<strong>UL</strong> <strong>Low</strong> <strong>Voltage</strong> <strong>General</strong><br />

<strong>Purpose</strong> <strong>Protection</strong><br />

<strong>Modular</strong> <strong>fuse</strong>-<strong>holders</strong><br />

UltraSafe US14<br />

UltraSafe <strong>fuse</strong>-<strong>holders</strong> for all types of 14x51 <strong>fuse</strong>-links<br />

No of<br />

Poles<br />

Catalog Number<br />

with auxiliary<br />

microswitch<br />

Reference Number<br />

with auxiliary<br />

microswitch<br />

Catalog Number with<br />

auxiliary microswitch &<br />

indicator light<br />

Reference Number with<br />

auxiliary microswitch &<br />

indicator light<br />

No of<br />

Mod.<br />

(17.5mm)<br />

1 US141M W227903 US141MI C331156 1.5 6<br />

1 + N US141NM A227907 US141NMI B227908 3 3<br />

2 US142M E227911 US142MI K331140 3 3<br />

2* US142M2 G227913 US142M2I M331142 3 3<br />

3 US143M L227917 US143MI S331147 4.5 2<br />

3* US143M2 N227919 US143M2I W331150 4.5 2<br />

3 + N US143NM S227923 US143NMI T227924 6 1<br />

3 + N* US143NM2 V227925 US143NM2I W227926 6 1<br />

4 US144M - US144MI - 6 1<br />

4* US144M2 - US144M2I - 6 1<br />

* Two auxiliary microswitches (see instructions for mounting) - The auxiliary microswitch function requires use of <strong>fuse</strong>s with strikers.<br />

Models without indicator light and with auxiliary microswitch can be equipped with indicator kit and auxiliary microswitch kit.<br />

Pack.<br />

Technical characteristics<br />

Shock and vibration<br />

Vibration withstand on the 3 main axis*:<br />

• Sinusoidal vibration testing according to IEC 60068-2-6<br />

13 to 100Hz y= 0.7g peak<br />

according to french marine application<br />

2 to 13Hz x= 1 mm peak<br />

• Random vibration testing according to IEC 61373<br />

Category Class B<br />

Shock withstand on the 3 main axis*:<br />

• Shock testing according to IEC 60068-2-27 15g/11ms/18 shocks<br />

• Shock testing according to IEC 61373 Category 1 Class B<br />

*For specific usage please consult us<br />

Plastic material<br />

Plastic material <strong>UL</strong>94V2 mini<br />

Flame retardant materials with glow wire flammability<br />

index to 960°C<br />

Operating temperature: -25°C +60°C(1)<br />

Storage temperature: -25°C +80°C<br />

(1) See derating table<br />

Connection<br />

Max. tightening torque: 3.5Nm (30Ibs.-in.)<br />

Wire range<br />

• Rigid wire = 1.5-35mm² (16-3AWG)<br />

• Multistrand wire = 25mm² (4AWG)<br />

PZ2 or flat 5.5x1mm screw drivers recommended<br />

(max. diameter 6mm)<br />

Specific usage conditions<br />

Ambient temperature >20°C 30°C 40°C 50°C 60°C<br />

Derating factor of current 1 0.95 0.9 0.8 0.7<br />

No of poles 1 to 3 4 to 6 >/= 7<br />

Derating factor of current 1 0.95 0.9<br />

Nominal Current (A)<br />

of <strong>fuse</strong>-link gR<br />

Max. operational current in<br />

<strong>fuse</strong>-holder (A)<br />

25 23 4<br />

32 28 6<br />

40 34 10<br />

50 40 10<br />

63 46 16<br />

Cable wire<br />

section (mm²)