are used to provide performance comparison with R 22. System designers normally use data based on<br />
the dew point temperatures as specified in EN 12<strong>90</strong>0. With the Copeland Selection Software version 4<br />
and above performance data sheets for both mid point and dew point definitions are available.<br />
It is essential that the glide of R 407 refrigerant blends are given careful consideration when adjusting<br />
pressure controls. Furthermore, it is crucial to consider the effect of pressure losses on glide when sizing<br />
heat exchangers. Pressure losses effectively increase glide significantly in the system. Failure to<br />
consider this in heat energy balance calculations will likely result in undersizing heat exchangers and<br />
other system components. These effects are especially apparent when operating a system near the limits<br />
of its application range.<br />
40 Application Envelopes<br />
10 K Suction Superheat<br />
Fig. 16: Operating Envelopes<br />
25 °C Suction Return Gas Temperature<br />
C6.2.2/0701/E 20