Deutschmann Automation GmbH & Co. KG<br />

Implemented protocols in UNIGATE <strong>CL</strong> with Universal Script<br />

10 Implemented protocols in UNIGATE <strong>CL</strong> with Universal<br />

Script<br />

UNIGATE <strong>CL</strong> is supplied with the Script “Universal Script Deutschmann“. The configuration of<br />

the protocols is carried out by means of the software WINGATE.<br />

Attention:<br />

The "Universal Script" will get lost and has to be input again if a Reset<br />

Device is carried out.<br />

The Script can be found on the Deutschmann Support-CD in the folder<br />

\Software\ProtocolDeveloper\Example\Universal\<br />

10.1 Protokoll: Transparent<br />

The data is transferred bidirectional from the UNIGATE.<br />

10.1.1 Data structure<br />

On the RS-entry side the timeout time of 2 ms is firmly set. If no more data is received within the<br />

timeout period, then the data that has been received so far is transferred to the bus.<br />

If less data is received through Rx then configured by the GSDML-file (I/O-length), then the rest<br />

is complemented with ZERO.<br />

Too much data received will be cut off.<br />

10.2 Protocol: Universal 232<br />

The protocol designation "Universal 232" and the relation to the<br />

"RS232-interface" in the description have eveloped over the years. The<br />

protocol also works with RS422 and RS485 though!<br />

10.2.1 Data structure<br />

10.2.2 Fieldbus parameters<br />

Trigger byte: See "The trigger byte", Chapter 10.5‚ on page 26<br />

Length byte: See "The length byte", Chapter 10.6‚ on page 26<br />

3.12.10 UNIGATE fieldbus gateway UNIGATE <strong>CL</strong> - <strong>Profinet</strong> V. 2.3 21