18/09/2003 <strong>HESC</strong>-<strong>UPS</strong> <strong>Manual</strong><br />

Output: unsigned int – value from ADC converter<br />

Units: ADC converter value<br />

Range: data range is 0 to 65,535Description:<br />

Returns the main input voltage (mV).<br />

16. MainVCmd() (0x91)<br />

Purpose:<br />

The MainVCmd() function provides the Host power management system with an accurate main input voltage. The<br />

Host management system can use this voltage, along with main input current information to help enable intelligent,<br />

adaptive power management systems.<br />

Protocol: Read Word<br />

Output: unsigned int – main input voltage in mV<br />

Units: mV<br />

Range: 0 to 65,535<br />

17. MainICmd() (0x92)<br />

Description:<br />

Returns the current being supplied to the <strong>HESC</strong> (mA).<br />

Purpose:<br />

The MainICmd() function provides the Host power management system an accurate measure of the current flowing<br />

into the <strong>HESC</strong>. The current being report by the MainICmd() will be either from the main input or battery or some from<br />

both inputs if both the main input and battery are the same potential. Compare the voltages returned by BattIVCmd()<br />

and the MainVCmd() to determine the source of the power.<br />

Protocol: Read Word<br />

Output: unsigned int – input current rate in mA increments<br />

Units: mA<br />

Range: 0 to 65,535<br />

18. InputPwrCmd() (0x93)<br />

Description:<br />

Returns the power being supplied to the <strong>HESC</strong>.<br />

Purpose:<br />

The InputPwrCmd() function provides the Host power management system a measure of the power flowing into the<br />

<strong>HESC</strong>-SER. The power being report by the InputPwrCmd() will be either from the main input or battery or some from<br />

both inputs if both the main input and battery are the same potential. Compare the voltages returned by BattIVCmd()<br />

and the MainVCmd() to determine the source of the power.<br />

Protocol: Read Word<br />

Output: unsigned int – input power in 10mW increments<br />

Units: 10mW<br />

Range: 0 to 65,535<br />

19. BattPwrCmd() (0x94)<br />

Description:<br />

Returns the power being charged/discharge to the battery through the <strong>HESC</strong>.<br />

<strong>Tri</strong>-M Engineering Tel: 800.665.5600, 604.945.9565<br />

1407 Kebet Way, Unit 100 Fax: 604.945.95<br />

Port Coquitlam, BC, V3C 6L3 E-mail: info@tri-m.com<br />

Canada<br />

Web site: www.tri-m.com<br />

18

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!