INSTAPOWER<br />

<strong>Switch</strong>-mode power supplies<br />

connect<strong>Power</strong> single-phase<br />

CP SNT 24 W 28 V 1 A<br />

CP SNT 24 W 24 V 1 A<br />

A<br />

L<br />

AC/DC<br />

N<br />

PWM<br />

+<br />

–<br />

DC<br />

L<br />

N<br />

FUSE<br />

+<br />

−<br />

L<br />

N<br />

FUSE<br />

+<br />

−<br />

Technical data<br />

Input<br />

Input voltage<br />

Input current<br />

Input frequency<br />

Turn-on current limit<br />

Input fuse<br />

Surge protection<br />

Output<br />

Output voltage<br />

Output current<br />

Output power<br />

Max. residual ripple<br />

Overload protection<br />

85...265 V AC, 120...300 V DC<br />

460 mA @ 115 V AC; 250 mA @ 230 V AC<br />

50/ 60 Hz<br />

Thermistor<br />

2 A time-lag fuse (internal)<br />

Varistor<br />

28 V DC<br />

1 A<br />

28 W<br />

< 2 %<br />

Surge current / thermal cut-out<br />

85...265 V AC, 120...300 V DC<br />

460 mA @ 115 V AC; 250 mA @ 230 V AC<br />

50/ 60 Hz<br />

Thermistor<br />

2 A time-lag fuse (internal)<br />

Varistor<br />

24 V DC<br />

1 A<br />

24 W<br />

< 2 %<br />

Surge current / thermal cut-out<br />

Surge protection<br />

Mains failure bridge-over time<br />

Control at 10...100% load<br />

Max. capacitance at output<br />

Insulation coordination (EN 50178)<br />

Electrical isolation, output-earth<br />

Electrical isolation, input-earth<br />

Electrical isolation, input-output<br />

Electrical isolation, I/O rail<br />

General data<br />

Ambient temperature (operational)<br />

Storage temperature<br />

Degree of efficiency at max. load<br />

St<strong>and</strong>ards<br />

Approvals<br />

EMC st<strong>and</strong>ards<br />

Varistor<br />

35 ms @ 115 V AC / 160 ms @ 230 V AC<br />

0.5%<br />

8000 µF<br />

0.5 kV<br />

1.5 kV<br />

3 kV<br />

4 kV<br />

-20...+50 °C<br />

-40 °C...+85 °C<br />

78%<br />

DIN EN 50178, DIN EN 60950, IEC950<br />

CE; CSA; GOSTME25<br />

EN 61000-6 /-2, -3<br />

Varistor<br />

35 ms @ 115 V AC / 160 ms @ 230 V AC<br />

0.5%<br />

8000 µF<br />

0.5 kV<br />

1.5 kV<br />

3 kV<br />

4 kV<br />

-20...+50 °C<br />

-40 °C...+85 °C<br />

78%<br />

DIN EN 50178, DIN EN 60950, IEC950<br />

CE; CSA; CSAEX; GOSTME25<br />

EN 61000-6 /-2, -3<br />

Dimensions<br />

Clamping range (nominal / min. / max.)<br />

Height x width x depth<br />

Note<br />

mm²<br />

Input/Output<br />

4 / 0.08 / 4<br />

90.5 / 52 / 62.5 mm<br />

Derating loss: 33% @ 60°C The internal varistor found in a switch-mode power<br />

supply does not replace the need for surge protection within a system.<br />

Input/Output<br />

4 / 0.08 / 4<br />

90.5 / 52 / 62.5 mm<br />

Derating loss: 33% @ 60°C The internal varistor found in a switch-mode power<br />

supply does not replace the need for surge protection within a system.<br />

Ordering data<br />

Screw connection<br />

Type Qty. Order No.<br />

CP SNT 24W 28V 1A 1 9928890028<br />

Type Qty. Order No.<br />

CP SNT 24W 24V 1A 1 9928890024<br />

Note<br />