A--Line Voltage<br />
To facilitate conduit, knockouts are provided in cabinet<br />
panel. Route conduit through knockout in cabinet and<br />
connect to side of control panel. Refer to figure 3 for<br />
thermostat, furnace and condensing unit wire connections<br />
and figure 4 for field wiring diagram.<br />
Note--Units are approved for use with copper conductors<br />
only.<br />
B--24V, Class II Circuit<br />
24V, Class II Circuit connections are made up below control<br />
box.<br />
Note--A complete unit wiring diagram is located inside<br />
the unit access panel.<br />
<strong>HS25</strong> and FURNACE (GAS OR ELECTRIC)<br />
THERMOSTAT CONNECTIONS<br />
(Some connections may not apply.<br />
Refer to specific thermostat and furnace.)<br />
Furnace Thermostat <strong>HS25</strong><br />
R<br />
W1<br />
W2<br />
Y<br />
G<br />
C<br />
POWER<br />
1ST STAGE AUX. HEAT<br />
2ND STAGE AUX. HEAT<br />
W2<br />
INDOOR BLOWER<br />
COMMON<br />
R<br />
W1<br />
Y<br />
G<br />
C<br />
COMPRESSOR<br />
COMMON<br />
Condensing<br />
Unit<br />
<strong>HS25</strong><br />
COMPRESSOR<br />
<strong>HS25</strong><br />
COMMON<br />
FIGURE 3<br />
<strong>HS25</strong> CONDENSING UNIT<br />
FIELD WIRING DIAGRAM<br />
CONDENSING UNIT<br />
ROOM THERMOSTAT<br />
TYPICAL<br />
INDOOR UNIT<br />
C<br />
Y1<br />
G<br />
W<br />
RC<br />
RH<br />
TB1<br />
TRANSFORMER<br />
R<br />
W1<br />
G<br />
TO<br />
HEATING<br />
CONTROLS<br />
TO<br />
COOLING SPEED<br />
24v<br />
T1<br />
YELLOW<br />
BLACK OR BLUE<br />
NOTE--SEE UNIT WIRING DIAGRAM<br />
FOR POWER SUPPLY CONNECTIONS.<br />
TO 24V CLASS II POWER SOURCE<br />
-- 20 VA MINIMUM<br />
W2<br />
W3<br />
C<br />
24V,<br />
CLASS II<br />
JUNCTION<br />
BOX<br />
TO<br />
HEATING<br />
SPEED<br />
POWER<br />
YELLOW<br />
GROUND<br />
PER NATIONAL<br />
AND LOCAL<br />
CODES<br />
K3 INDOOR BLOWER RELAY<br />
NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH BLOWER RELAY, IT MUST BE<br />
FIELD PROVIDED AND INSTALLED (P--8--3251 OR EQUIVALENT)<br />
24V, CLASS II VOLTAGE INSTALLED AT FACTORY<br />
24V, CLASS II VOLTAGE FIELD INSTALLED<br />
FIGURE 4<br />