D ESIGN F EATURES<br />

Principles of Operation<br />

Evaporative Mode<br />

(Latent Heat Transfer)<br />

In the evaporative mode, the process fluid enters the<br />

<strong>eco</strong>-ATWE cooler through the top coil connections and<br />

circulates through the finned coils. With both pumps<br />

energized, the heat from the process fluid is transferred<br />

through the coil tubes to the water cascading downward<br />

over the coils while simultaneously air is drawn upward<br />

over the coil opposite the water flow using the fan drive<br />

system (Fan on, Pump A & B on). A small portion of the<br />

water is evaporated to dissipate the heat to the<br />

atmosphere in a latent heat transfer. This mode of<br />

operation provides fan energy savings and lower leaving<br />

water temperatures by utilizing evaporative cooling.<br />

Water Efficient Mode<br />

(Evaporative and Sensible Heat Transfer)<br />

The joint wet and dry operation mode provides water<br />

savings as well as low approach temperatures. In this joint<br />

mode of operation, the fan is on and the process fluid<br />

enters the coils through the top coil connections (Fan on,<br />

Pump A on, Pump B off). Recirculating pump B is turned off<br />

and coil B rejects a portion of the heat load to the<br />

atmosphere through the tube and fin walls to the air<br />

passing over the coils using sensible heat transfer. Pump A is<br />

left on where heat from the process fluid is transferred<br />

through the coil tubes to the water cascading downward<br />

over coil A. This mode of operation minimizes the amount<br />

of water used while maintaining the cooling capacity<br />

required. The cooled fluid then returns to the process via<br />

the bottom coil connection.<br />

Dry Mode<br />

(Sensible Heat Transfer)<br />

In the dry mode, the recirculating spray pumps are<br />

deenergized (Fan on, Pump A & B off). The process fluid<br />

enters the <strong>eco</strong>-ATWE cooler through the top coil connection<br />

and circulates through the coil with the Fan On. Heat from<br />

the process fluid is dissipated to the atmosphere by sensible<br />

heat transfer through the tube walls to the air passing over<br />

the coils. The coils are finned to promote optimal airflow<br />

over the coil and to maximize heat transfer area. Air is<br />

drawn over the finned coils by the fan drive system. The<br />

process fluid then returns to the heat source via the bottom<br />

coil connection. This mode of operation eliminates water<br />

consumption when the dry bulb temperature is favorable.<br />

12