5HTXLUHPHQWV#IRU#(0&#&RPSOLDQFH<br />
All Variable Speed Drives (VSDs) potentially produce electrical emissions which are radiated<br />
into the environment and conducted back into the ac sup<strong>pl</strong>y. VSDs are inherently immune to any<br />
additional external electrical noise. The following information is provided to maximise the<br />
Electro Magnetic Compatibility (EMC) of VSDs and systems in their intended operating<br />
environment, by minimising their emissions and maximising their immunity.<br />
0LQLPLVLQJ#5DGLDWHG#(PLVVLRQV<br />
EN55011/EN55022 radiated emission measurements are made between 30MHz and 1GHz in the<br />
far field at a distance of 10 to 30 metres (32.8 to 98.4 feet). Limits lower than 30MHz or in close<br />
proximity are not specified. Emissions from individual components tend to be additive.<br />
• Use a screened/armoured cable between VSD/cubicle and motor containing the motor<br />
protective earth (PE) connection. It should have a 360° screen termination. Earth screen at<br />
both ends connecting to the motor frame and VSD/cubicle back<strong>pl</strong>ate. Maintain the screen<br />
integrity using 360° terminations.<br />
1RWH=# 6RPH#KD]DUGRXV#DUHD#LQVWDOODWLRQV#PD\#SUHFOXGH#GLUHFW#HDUWKLQJ#DW#ERWK#HQGV#RI#WKH<br />
VFUHHQ/#LQ#WKLV#FDVH#HDUWK#RQH#HQG#YLD#D#4µ)#839DF#FDSDFLWRU/#DQG#WKH#RWKHU#PXVW#EH<br />
GLUHFWO\#HDUWKHG1<br />
• Keep unshielded cable as short as possible inside the cubicle.<br />
• Always maintain the integrity of the shield.<br />
• If the cable is interrupted to insert contactors etc., re-connect the screen using the shortest<br />
possible route.<br />
• Keep the length of screen stripped-back as short as possible when making screen<br />
connections.<br />
• Ideally use 360° screen terminations using cable glands or `U’ clips on power screen rails.<br />
If a shielded cable is not available, lay unshielded motor cables in a metal conduit which will act<br />
as a shield. The conduit must be continuous with a direct electrical contact to the VSD and motor<br />
housing. If links are necessary, use braid with a minimum cross sectional area of 10mm 2 .<br />
1RWH=# 6RPH#PRWRU#JODQG#ER[HV/#FRQGXLW#DQG#FRQGXLW#JODQGV#DUH#PDGH#RI#SODVWLF/#LI#WKLV#LV#WKH<br />
FDVH/#WKHQ#EUDLG#PXVW#EH#FRQQHFWHG#LQ#SDUDOOHO#WR#PDLQWDLQ#VFUHHQ#LQWHJULW\1#,Q#DGGLWLRQ#DW<br />
WKH#PRWRU#HQG/#HQVXUH#WKDW#WKH#VFUHHQ#LV#HOHFWULFDOO\#FRQQHFWHG#WR#WKH#PRWRU#IUDPH#VLQFH<br />
VRPH#WHUPLQDO#ER[HV#DUH#LQVXODWHG#IURP#WKH#IUDPH#E\#JDVNHW2SDLQW1<br />
(DUWKLQJ#5HTXLUHPHQWV<br />
,03257$17=# 3URWHFWLYH#HDUWKLQJ#DOZD\V#WDNHV#SUHFHGHQFH#RYHU#(0&#HDUWKLQJ1<br />
3URWHFWLYH#(DUWK#+3(,#&RQQHFWLRQV<br />
1RWH=# ,Q#DFFRUGDQFH#ZLWK#LQVWDOODWLRQV#WR#(193537/#RQO\#RQH#SURWHFWLYH#HDUWK#FRQGXFWRU#LV<br />
SHUPLWWHG#DW#HDFK#96'#SURWHFWLYH#HDUWK#WHUPLQDO#FRQWDFWLQJ#SRLQW1<br />
Local wiring regulations may require the protective earth connection of the motor to be<br />
connected locally, i.e. not as specified in these instructions. This will not cause shielding<br />
problems because of the relatively high RF impedance of the local earth connection.<br />
8