Water regulating valve setting<br />
The correct setting of the valve is easily determined.<br />
1. Supply cooling water to <strong>HX</strong>.<br />
2. Direct the outlet hose into a bucket or drain.<br />
3. Turn the <strong>HX</strong> on.<br />
4. Turn the setpoint to minimum. The <strong>HX</strong> should enter the cool<br />
cycle. Observe full flow from the outlet hose. Allow it to run<br />
until all air is displaced.<br />
5. Turn setpoint to maximum. The <strong>HX</strong> should enter the heat<br />
cycle.<br />
6. Adjust the valve stem closed (CCW) until the flow stops.<br />
7. Slowly open the valve stem (CW) until a small but constant<br />
trickle is exiting the outlet hose. This is the point where the<br />
valve is just beginning to crack open. This is the correct<br />
setting.<br />
8. Turn setpoint to minimum. The <strong>HX</strong> should enter the cool<br />
cycle. Full flow should again be observed from the outlet<br />
hose.<br />