Special Hazards/Special Systems<br />
Preaction systems contain no water in the sprinkler piping under normal operating<br />
conditions. The piping either contains air at atmospheric pressure (i.e., unsupervised<br />
systems) or a low pressure compressed gas, such as air or dry nitrogen, for the purpose of<br />
supervising the integrity of the sprinkler piping. Usually, supervision of the sprinkler piping<br />
is done at a pressure of either 2 to 10 psi (0,1 to 0,7 bar) , or 10 to 26 psi (0,7 to 1,8 bar),<br />
depending on the type of preaction system being used. Areas typically protected by<br />
preaction systems include computer rooms, museums, libraries, and freezers.<br />
Single Interlock Preaction Systems<br />
Single interlock preaction systems are designed for water sensitive environments in heated<br />
areas that require protection from inadvertent water flow into the sprinkler system piping as<br />
a result of damaged sprinklers or sprinkler piping; or, during a fire event, where water is<br />
required at the sprinkler as soon as the sprinkler operates. Preaction systems can also<br />
replace dry pipe systems, providing cost advantages except for storage occupancies in the<br />
hydraulics of the system (i.e., 1500 ft 2 (139.4 m 2 ) design area vs.1950 ft 2 (181.1 m 2 )<br />
design area for dry systems) and where dry system piping capacities exceed volume<br />
limitations imposed by the applicable standards, where water delivery performance is<br />
adversely affected.<br />
<strong>Automatic</strong> (closed) sprinklers are attached to a piping system containing 2-10 psi (0,1 –<br />
0,7 bar) supervisory pressure, and a supplemental electric fire detection system is installed<br />
in the same area protected by the sprinklers. This detection system is used in conjunction<br />
with an approved releasing control panel. Preaction systems may also be activated by<br />
mechanical means using either wet pilot or dry pilot <strong>line</strong> sprinklers or fixed temperature<br />
release pilot <strong>line</strong> detectors.<br />
When one detector activates in the event of a fire, the deluge valve opens allowing water to<br />
enter and fill the sprinkler system piping. Water then stands ready at the sprinkler and will<br />
immediately discharge once the sprinkler operates, acting like a wet pipe sprinkler system.<br />
Water will only discharge from those sprinklers that have been operated by heat over the<br />
fire. Loss of supervisory air pressure as a result of damaged sprinklers or damaged system<br />
piping will only activate a supervisory alarm and not cause the deluge valve to open.<br />
For more detailed information including approval data, please refer to the technical bulletin specified.<br />