eco-ATWB Engineering Bulletin - Evapco
eco-ATWB Engineering Bulletin - Evapco
eco-ATWB Engineering Bulletin - Evapco
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Selections for <strong>ATWB</strong> Closed Circuit Coolers are available from EVAPCO’s evap ele Equipment Selection Program.<br />
Please contact your local sales representative for more information on the evap ele program.<br />
Swing Out Radius of Motor Cover<br />
30-5/8<br />
<strong>Engineering</strong> Data & Dimensions<br />
<strong>eco</strong>-ATW Models 9-3H9 to 9-6K9<br />
P<br />
ACCESS DOOR<br />
21-3/8<br />
(2) 4 BFW<br />
FLUID IN<br />
48-3/4 26-3/8<br />
U<br />
ACCESS<br />
DOOR<br />
A<br />
(2) 4 BFW<br />
FLUID OUT<br />
H<br />
(2) 1/2 FPT VENT<br />
2 MPT<br />
MAKE-UP<br />
6<br />
E<br />
23-1/8<br />
15<br />
3<br />
2 MPT<br />
DRAIN<br />
3 MPT<br />
OVERFLOW<br />
5-1/4<br />
4-1/4<br />
67-1/4<br />
8' 5-1/2" 15-5/8<br />
8' 11-1/2"<br />
Note: The number of coil connections doubles when the flow rate exceeds 900 GPM on <strong>eco</strong>-ATW 9x9 models. This required option is referred to as the High Flow coil configuration.<br />
<strong>eco</strong>-ATW<br />
Weights (lbs) Fans Spray Pump<br />
Coil Remote Sump Dimensions <br />
Model Heaviest Volume Gallons* Conn. Operating Coil Upper Lower Height<br />
Number† Shipping Section†† Operating HP CFM HP GPM (Gallons) Required Size Weight (lbs) A U E H<br />
<strong>eco</strong>-ATW 9-3H9 9,460 8,020 13,450 7.5 37,660 2 410 164 250 8" 12,170 19 1/2" 6' 11 1/2" 4' 3 7/8" 11' 3 3/8"<br />
<strong>eco</strong>-ATW 9-3I9 9,470 8,030 13,460 10 41,440 2 410 164 250 8" 12,180 19 1/2" 6' 11 1/2" 4' 3 7/8" 11' 3 3/8"<br />
<strong>eco</strong>-ATW 9-3J9 9,600 8,160 13,590 15 46,620 2 410 164 250 8" 12,310 19 1/2" 6' 11 1/2" 4' 3 7/8" 11' 3 3/8"<br />
<strong>eco</strong>-ATW 9-3K9 9,660 8,220 13,650 20 50,540 2 410 164 250 8" 12,370 19 1/2" 6' 11 1/2" 4' 3 7/8" 11' 3 3/8"<br />
<strong>eco</strong>-ATW 9-4H9 11,070 9,630 15,470 7.5 36,560 2 410 215 250 8" 14,190 27" 7' 7" 4' 3 7/8" 11' 10 7/8"<br />
<strong>eco</strong>-ATW 9-4I9 11,080 9,640 15,480 10 40,240 2 410 215 250 8" 14,200 27" 7' 7" 4' 3 7/8" 11' 10 7/8"<br />
<strong>eco</strong>-ATW 9-4J9 11,210 9,770 15,610 15 45,270 2 410 215 250 8" 14,330 27" 7' 7" 4' 3 7/8" 11' 10 7/8"<br />
<strong>eco</strong>-ATW 9-4K9 11,270 9,830 15,670 20 49,060 2 410 215 250 8" 14,390 27" 7' 7" 4' 3 7/8" 11' 10 7/8"<br />
<strong>eco</strong>-ATW 9-5H9 12,790 11,350 17,610 7.5 35,460 2 410 265 250 8" 16,330 34 1/2" 8' 2 1/2" 4' 3 7/8" 12' 6 3/8"<br />
<strong>eco</strong>-ATW 9-5I9 12,800 11,360 17,620 10 39,030 2 410 265 250 8" 16,340 34 1/2" 8' 2 1/2" 4' 3 7/8" 12' 6 3/8"<br />
<strong>eco</strong>-ATW 9-5J9 12,930 11,490 17,750 15 43,910 2 410 265 250 8" 16,470 34 1/2" 8' 2 1/2" 4' 3 7/8" 12' 6 3/8"<br />
<strong>eco</strong>-ATW 9-5K9 12,990 11,550 17,810 20 47,590 2 410 265 250 8" 16,530 34 1/2" 8' 2 1/2" 4' 3 7/8" 12' 6 3/8"<br />
<strong>eco</strong>-ATW 9-6I9 14,480 13,040 19,720 10 37,820 2 410 315 250 8" 18,440 42" 8' 10" 4' 3 7/8" 13' 1 7/8"<br />
<strong>eco</strong>-ATW 9-6J9 14,610 13,170 19,850 15 42,550 2 410 315 250 8" 18,570 42" 8' 10" 4' 3 7/8" 13' 1 7/8"<br />
<strong>eco</strong>-ATW 9-6K9 14,670 13,230 19,910 20 46,120 2 410 315 250 8" 18,630 42" 8' 10" 4' 3 7/8" 13' 1 7/8"<br />
† Model Numbers end in “-Z” for units with Series Flow piping configuration. Series Flow units may require additional coil connections and will require<br />
crossover piping. Model numbers will include “R” for units with Low Sound Fan(s) and “S” for units with an option that negates CTI certification.<br />
†† Heaviest section is the coil/fan section.<br />
* Gallons shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer<br />
during operation (12” would normally be sufficient).<br />
When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an<br />
oversized outlet to facilitate drainage to the remote sump.<br />
Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and<br />
piping configuration. Coil connections are 4” bevel for weld (BFW). Other connection types such as grooved for mechanical coupling or flanged are<br />
also available as options.<br />
29