Water regulating valve setting<br />

The correct setting of the valve is easily determined.<br />

1. Supply cooling water to <strong>HX</strong>.<br />

2. Direct the outlet hose into a bucket or drain.<br />

3. Turn the <strong>HX</strong> on.<br />

4. Turn the setpoint to minimum. The <strong>HX</strong> should enter the cool<br />

cycle. Observe full flow from the outlet hose. Allow it to run<br />

until all air is displaced.<br />

5. Turn setpoint to maximum. The <strong>HX</strong> should enter the heat<br />

cycle.<br />

6. Adjust the valve stem closed (CCW) until the flow stops.<br />

7. Slowly open the valve stem (CW) until a small but constant<br />

trickle is exiting the outlet hose. This is the point where the<br />

valve is just beginning to crack open. This is the correct<br />

setting.<br />

8. Turn setpoint to minimum. The <strong>HX</strong> should enter the cool<br />

cycle. Full flow should again be observed from the outlet<br />

hose.<br />