9. Lift the TCA straight up out of the unit.<br />

10. Inspect the insulation on the inside of the case walls while<br />

the TCA is removed. Replace any that is wet. Install insulation<br />

on the new TCA.<br />

11. Transfer the strainer from inside the old TCA to the new TCA,<br />

if required.<br />

12. Clean the refrigeration stubs on the new TCA carefully prior<br />

to installation. Clean the inside of the mating copper lines<br />

prior to installation.<br />

13. Lower the TCA into place and secure the mounting flange to<br />

the mounting rails.<br />

CAUTION: The refrigerant inlet and outlet lines are stainless<br />

steel. They are easily damaged by excessive heat.<br />

Solder the fittings as follows:<br />

A. Ensure all fittings have been carefully cleaned.<br />

B. Apply a paste-type flux.<br />