SECTION 2 – RELIABILITY PERFORMANCE MEASURES<br />
<strong>Reliability</strong> Performance Indices<br />
The benchmarks and standards established by the <strong>Commission</strong> are based<br />
on four reliability performance indices which have been adopted by the Institute<br />
of Electrical and Electronic Engineers, Inc. (IEEE). These indices include: (1)<br />
Customer Average Interruption Duration Index (CAIDI); (2) System Average<br />
Interruption Frequency Index (SAIFI); (3) System Average Interruption Duration<br />
Index (SAIDI); and (4) Momentary Average Interruption Frequency index (MAIFI).<br />
CAIDI is the average duration of sustained interruptions 14 for those<br />
customers who experience interruptions during the analysis period. CAIDI<br />
represents the average time required to restore service to the average<br />
customer per sustained interruption. It is determined by dividing the sum<br />
of all sustained customer interruption durations, in minutes, by the total<br />
number of interrupted customers.<br />
SAIFI measures the average frequency of sustained interruptions per<br />
customer occurring during the analysis period. It is calculated by dividing<br />
the total number of sustained customer interruptions by the total number of<br />
customers served.<br />
SAIDI is the average duration of sustained customer interruptions per<br />
customer occurring during the analysis period. It is the average time<br />
customers were without power. It is determined by dividing the sum of all<br />
sustained customer interruption durations, in minutes, by the total number<br />
of customers served. SAIDI is also the product of CAIDI and SAIFI.<br />
MAIFI measures the average frequency of momentary interruptions 15 per<br />
customer occurring during the analysis period. It is calculated by dividing<br />
the total number of momentary customer interruptions by the total number<br />
of customers served.<br />
The actual values of these four reliability indices are submitted by the<br />
EDCs on both a quarterly (rolling 12-month average) and annual basis. Also<br />
14 The loss of electric service by one or more customers for the period defined as a sustained customer interruption<br />
by IEEE as it may change from time to time – currently 5 minutes or greater. The term does not include “major<br />
events” or the authorized termination of service to an individual customer.<br />
15 The loss of electric service by one or more customers for the period defined as a momentary customer interruption<br />
by the IEEE as it may change from time to time – currently less than 5 minutes. The term does not include “major<br />
events” or the authorized termination of service to an individual customer.<br />
Electric Service <strong>Reliability</strong> in <strong>Pennsylvania</strong> 3