04.10.2014 Views

INSTALLATION INSTRUCTIONS HS25 SERIES UNITS - Lennox

INSTALLATION INSTRUCTIONS HS25 SERIES UNITS - Lennox

INSTALLATION INSTRUCTIONS HS25 SERIES UNITS - Lennox

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PRODUCT LITERATURE<br />

¤1995 <strong>Lennox</strong> Industries Inc.<br />

Dallas, Texas<br />

£<br />

<strong>INSTALLATION</strong><br />

<strong>INSTRUCTIONS</strong><br />

+6 6(5,(6 81,76<br />

&21'(16,1* 81,76<br />

0<br />

<br />

6XSHUVHGHV 0<br />

/LWKR 86$<br />

TABLE OF CONTENTS<br />

<strong>HS25</strong> CONDENSING UNIT ......................... 1<br />

SHIPPING AND PACKING LIST ...................... 1<br />

GENERAL INFORMATION .......................... 1<br />

<strong>HS25</strong> UNIT DIMENSIONS .......................... 2<br />

<strong>HS25</strong> PARTS ARRANGEMENT ...................... 3<br />

SETTING THE UNIT ................................ 3<br />

ELECTRICAL ...................................... 3<br />

PLUMBING ....................................... 5<br />

REFRIGERATION .................................. 5<br />

LEAK TESTING .................................... 5<br />

EVACUATION ..................................... 5<br />

START--UP ........................................ 6<br />

CHARGING ....................................... 7<br />

SYSTEM OPERATION .............................. 7<br />

MAINTENANCE ................................... 7<br />

<strong>HS25</strong> CHECK POINTS .............................. 8<br />

<strong>HS25</strong> CONDENSING UNIT<br />

<strong>HS25</strong> condensing units are designed for expansion<br />

valve systems only. They are not designed for RFC systems.<br />

Refer to <strong>Lennox</strong> engineering handbook for expansion<br />

valve kits which must be ordered separately.<br />

SHIPPING AND PACKING LIST<br />

1-- Assembled <strong>HS25</strong> condensing unit<br />

1-- Filter/drier (field--installed)<br />

Check unit for shipping damage. Consult last carrier<br />

immediately if damage is found.<br />

GENERAL INFORMATION<br />

These instructions are intended as a general guide and<br />

do not supersede national or local codes in any way.<br />

Authorities having jurisdiction should be consulted before<br />

installation.<br />

IMPORTANT<br />

The Clean Air Act of 1990 bans the intentional<br />

venting of refrigerant (CFC’s and HCFC’s) as of July<br />

1, 1992. Approved methods of recovery, recycling<br />

or reclaiming must be followed. Fines and/or incarceration<br />

may be levied for non--compliance.<br />

RETAIN THESE <strong>INSTRUCTIONS</strong><br />

FOR FUTURE REFERENCE<br />

WARNING<br />

Product contains fiberglass wool.<br />

Disturbing the insulation in this product during<br />

installation, maintenance, or repair will expose<br />

you to fiberglass wool. Breathing this may cause<br />

lung cancer. (Fiberglass wool is known to the<br />

State of California to cause cancer.)<br />

Fiberglass wool may also cause respiratory, skin,<br />

and eye irritation.<br />

To reduce exposure to this substance or for further<br />

information, consult material safety data sheets<br />

available from address shown below, or contact<br />

your supervisor.<br />

<strong>Lennox</strong> Industries Inc.<br />

P.O. Box 799900<br />

Dallas, TX 75379--9900<br />

3DJH


<strong>HS25</strong> UNIT DIMENSIONS--INCHES (MM)<br />

INLET AIR<br />

<strong>HS25</strong><br />

CONDENSING<br />

UNIT<br />

COMPRESSOR<br />

INLET<br />

AIR<br />

B<br />

SUCTION LINE<br />

INLET<br />

(<strong>HS25</strong>-211-460)<br />

LIQUID<br />

LINE INLET<br />

(<strong>HS25</strong>-510-650)<br />

ELECTRICAL<br />

INLETS<br />

INLET AIR<br />

TOP VIEW<br />

C<br />

DISCHARGE AIR<br />

A<br />

LIQUID<br />

LINE INLET<br />

(<strong>HS25</strong>-211-460)<br />

SUCTION<br />

LINE INLET<br />

(<strong>HS25</strong>-510-650)<br />

L<br />

D<br />

2-9/16<br />

(65)<br />

H<br />

J<br />

K<br />

K<br />

J<br />

2-3/4 (70)<br />

F<br />

4-7/8 (22) 4<br />

4<br />

(102)<br />

(102)<br />

E<br />

G<br />

FRONT VIEW<br />

H<br />

1-3/8<br />

(35)<br />

SIDE VIEW<br />

6-1/16<br />

(154)<br />

Model No. A B C D E F G H J K L<br />

<strong>HS25</strong>-211<br />

in. 27-7/8 25-7/8 29-7/8 7-1/4 22-7/16 14-7/16 22-1/8 1-7/8 2-7/8 5-1/2 4-1/2<br />

<strong>HS25</strong>-261 mm 708 657 759 184 570 367 562 48 73 140 114<br />

<strong>HS25</strong>-311 in. 30-7/8 32-1/8 34-1/16 8-1/4 26-5/8 18-5/8 28-1/8 2 3-7/8 7-1/2 4-1/2<br />

