Wide Scope of <strong>Control</strong> Functions<br />
With the <strong>SIMOCODE</strong>-<strong>DP</strong> system nine<br />
different control functions can be<br />
implemented:<br />
• Overload relay<br />
• Direct starter<br />
• Reversing starter<br />
• Star-delta starter<br />
• Dahl<strong>and</strong>er<br />
• Pole-changing switch<br />
• Slide valve (Encoder)<br />
• Solenoid valve<br />
• SIKOSTART® 3RW22<br />
(Soft starter)<br />
In addition, permanent or nonmaintained<br />
comm<strong>and</strong> mode can be<br />
set. All control functions can be<br />
implemented using the <strong>3UF5</strong>0 basic<br />
unit. If more than four inputs <strong>and</strong> four<br />
outputs are required, an additional<br />
eight inputs <strong>and</strong> four outputs can be<br />
fitted by using an extension module.<br />
Cost reduction by pre-defined<br />
control functions<br />
In the <strong>SIMOCODE</strong>-<strong>DP</strong>, all necessary<br />
interlocking requirements for the<br />
relevant control function (e.g. with<br />
encoders the undelayed deactivation<br />
of the motor in case of an operation of<br />
the limit or torque switch) are implemented.<br />
This offers major advantages:<br />
• Reducing the dem<strong>and</strong>s put on the<br />
user program in the programmable<br />
controller, i.e. fast planning, fewer<br />
possibilities for errors, shorter<br />
program cycle times<br />
• Time-critical functions of the<br />
motor feeder are independent of<br />
the signal process time in the<br />
automation level <strong>and</strong> on the<br />
communication system.<br />
In addition, run time checks can be set<br />
for the start or stop of motors <strong>and</strong> for<br />
the slide valve control functions in<br />
between the limits.<br />
Safety by operator enable <strong>and</strong><br />
manual/automatic switch-over<br />
In the automatic mode, control<br />
comm<strong>and</strong>s (e.g. ON, OFF) are transmitted<br />
to <strong>SIMOCODE</strong>-<strong>DP</strong> via the bus.<br />
<strong>Control</strong> comm<strong>and</strong>s from the switchgear<br />
cubicle (e.g. of the operating<br />
module) or from the local control<br />
station are only possible in this<br />
operating mode if the corresponding<br />
operator enable comm<strong>and</strong>s have been<br />
set.<br />
3/N/PE~ 50/60 Hz 400/230 V<br />
L1<br />
L2<br />
L3<br />
NPE<br />
Q1<br />
1L1<br />
2L1<br />
1N<br />
2N<br />
F11<br />
Q1<br />
RMT<br />
l ><br />
2<br />
3<br />
-K1 -K2<br />
-K3<br />
Overload<br />
Current imbalance<br />
Phase failure<br />
Thermistor<br />
Earth fault<br />
Blocking protection<br />
Current value detection<br />
1<br />
A1A2 T1T2 1 2 3 4 5<br />
230 V AC<br />
<strong>3UF5</strong>0<br />
PROFIBUS-<strong>DP</strong><br />
6 7 8 9 10 11 B A SPE/PE<br />
Ready<br />
Gen. Fault<br />
Test/<br />
Reset<br />
Switching at the<br />
cubicle door via<br />
the <strong>3UF5</strong>2<br />
operating module<br />
ON<br />
OFF<br />
2<br />
3<br />
ON<br />
OFF<br />
Local<br />
1<br />
1U 1V 1W<br />
M<br />
3~<br />
2W<br />
2U<br />
2V<br />
-K1 -K2<br />
-K3<br />
5