Specification: Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> – <strong>NozzFlow</strong><br />

Division 15, Section 15800<br />

2005 Master Spec Format (Section/Category): 23 37 16<br />

c. DESIGN PARAMETERS<br />

1. Use fabric air diffusers only for positive pressure air distribution.<br />

2. Do not use fabric air diffusers in concealed locations.<br />

3. Fabric diffusers shall be designed from minimum 0.25” water gage to 3” as the maximum – 0.5”<br />

being the standard.<br />

4. Design temperatures between –40°F and 140°F<br />

5. Manufacturer shall approve all technical design parameters.<br />

d. HANGERS AND SUPPORT (must specify only one of the below system types)<br />

1. Type 1: One row cable system located 1.5” above 12 o’clock of Fabric<strong>Air</strong> ® system. Fabric<strong>Air</strong> ®<br />

system to be attached to hardware using one single row of plastic hooks located 12 o’clock<br />

spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down straps as<br />

required.<br />

Hardware options – (please select one)<br />

a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />

b. Stainless Steel Cable – all other components Stainless Steel<br />

c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />

2. Type 2: Two rows cable system located 1.5” above 3 & 9 o’clock of Fabric<strong>Air</strong> ® system.<br />

Fabric<strong>Air</strong> ® system to be attached to hardware using two rows of plastic hooks located 3 & 9<br />

o’clock spaced 20 inches. Hardware to include cable, cable clamps, turnbuckles, and tie down<br />

straps as required.<br />

Hardware options – (please select one)<br />

a. Plastic Coated Stainless Steel Cable – all other components Stainless Steel<br />

b. Stainless Steel Cable – all other components Stainless Steel<br />

c. Plastic Coated Galvanized Cable – all other components Galvanized Steel<br />

3. Type 3: One row T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-rail<br />

and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using one single<br />

row of plastic sliders located 12 o’clock spaced 20 inches.<br />

Hardware options – (please select one)<br />

a. Aluminum Rails – all other components Stainless Steel<br />

b. Aluminum Rails – all other components Galvanized Steel<br />

4. Type 4: Two rows T-rail system fixed directly to ceiling. Hardware to include tie down strap, T-<br />

rail and end lock T-rail as required. Fabric<strong>Air</strong> ® system to be attached to hardware using two rows<br />

of plastic sliders located 3 & 9 o’clock spaced 20 inches.<br />

Hardware options – (please select one)<br />

a. Aluminum Rails – all other components Stainless Steel<br />

b. Aluminum Rails – all other components Galvanized Steel<br />

Fabric<strong>Air</strong> ® <strong>Trevira</strong> <strong>CS</strong> <strong>100</strong> - <strong>NozzFlow</strong> Last up-date: 06/2011<br />

Specification guidelines for Fabric<strong>Air</strong> ® products – subject to change without further notice. Page 3 of 5<br />

For more information, contact: Fabric<strong>Air</strong>, Inc.: info@fabricair.com or Phone: (502) 493 2210