<strong>HS25</strong>-411-413<br />

413<br />

<strong>HS25</strong>-461-463 mm 784 816 865 210 676 473 714 51 98 191 114<br />

<strong>HS25</strong>-511-513<br />

<strong>HS25</strong>-651-653<br />

in. 40-7/8 32-1/8 34-1/16 15-1/4 26-5/8 18-5/8 28-1/8 2 3-7/8 7-1/2 8-1/2<br />

mm 1038 816 865 387 676 473 714 51 98 191 216<br />

3DJH


<strong>HS25</strong> PARTS ARRANGEMENT<br />

CONDENSER FAN<br />

(NOT SHOWN)<br />

TOP OF CABINET<br />

DUAL CAPACITOR<br />

(Single--Phase Units)<br />

<strong>HS25</strong> UNIT COMPONENTS<br />

TD1--1<br />

TIME DELAY<br />

FAN CAPACITOR<br />

(Three--Phase Units)<br />

CONTACTOR<br />

THERMOMETER<br />

WELL<br />

LIQUID LINE<br />

SERVICE VALVE<br />

AND GAUGE PORT<br />

HIGH PRESSURE<br />

SWITCH<br />

COMPRESSOR<br />

SUCTION<br />

SERVICE<br />

VALVE<br />

AND GAUGE PORT<br />

(LIVE)<br />

SUCTION<br />

GAUGE<br />

PORT<br />

COMPRESSOR<br />

TERMINAL BOX<br />

ACCUMULATOR<br />

(<strong>HS25</strong>--511/651 ONLY)<br />

SETTING THE UNIT<br />

Refer to unit dimensions on page 1 for sizing mounting<br />

slab, platforms or supports. Refer to figure 2 for installation<br />

clearances.<br />

<strong>INSTALLATION</strong> CLEARANCES<br />

NOTE-- 48” (1219mm) CLEARANCE REQUIRED<br />

ON TOP OF UNIT.<br />

*36”<br />

(914mm)<br />

),*85( <br />

A--Slab Mounting<br />

When installing unit at grade level, install on a level<br />

slab high enough above grade to allow adequate drainage<br />

of water. Top of slab should be located so run--off<br />

water from higher ground will not collect around unit.<br />

B--Roof Mounting<br />

Install unit at a minimum of 4 inches above surface of the<br />

roof. Care must be taken to ensure weight of unit is properly<br />

distributed over roof joists and rafters. Either redwood<br />

or steel supports are recommended.<br />

36”<br />

(914mm)<br />

*36”<br />

(914mm)<br />

FIGURE 2<br />

36”<br />

(914mm)<br />

*One dimension may be 12” (305 mm).<br />

ELECTRICAL<br />

Wiring must conform to current standards of the National<br />

Electric Code (NEC), Canadian Electrical Code<br />

(CEC) and local codes. Refer to the furnace or blower<br />

coil installation instructions for additional wiring application<br />

diagrams and refer to unit rating plate for<br />

