOT<br />
R<br />
R<br />
24 VAC HOT<br />
R<br />
R<br />
R<br />
DEHUMIDIFY<br />
DHUM<br />
DEHUM<br />
DEHUMIDIFY<br />
DHUM<br />
DEHUM<br />
DE<br />
NOTE 18<br />
DE<br />
NOTE 18<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
24 VAC COMM<br />
C<br />
COM<br />
C<br />
HUM<br />
HUM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 6, 10, 11, 13, 15, 18, and 19<br />
Fig. 21—Variable-Speed Condensing<br />
Furnace — With DE Connection —<br />
With 1–Speed Air Conditioner<br />
A99208<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
See notes 6, 10, 11, 13, 16, 18, and 19<br />
A99209<br />
Fig. 22—Variable-Speed 2–Stage Condensing<br />
Furance — With DE Connection —<br />
With 2–Speed Air Conditioner<br />
THERMIDISTAT<br />
VARIABLE-SPEED<br />
CONDENSING<br />
FURNACE<br />
1-SPEED<br />
HEAT PUMP<br />
THERMIDISTAT<br />
VARIABLE-SPEED<br />
CONDENSING<br />
FURNACE<br />
2-SPEED<br />
HEAT PUMP<br />
RVS COOLING<br />
O/W2<br />
HEAT STAGE 3<br />
(FURNACE HI)<br />
Y1/W2<br />
HEAT STAGE 2<br />
(FURNACE LO) W/W1<br />
HEAT/COOL STAGE 1<br />
(COMPRESSOR)<br />
FAN<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
24 VAC COMM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
Y/Y2<br />
G<br />
R<br />
DHUM<br />
C<br />
HUM<br />
B<br />
S1<br />
S2<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
See notes 3, 7, 9, 10, 11, 14, 15, 17, 18, and 19<br />
A99210<br />
Fig. 23—Variable-Speed 2–Stage Condensing<br />
Furnace — With DE Connection —<br />
With 1–Speed Heat Pump (Dual Fuel)<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
DEHUM<br />
DE<br />
NOTE 18<br />
COM<br />
HUM<br />
OUTDOOR<br />
SENSOR<br />
O<br />
W2<br />
Y<br />
R<br />
C<br />
RVS COOLING O/W2<br />
HEAT/COOL<br />
STAGE 1 Y1/W2<br />
(COMPRESSOR LO)<br />
HEAT STAGE 3<br />
(FURNACE) W/W1<br />
HEAT/COOL<br />
STAGE 2 Y/Y2<br />
(COMPRESSOR HI)<br />
FAN G<br />
24 VAC HOT<br />
DEHUMIDIFY<br />
24 VAC COMM<br />
HUMIDIFY<br />
N/A<br />
OUTDOOR<br />
SENSOR<br />
CONNECTION<br />
R<br />
DHUM<br />
C<br />
HUM<br />
B<br />
S1<br />
S2<br />
W2<br />
W/W1<br />
Y/Y2<br />
G<br />
R<br />
DEHUM<br />
DE<br />
NOTE 18<br />
COM<br />
HUM<br />
HUMIDIFIER<br />
SOLENOID VALVE<br />
(24 VAC)<br />
OUTDOOR<br />
SENSOR<br />
Y1<br />
W1<br />
Y2<br />
See notes 3, 7, 9, 10, 11, 14, 15, 17, 18, and 19<br />
A02012<br />
Fig. 24—Variable-SPeed 2–Stage Condensing<br />
Furnace — With DE Connection —<br />
With 2–Speed Heat Pump (Dual Fuel)<br />
O<br />
R<br />
C<br />
7
Copyright 2002 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231<br />