compact<strong>Power</strong><br />

Unregulated power supplies<br />

compact<strong>Power</strong> 3-phase<br />

CP NT3 500<br />

CP NT3 600<br />

PE<br />

INPUT<br />

OUTPUT<br />

400V -5% +<br />

+5% +5% +5%<br />

400V 400V<br />

-5% -5% 3x =<br />

+<br />

130° 24VDC<br />

-<br />

~<br />

-<br />

INPUT<br />

400V -5% +5% +5% +5%<br />

400V 400V<br />

-5% -5% 3x =<br />

130°<br />

PE<br />

~<br />

OUTPUT<br />

+<br />

+<br />

24VDC<br />

M<br />

-<br />

-<br />

0V<br />

Fail<br />

D<br />

Technical data<br />

Input<br />

Input voltage<br />

Input current<br />

Input frequency<br />

No-load input current<br />

Input fuse<br />

Ext. Back-up fuse<br />

Output<br />

Output voltage<br />

Output current at 40°C / 60°C<br />

Output power<br />

Max. residual ripple<br />

Fusing<br />

Protective circuit, load side<br />

Insulation coordination (EN 50178)<br />

Electric shock protection<br />

Insulation strength<br />

Insulation class<br />

Protection degree<br />

Class of protection<br />

General data<br />

Ambient temperature (operational)<br />

Storage temperature<br />

Degree of efficiency at max. load<br />

Installation advice<br />

Fan signal<br />

Height x width x depth<br />

Status indication<br />

Weight<br />

St<strong>and</strong>ards<br />

EMC st<strong>and</strong>ards<br />

Approvals<br />

3 x 400 V ±5 %<br />

0.9 A<br />

50/ 60 Hz<br />

0.13 A<br />

3 x primary thermostatic switch<br />

3 x 1.6 A time-lag<br />

24 V DC SELV<br />

22 A / 20 A<br />

500 W<br />

< 2 %<br />

External 20 / 22 A slo-blow<br />

Varistor<br />

acc. to BGV A3<br />

4 kV<br />

B<br />

IP 20<br />

I<br />

-20...+60 °C<br />

-20 °C...+80 °C<br />

78%<br />

Direct mounting<br />

No integrated fan<br />

215 / 108 / 220 mm<br />

Green LED<br />

10 kg<br />

DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG<br />

EN 61000-6 /-2, -3<br />

cCSAus; CE; cULus; GOSTME25<br />

3 x 400 V ±5 %<br />

1.2 A<br />

50/ 60 Hz<br />

0.15 A<br />

3 x primary thermostatic switch<br />

3 x 2 A time-lag<br />

24 V DC SELV<br />

26 A / 25 A<br />

600 W<br />

< 2 %<br />

External 25 / 26 A slo-blow<br />

Varistor<br />

acc. to BGV A3<br />

4 kV<br />

B<br />

IP 20<br />

I<br />

-20...+60 °C<br />

-20 °C...+80 °C<br />

78%<br />

Direct mounting<br />

Open collector