minimum circuit ampacity and maximum overcurrent<br />

protection size.<br />

WARNING<br />

Unit must be grounded in accordance with<br />

national and local codes.<br />

Electric Shock Hazard.<br />

Can cause injury or death.<br />

3DJH


A--Line Voltage<br />

To facilitate conduit, knockouts are provided in cabinet<br />

panel. Route conduit through knockout in cabinet and<br />

connect to side of control panel. Refer to figure 3 for<br />

thermostat, furnace and condensing unit wire connections<br />

and figure 4 for field wiring diagram.<br />

Note--Units are approved for use with copper conductors<br />

only.<br />

B--24V, Class II Circuit<br />

24V, Class II Circuit connections are made up below control<br />

box.<br />

Note--A complete unit wiring diagram is located inside<br />

the unit access panel.<br />

<strong>HS25</strong> and FURNACE (GAS OR ELECTRIC)<br />

THERMOSTAT CONNECTIONS<br />

(Some connections may not apply.<br />

Refer to specific thermostat and furnace.)<br />

Furnace Thermostat <strong>HS25</strong><br />

R<br />

W1<br />

W2<br />

Y<br />

G<br />

C<br />

POWER<br />

1ST STAGE AUX. HEAT<br />

2ND STAGE AUX. HEAT<br />

W2<br />

INDOOR BLOWER<br />

COMMON<br />

R<br />

W1<br />

Y<br />

G<br />

C<br />

COMPRESSOR<br />

COMMON<br />

Condensing<br />

Unit<br />

<strong>HS25</strong><br />

COMPRESSOR<br />

<strong>HS25</strong><br />

COMMON<br />

FIGURE 3<br />

<strong>HS25</strong> CONDENSING UNIT<br />

FIELD WIRING DIAGRAM<br />

CONDENSING UNIT<br />

ROOM THERMOSTAT<br />

TYPICAL<br />

INDOOR UNIT<br />

C<br />

Y1<br />

G<br />

W<br />

RC<br />

RH<br />

TB1<br />

TRANSFORMER<br />

R<br />

W1<br />

G<br />

TO<br />

HEATING<br />

CONTROLS<br />

TO<br />

COOLING SPEED<br />

24v<br />

T1<br />

YELLOW<br />

BLACK OR BLUE<br />

NOTE--SEE UNIT WIRING DIAGRAM<br />

FOR POWER SUPPLY CONNECTIONS.<br />

TO 24V CLASS II POWER SOURCE<br />

-- 20 VA MINIMUM<br />

W2<br />

W3<br />

C<br />

24V,<br />

CLASS II<br />

JUNCTION<br />

BOX<br />

TO<br />

HEATING<br />

SPEED<br />

POWER<br />

YELLOW<br />

GROUND<br />

PER NATIONAL<br />

AND LOCAL<br />

CODES<br />

K3 INDOOR BLOWER RELAY<br />

NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH BLOWER RELAY, IT MUST BE<br />

