CONDENSER REQUIREMENTS:<br />
WATER COOLED UNITS<br />
The facility cooling water supply must meet or exceed the<br />
requirements shown below for the unit to operate at its full rated<br />
capacity.<br />
As the temperature of the cooling water supply increases, the<br />
required flow and pressure of the cooling water supply increases.<br />
Example: On the <strong>HX</strong>-300, if the temperature of the cooling<br />
water supply is 65°F (18°C), the flow rate must be at least 4.0<br />
gpm ( 15.1 lpm ), with a pressure differential of at least 8 psi<br />
(55 kPa). However, if the temperature of the cooling water<br />
supply rises to 85°F ( 29°C ), the flow rate must be at least 11.0<br />
gpm (42 lpm ), with a pressure differential of at least 25 psi<br />
( 172 kPa).<br />
A water regulating valve, located in TAP WATER line, regulates<br />
the flow rate of the cooling water supply as it enters the unit.<br />
The valve regulates the flow rate based on the heat load. Flow<br />
through the unit stops automatically when the unit is shut off.<br />