SECTION 2 – RELIABILITY PERFORMANCE MEASURES<br />

<strong>Reliability</strong> Performance Indices<br />

The benchmarks and standards established by the <strong>Commission</strong> are based<br />

on four reliability performance indices which have been adopted by the Institute<br />

of Electrical and Electronic Engineers, Inc. (IEEE). These indices include: (1)<br />

Customer Average Interruption Duration Index (CAIDI); (2) System Average<br />

Interruption Frequency Index (SAIFI); (3) System Average Interruption Duration<br />

Index (SAIDI); and (4) Momentary Average Interruption Frequency index (MAIFI).<br />

CAIDI is the average duration of sustained interruptions 14 for those<br />

customers who experience interruptions during the analysis period. CAIDI<br />

represents the average time required to restore service to the average<br />

customer per sustained interruption. It is determined by dividing the sum<br />

of all sustained customer interruption durations, in minutes, by the total<br />

number of interrupted customers.<br />

SAIFI measures the average frequency of sustained interruptions per<br />

customer occurring during the analysis period. It is calculated by dividing<br />

the total number of sustained customer interruptions by the total number of<br />

customers served.<br />

SAIDI is the average duration of sustained customer interruptions per<br />

customer occurring during the analysis period. It is the average time<br />

customers were without power. It is determined by dividing the sum of all<br />

sustained customer interruption durations, in minutes, by the total number<br />

of customers served. SAIDI is also the product of CAIDI and SAIFI.<br />

MAIFI measures the average frequency of momentary interruptions 15 per<br />

customer occurring during the analysis period. It is calculated by dividing<br />

the total number of momentary customer interruptions by the total number<br />

of customers served.<br />

The actual values of these four reliability indices are submitted by the<br />

EDCs on both a quarterly (rolling 12-month average) and annual basis. Also<br />

14 The loss of electric service by one or more customers for the period defined as a sustained customer interruption<br />

by IEEE as it may change from time to time – currently 5 minutes or greater. The term does not include “major<br />

events” or the authorized termination of service to an individual customer.<br />

15 The loss of electric service by one or more customers for the period defined as a momentary customer interruption<br />

by the IEEE as it may change from time to time – currently less than 5 minutes. The term does not include “major<br />

events” or the authorized termination of service to an individual customer.<br />

Electric Service <strong>Reliability</strong> in <strong>Pennsylvania</strong> 3