VAD-30F21<br />

Fan Outlet Area = 5.03 ft. 2 Max. Motor Frame Size = 365T Min. Motor Frame Size = 182T<br />

Cone Outlet Area = 7.22 ft. 2 Tip Speed = 7.92 x RPM<br />

Outlet Condition Corrections<br />

20<br />

Pressure Correction, Pc<br />

10<br />

6<br />

4<br />

2<br />

1<br />

0.6<br />

0.4<br />

0.2<br />

0.1<br />

0.06<br />

0.04<br />

Pt = Ps + Pc<br />

D<br />

C<br />

Pc = (<br />

CFM<br />

K<br />

B<br />

A<br />

(<br />

2<br />

A Ducted with cone K = 27,170<br />

B Ducted outlet K = 20,150<br />

C Free with cone K = 19,020<br />

D Free discharge K = 10,520<br />

0.02<br />

5<br />

6 7 8<br />

9<br />

10<br />

CFM x 1,000<br />

20 30 40 50<br />

VAD-30F21<br />

1170 RPM<br />

2.80<br />

7.0<br />

2.40<br />

40°<br />

6.0<br />

Total Pressure (in. wg)<br />

2.00<br />

1.60<br />

1.20<br />

0.80<br />

0.40<br />

10°<br />

15°<br />

20°<br />

25°<br />

30°<br />

35°<br />

74%<br />

25°<br />

20°<br />

15°<br />

0.00 10°<br />

0.0<br />

0 2 4 6 8 10 12 14 16 18 20<br />

70%<br />

65%<br />

CFM x 1,000<br />

60%<br />

55%<br />

50%<br />

45%<br />

30°<br />

35°<br />

40°<br />

5.0<br />

4.0<br />

3.0<br />

2.0<br />

1.0<br />

Horsepower<br />

Performance certified is for model VAD installation type D: Ducted inlet, Ducted outlet. Power ratings (Bhp) do not include transmission losses.<br />

Performance ratings do not include the effects of appurtenances (accessories).<br />