D ESIGN F EATURES<br />
Principles of Operation<br />
Evaporative Mode<br />
(Latent Heat Transfer)<br />
In the evaporative mode, the process fluid enters the<br />
<strong>eco</strong>-ATWE cooler through the top coil connections and<br />
circulates through the finned coils. With both pumps<br />
energized, the heat from the process fluid is transferred<br />
through the coil tubes to the water cascading downward<br />
over the coils while simultaneously air is drawn upward<br />
over the coil opposite the water flow using the fan drive<br />
system (Fan on, Pump A & B on). A small portion of the<br />
water is evaporated to dissipate the heat to the<br />
atmosphere in a latent heat transfer. This mode of<br />
operation provides fan energy savings and lower leaving<br />
water temperatures by utilizing evaporative cooling.<br />
Water Efficient Mode<br />
(Evaporative and Sensible Heat Transfer)<br />
The joint wet and dry operation mode provides water<br />
savings as well as low approach temperatures. In this joint<br />
mode of operation, the fan is on and the process fluid<br />
enters the coils through the top coil connections (Fan on,<br />
Pump A on, Pump B off). Recirculating pump B is turned off<br />
and coil B rejects a portion of the heat load to the<br />
atmosphere through the tube and fin walls to the air<br />
passing over the coils using sensible heat transfer. Pump A is<br />
left on where heat from the process fluid is transferred<br />
through the coil tubes to the water cascading downward<br />
over coil A. This mode of operation minimizes the amount<br />
of water used while maintaining the cooling capacity<br />
required. The cooled fluid then returns to the process via<br />
the bottom coil connection.<br />
Dry Mode<br />
(Sensible Heat Transfer)<br />
In the dry mode, the recirculating spray pumps are<br />
deenergized (Fan on, Pump A & B off). The process fluid<br />
enters the <strong>eco</strong>-ATWE cooler through the top coil connection<br />
and circulates through the coil with the Fan On. Heat from<br />
the process fluid is dissipated to the atmosphere by sensible<br />
heat transfer through the tube walls to the air passing over<br />
the coils. The coils are finned to promote optimal airflow<br />
over the coil and to maximize heat transfer area. Air is<br />
drawn over the finned coils by the fan drive system. The<br />
process fluid then returns to the heat source via the bottom<br />
coil connection. This mode of operation eliminates water<br />
consumption when the dry bulb temperature is favorable.<br />
12