Technical Specification<br />

<strong>3UF5</strong>0 basic unit, <strong>3UF5</strong>1 extansion module, <strong>3UF5</strong>2 operator panel, 3WX3G h<strong>and</strong>-held-unit<br />

Permiss. ambient/storage temperature -25 °C to +60 °C/ -40 °C to +80 °C<br />

Site altitude<br />

up to 2000 m above sea level<br />

Degree of protection (in acc. IEC 529) IP 20 max. setting curent I e w 100 A; IP 00 max. setting current I e > 100 A;<br />

Shock resistance (sinewave)<br />

Mounting position<br />

Mounting<br />

10 g/5 ms<br />

free choice<br />

max. setting current I e w 100 A: snap-on mounting onto 35 mm top-hat rail or screw fixing<br />

with insertion clip<br />

max. setting current I e > 100 A: screw fixing directly to contactor of srewfiring<br />

EMC interference immunity Conducted interference, burst in acc. with IEC 61000-4-4: 2 kV (corr. to severity 3)<br />

Conducted interference, surge in acc. with IEC 61000-4-5: 2 kV (corr. to severity 3)<br />

Electrostatic discharge in acc. with IEC 61000-4-2: 8 kV (corr. to severity 3)<br />

Field-related interference in acc. with IEC 61000-4-3: 3 V/m (corr. to severity 2)<br />

(see special notes in the manual)<br />

EMC emitted interference Limit value class A in acc. with EN 55011 1991<br />

<strong>3UF5</strong>0 basic unit<br />

Display<br />

green LED „Ready“<br />

green LED „Bus“<br />

red LED „General Fault“<br />

Buttons<br />

Test/Reset<br />

<strong>System</strong> interface<br />

PROFIBUS-<strong>DP</strong> interface<br />

Main circuit<br />

Permanent light “Ready“<br />

Off “no control supply voltage“ or “function test negative, device blocked“<br />

Permanent light “Bus operation“<br />

Permanent light/flashing light “Branch fault“,␣␣e.g. overload tripping<br />

By pressing the Test/Reset button the device can be reset after a tripping or it can be<br />

tested as to its functionality<br />

RS232 for connection of extension module, operating module, manual operating device or PC<br />

RS485 for connection of the PROFIBUS-<strong>DP</strong> line via terminals (connection cross-section<br />

as with auxiliary contactors or via 9-pole SUB-D socket)<br />

Rated insulation voltage U I 690 V for blank/uninsulated conductor (<strong>3UF5</strong>001 - <strong>3UF5</strong>021)<br />

} for pollution degree 3<br />

1000 V for insulated conductor <strong>3UF5</strong>031 - <strong>3UF5</strong>051<br />

1000 V for blank/uninsulated conductor (<strong>3UF5</strong>031 <strong>and</strong> <strong>3UF5</strong>051)<br />

Rated impulse strength U imp<br />

6 kV <strong>3UF5</strong>001 - <strong>3UF5</strong>021<br />

8 kV <strong>3UF5</strong>031 - <strong>3UF5</strong>051<br />

Rated frequency <strong>and</strong> current type<br />

50 Hz/60 Hz; three-phase AC<br />

Diameter of push-through openings 10 mm (devices with max. setting current I e w 25 A)<br />

(max. I e w 100 A) 15 mm (devices with max. setting current I e 100 A)<br />

for devices with setting current I e >100 A: mounting with connection bars<br />

Busbar connection (Current range) 50 to 205 A 125 to 500 A 200 to 820 A<br />

Torque M8: 10 to 14 Nm M10: 14 to 24 Nm M10: 14 to 24 Nm<br />

M12: 20 to 35 Nm<br />

Flexible with cable lug 35 to 95 mm 2 50 to 240 mm 2 50 to 240 mm 2<br />

Str<strong>and</strong>ed with cable lug 50 to 120 mm 2 70 to 240 mm 2 70 to 240 mm 2<br />

Auxiliary circuit/control circuit<br />

Rated control supply voltage U e AC 50/60 Hz, 115 V <strong>and</strong> 230 V DC 24 V<br />

Working range AC 50/60 Hz, 0.85 to 1.1 U s DC 24 V, 0.85 to 1.2 U s (DIN 19240)<br />

Power consumption AC 50/60 Hz, 5 VA DC 24 V, 5 W<br />

Mains buffering time<br />

200 ms<br />

Rated insulation voltage U I 300 V (for pollution degree 3)<br />

Rated impulse strength U imp<br />

4 kV<br />

Outputs<br />

4 mono-/bistable outputs depending on the variant<br />

Auxiliary contacts of outputs<br />

3 outputs thereof are connected to a common potential <strong>and</strong> 1 is connected separately; can be freely assigned to the<br />

control functions (e.g. for activation of mains <strong>and</strong> star-delta contactor as well as signalling of the operating state)<br />

Upstream short-circuit protection for<br />

Fuse-links utilization category gL/gA 6 A, fast 10 A<br />

auxiliary contacts (outputs)<br />

Circuit-breaker 1.6 A, C characteristic<br />

Rated continuous current<br />

5 A<br />

17