The minimum connection requirements for operating the<br />

<strong>Converter</strong> are highlighted in the following text with the symbol<br />

opposite.<br />

MINIMUM<br />

CONNECTION<br />

REQUIREMENT<br />

The <strong>Converter</strong> is using the default Armature Voltage feedback when following the<br />

`minimum connections’ instructions.<br />

+<br />

Motor<br />

Armature<br />

-<br />

A-<br />

-<br />

Motor<br />

Field<br />

+<br />

L<br />

N<br />

Auxiliary<br />

Power<br />

Main<br />

Contactor Coil<br />

N<br />

C<br />

L1 L2 L3<br />

A+<br />

FL1<br />

FL2<br />

F+<br />

F-<br />

MVA+<br />

MVA-<br />

Standard<br />

Door<br />

Assembly<br />

AC Line Choke<br />

PROTECTIVE<br />

EARTH<br />

To contactor control<br />

Suitable branch protection<br />

fuses or circuit breaker<br />

Start Contactor<br />

Figure 3-7 Minimum Connection Requirements (`general purpose' configuration)<br />

,03257$17=# ,QGLFDWRU#ODPSV/#DQQXQFLDWRUV/#HWF1/#IRU#%'ULYH#2Q%#FRQGLWLRQ#VKRXOG#EH#VZLWFKHG#E\#DQ<br />

DX[LOLDU\#FRQWDFWRU#RI#WKH#PDLQ#FRQWDFWRU/#QRW#E\#WKH#FRQWUROOHU#DX[LOLDU\#UHOD\1<br />

7R#DYRLG#GDPDJLQJ#WKH#GULYH#1(9(5#FDUU\#RXW#KLJK#YROWDJH#UHVLVWDQFH#RU#GLHOHFWULF<br />

VWUHQJWK#WHVWV#ZLWKRXW#ILUVW#FRPSOHWHO\#GLVFRQQHFWLQJ#WKH#GULYH#IURP#WKH#FLUFXLW#EHLQJ#WHVWHG1<br />

• Power connections must have a minimum rating of 1.1 x full load current. (1.25 x FLC when<br />

required to com<strong>pl</strong>y with UL requirements).<br />

• All incoming main AC power sup<strong>pl</strong>y connections must be protected with high speed<br />

semiconductor fuses. Refer to Chapter 11: “Technical Specifications” for fuse information.<br />

• The External AC Sup<strong>pl</strong>y EMC Filter must only be fitted on the mains side of the contactor.<br />