FIELD PROVIDED AND INSTALLED (P--8--3251 OR EQUIVALENT)<br />

24V, CLASS II VOLTAGE INSTALLED AT FACTORY<br />

24V, CLASS II VOLTAGE FIELD INSTALLED<br />

FIGURE 4<br />

3DJH


PLUMBING<br />

Field refrigerant piping consists of liquid and suction<br />

lines from the condensing unit (sweat connections) to<br />

the indoor evaporator coil. Use <strong>Lennox</strong> L10 (flare) or L15<br />

(sweat) series line sets as shown in table 1 or use field--<br />

fabricated refrigerant lines. Refer to the piping section of<br />

the <strong>Lennox</strong> Unit Information Service Manual for proper<br />

size, type and application of field--fabricated lines.<br />

Sweat Connection Procedure<br />

1-- End of refrigerant line must be cut square, kept<br />

round, free from nicks or dents and deburred (I.D.<br />

and O.D.)<br />

2-- Wrap a wet cloth around the valve body and copper<br />

tube stub; braze the line set tubing to the valve.<br />

3-- Quench joint with water or a wet cloth to prevent<br />

possible heat damage to the valve core and opening<br />

port.<br />

IMPORTANT--Tube end must stay bottomed in the<br />

fitting during final assembly to ensure proper seating,<br />

sealing and rigidity.<br />

4-- Install filter drier, provided with unit, in the liquid<br />

line as close as possible to the expansion device.<br />

If refrigerant tubes are routed through a wall, seal and<br />

isolate the opening so vibration is not transmitted to<br />

the building.<br />

NOTE-Line length should be no greater than 50 feet<br />

(15.2 m). Select line set diameters from table 1 to ensure<br />

oil return to compressor.<br />

+6<br />

81,7<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

/,48,'<br />

/,1(<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

7$%/( <br />

5()5,*(5$17 /,1( .,76<br />

68&7,21<br />

/,1(<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

LQ<br />

PP<br />

/<br />

/,1( 6(76<br />

/ <br />

IW IW<br />

PP<br />

/ <br />

IW IW<br />

PP<br />

/ <br />

IW IW<br />

PP<br />

),(/'<br />

)$%5,&$7('<br />

/<br />

/,1( 6(76<br />

/ <br />

IW IW<br />

PP<br />

/ <br />

IW IW<br />

PP<br />

/ <br />

IW IW<br />

PP<br />

),(/'<br />

)$%5,&$7('<br />

REFRIGERATION<br />

Service Valves and Gauge Manifold Attachment<br />

The liquid line and suction line service valves and<br />

gauge ports are accessible on inside of unit. These<br />

gauge ports are used for leak testing, evacuating,<br />

charging and checking charge.<br />

IMPORTANT--Services valves are closed to line set connections.<br />

Do not open until refrigerant lines and indoor<br />

coil have been leak tested and evacuated. All precautions<br />

should be exercised to keep the system free from<br />

dirt, moisture and air.<br />

/($. 7(67,1*<br />

After the line set has been connected to the indoor and<br />

outdoor units, the line set connections and indoor unit<br />

must be checked for leaks.<br />

WARNING<br />

Never use oxygen to pressurize refrigeration or air<br />

conditioning system. Oxygen will explode on contact<br />

with oil and could cause personal injury.<br />

When using high pressure gas such as nitrogen or<br />

CO 2 for this purpose, be sure to use a regulator<br />

that can control the pressure down to 1 or 2 psig<br />

(6.9 to 13.8 kPa).<br />

Using an Electronic Leak Detector or Halide<br />

1-- Connect a cylinder of nitrogen with a pressure regulating<br />

valve to the center port of the manifold<br />

gauge set.<br />

2-- Connect the high pressure hose of the manifold<br />

gauge set to the service port of the suction valve.<br />

(Normally, the high pressure hose is connected to<br />

the liquid line port, however, connecting it to the<br />

suction port better protects the manifold gauge set<br />

from high pressure damage.)<br />

3-- With both manifold valves closed, open the valve<br />

on the R22 bottle (vapor only).<br />

4-- Open the high pressure side of the manifold to allow<br />

R22 into the line set and indoor unit. Weigh in a<br />

trace amount of R22. [A trace amount is a maximum<br />

of 2 ounces (57g) refrigerant or 3 pounds (31<br />

kPa) pressure]. Close the valve on the R22 bottle<br />

and the valve on the high pressure side of the manifold<br />

gauge set. Disconnect R22 bottle.<br />

