Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />
Division 15, Section 15800<br />
2005 Master Spec Format (Section/Category): 23 37 16<br />
c. DESIGN PARAMETERS<br />
1. Use fabric air diffusers only for positive pressure air distribution.<br />
2. Do not use fabric air diffusers in concealed locations.<br />
3. Fabric diffusers shall be designed from minimum 0.25” water gage to 3” as the maximum – 0.5”<br />
being the standard.<br />
4. Design temperatures between –40°F and 140°F<br />
5. Manufacturer shall approve all technical design parameters.<br />
d. HANGERS AND SUPPORT (must specify only one of the below system types)<br />
1. Type 1: One row cable system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system. Fabric<strong>Air</strong> ®<br />
system to be attached to hardware using one single row of plastic hooks located 12 o’clock<br />
spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down straps as<br />
required.<br />
Hardware options – (please select one)<br />
a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />
b. Stainless Steel Cable – all other components Stainless Steel<br />
c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />
2. Type 2: Two rows cable system located 1.5” above 3 & 9 o’clock of Fabric<strong>Air</strong> ® system.<br />
Fabric<strong>Air</strong> ® system to be attached to hardware using two rows of plastic hooks located 3 & 9<br />
o’clock spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down<br />
straps as required.<br />
Hardware options – (please select one)<br />
a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />
b. Stainless Steel Cable – all other components Stainless Steel<br />
c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />
3. Type 3: One row T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-rail<br />
and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single<br />
row of plastic sliders located 12 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />
4. Type 4: Two rows T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-<br />
rail and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using two rows<br />
of plastic sliders located 3 & 9 o’clock spaced 20 inches.<br />
Hardware options – (please select one)<br />
a. Aluminum Rails – all other components Stainless Steel<br />
b. Aluminum Rails – all other components Galvanized Steel<br />