AUTOMATIC<br />

FUSES<br />

Loading of automatic fuses. Supply current differing from the nominal current value of the luminaire make correct dimensioning<br />

of the fuses protecting the circuit necessary. In the following a guideline to the maximum number of light sources that can be<br />

switched via a one pole automatic fuse. If multiple pole fuses are used, this figure is reduced by 20%. The data can differ according<br />

to manufacturer. The basis for the data is always the technical data sheet of the electronic control gears used in the luminaries.<br />

neon lamps/compact neon lamps<br />

lamp type<br />

Fq<br />

switch off characteristic<br />

protection value (Ampere)<br />

ECG 1 or 2 lamps<br />

B<br />

10<br />

1 lamps<br />

B<br />

10<br />

2 lamps<br />

B<br />

16<br />

1 lamps<br />

number of lamps<br />

FH 14 W 37 12 61 19<br />

FH 21 W 25 12 41 19<br />

FH 28 W 17 12 41 19<br />

FH 35 W 17 8 28 13<br />

FQ 24 W 25 12 41 19<br />

FQ 39 W 25 8 41 13<br />

FQ 54 W 17 8 28 13<br />

FQ 49 W 17 8 28 13<br />

FQ 80 W 8 o.A. 13 o.A.<br />

FC 22 W 15 25 25 25<br />

FC 40 W 12 19 19 19<br />

FC 55 W 8 13 13 13<br />

TC-L 18 W 26 13 32 16<br />

TC-L 24 W 26 10 32 16<br />

TC-L 36 W 26 8 32 12<br />

TC-L 40 W 18 8 26 12<br />

TC-L 55 W 18 8 26 12<br />

TC-L 80 W o.A. o.A. o.A. o.A.<br />

TC-DE/TE 13 15 13 25 21<br />

TC-DE/TE 18 15 13 25 21<br />

TC-DE/TE 26 12 8 25 19<br />

TC-TE 32 12 8 25 13<br />

TC-TE 42 12 8 19 13<br />

TC-TE 57 12 o.A. 19 o.A.<br />

B<br />

16<br />

2 lamps<br />

discharge lamps<br />

lamps type<br />

switch off characteristic<br />

protection value (Ampere)<br />

CG type<br />

B<br />

10<br />

ECG<br />

B<br />

10<br />

CCG<br />

B<br />

16<br />

ECG<br />

B<br />

16<br />

CCG<br />

C<br />

10<br />

ECG<br />

number of luminaires<br />

CDM-T / TC 35 W 8 11 14 18 16 22 28 36<br />

C<br />

10<br />

CCG<br />

C<br />

16<br />

ECG<br />

C<br />

16<br />

CCG<br />

CDM-DE / T / TC 70 W 6 6 13 12 10 12 26 23<br />

CDM -DE / T 150 W 4 4 7 7 7 7 20 14<br />

HQI-E 250 W 3 5 5 10<br />

HQI-E 400 W 2 3 3 6<br />

SDW-T 50 W 8 15 18 31<br />

SDW-T 100 W 5 10 10 20<br />

SDW-TG 100 W 5 10 8 22<br />