5-- Adjust nitrogen pressure to 150 psig (1034 kPa). Open<br />

the valve on the high side of the manifold gauge set<br />

which will pressurize line set and indoor unit.<br />

6-- After a short period of time, open a refrigerant port<br />

to make sure the refrigerant added is adequate to be<br />

detected. (Amounts of refrigerant will vary with line<br />

lengths.) Check all joints for leaks. Purge nitrogen<br />

and R22 mixture. Correct any leaks and recheck.<br />

(9$&8$7,1*<br />

Evacuating the system of non--condensables is critical<br />

for proper operation of the unit. Non--condensables are<br />

defined as any gas that will not condense under temperatures<br />

and pressures present during operation of an air<br />

conditioning system. Non--condensables and water vapor<br />

combine with refrigerant to produce substances<br />

that corrode copper piping and compressor parts.<br />

1-- Connect manifold gauge set to the service valve<br />

ports as follows: low pressure gauge to suction<br />

line service valve; high pressure gauge to liquid<br />

line service valve.<br />

3DJH


2-- Connect the vacuum pump (with vacuum gauge)<br />

to the center port of the manifold gauge set.<br />

3-- Open both manifold valves and start vacuum pump.<br />

4-- Evacuate the line set and indoor unit to anabsolute<br />

pressure of 23mm of mercury or approximately 1<br />

inch of mercury. During the early stages of evacuation,<br />

it is desirable to close the manifold gauge<br />

valve at least once to determine if there is a rapid<br />

rise in absolute pressure. A rapid rise in pressure<br />

indicates a relatively large leak. If this occurs, the<br />

leak testing procedure must be repeated.<br />

NOTE -- The term absolute pressure means the total<br />

actual pressure within a given volume or system,<br />

above the absolute zero of pressure. Absolute<br />

pressure in a vacuum is equal to atmospheric pressure<br />

minus vacuum pressure.<br />

5-- When the absolute pressure reaches 23mm of mercury,<br />

close the manifold gauge valves, turn off the<br />

vacuum pump and disconnect the manifold gauge<br />

center port hose from vacuum pump. Attach the<br />

manifold center port hose to a nitrogen cylinder<br />

with pressure regulator set to 150 psig (1034 kPa)<br />

and purge the hose. Open the manifold gauge<br />

valves to break the vacuum in the line set and indoor<br />

unit. Close the manifold gauge valves.<br />

&$87,21<br />

Danger of Equipment Damage.<br />

Avoid deep vacuum operation. Do not use compressors<br />

to evacuate a system.<br />

Extremely low vacuums can cause internal arcing<br />

and compressor failure.<br />

Damage caused by deep vacuum operation will<br />

void warranty.<br />

6-- Shut off the nitrogen cylinder and remove the manifold<br />

gauge hose from the cylinder. Open the manifold<br />

gauge valves to release the nitrogen from the<br />

line set and indoor unit.<br />

7-- Reconnect the manifold gauge to the vacuum<br />

pump, turn the pump on and continue to evacuate<br />

the line set and indoor unit until the absolute pressure<br />

does not rise above .5mm of mercury within a<br />

20 minute period after shutting off the vacuum<br />

pump and closing the manifold gauge valves.<br />

8-- Depending on the equipment used to determine<br />

the vacuum level, absolute pressure of .5mm of<br />

mercury is equal to 500 microns.<br />

9-- When the absolute pressure requirement above has<br />

been met, disconnect the manifold hose from the<br />

vacuum pump and connect it to an upright bottle of<br />

R22 refrigerant. Open the manifold gauge valves to<br />

break the vacuum in the line set and indoor unit.<br />

Close manifold gauge valves and shut off R22 bottle<br />

and remove manifold gauge set.<br />

START--UP<br />

Cooling Start--up<br />

1-- Rotate the fan to check for frozen bearings or binding.<br />

2-- Inspect all factory and field--installed wiring for<br />

loose connections.<br />

3-- Open liquid line and suction line service valves to<br />

release refrigerant charge (contained in condensing<br />

unit) into system. Replace and tighten caps.<br />

Use a back--up wrench on the suction and liquid<br />

valves when removing or replacing valve caps.<br />

4-- To open suction valve, remove hex cap and turn<br />

valve stem fully open using an Allen (hex) wrench.<br />

To open liquid valve, remove cap and turn valve<br />

stem until it is fully open and back--seated.<br />

NOTE--When replacing valve caps, the caps should<br />

be made finger tight and then tightened an additional<br />

1/6th of a turn.<br />

5-- Check voltage supply at the disconnect switch. The<br />

voltage must be within range listed on unit nameplate.<br />

If not, do not start equipment until the power<br />

company has been consulted and the voltage<br />

condition corrected.<br />

6-- Set thermostat for a cooling demand, turn on power<br />

to blower and close condensing unit disconnect<br />

switch to start.<br />

7-- Recheck unit voltage with unit running. Power<br />

must be within range shown on unit nameplate.<br />

Check amperage draw of unit. Refer to unit nameplate<br />

for correct running amps.<br />

Three--Phase Compressor Rotation<br />

Three--phase scroll compressors must be phased sequentially<br />

to ensure correct compressor rotation and<br />

operation. At compressor start--up, a rise in discharge<br />

and drop in suction pressures indicate proper compressor<br />

phasing and operation. If discharge and suctions<br />

pressures do not perform normally, follow the<br />

steps below to correctly phase in the unit.<br />

1-- Disconnect power to the unit.<br />

2-- Reverse any two field power leads to the unit.<br />

3-- Reapply power to the unit.<br />

Discharge and suction pressures should operate at<br />

their normal start--up ranges.<br />

3DJH


NOTE--Compressor noise level will be significantly<br />

higher when phasing is incorrect and the unit will not<br />

provide cooling when compressor is operating backwards.<br />

Continued backward operation will cause the<br />

compressor to cycle on internal protector.<br />

3DJH


CHARGING<br />

Units are factory charged with the amount of R--22 refrigerant<br />

indicated on the unit rating plate. This charge<br />

is based on a matching indoor coil and outdoor coil<br />

with 20 ft. (6.1m) line set. For varying lengths of line set,<br />

refer to table 2 for refrigerant charge adjustment.<br />

/LTXLG /LQH<br />

6HW 'LDPHWHU<br />

LQ<br />

PP<br />

7$%/( <br />

2]V SHU IW J SHU P DGMXVW<br />

IURP IW P OLQH VHW<br />

RXQFHV SHU IW<br />

J SHU P<br />

,I OLQH OHQJWK LV JUHDWHU WKDQ IW P DGG WKLV DPRXQW ,I OLQH OHQJWK<br />

LV OHVV WKDQ IW P VXEWUDFW WKLV DPRXQW<br />

If the system is void of refrigerant, the recommended<br />

and most accurate method of charging is to weigh<br />

the refrigerant according to the total amount shown<br />

on the unit nameplate. If weighing facilities are not<br />

available or if unit is just low on charge, use the following<br />

procedure:<br />

([SDQVLRQ 9DOYH 6\VWHPV<br />

The following procedure is intended as a general<br />

guide and is for use on expansion valve systems only.<br />

For best results, indoor temperature should be 70E F<br />

(21EC) to 80E F (26EC). Be sure to monitor system<br />

pressures while charging.<br />

1-- Record outdoor ambient temperature.<br />

2-- Operate unit to allow system to stabilize both before<br />

and after each charge adjustment.<br />

3-- Check to make sure thermometer well is filled<br />

with mineral oil before checking liquid line temperature.<br />

4-- Outdoor temperature should be 60E F(16EC) or<br />

above. Place thermometer in well and read liquid<br />

line temperature. Difference between ambient<br />

and liquid temperatures should match values<br />

given in table 3. Refrigerant must be added to<br />

lower approach temperature and removed to increase<br />

approach temperature. Loss of charge results<br />

in low capacity and efficiency.<br />

02'(/ 12<br />

+6 <br />

+6 <br />

+6 <br />

+6 <br />

+6 <br />

+6 <br />

+6 <br />

7$%/( <br />

$3352$&+ 0(7+2'<br />

/,48,' 7(03 0,186 $0%,(17 7(03 E) E&<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

1RWH )RU EHVW UHVXOWV WKH VDPH WKHUPRPHWHU VKRXOG EH XVHG WR FKHFN<br />

ERWK RXWGRRU DPELHQW DQG OLTXLG WHPSHUDWXUHV<br />

SYSTEM OPERATION<br />

Condensing unit and indoor blower cycle on demand<br />

from room thermostat. When thermostat blower<br />

switch is moved to ON position, indoor blower operates<br />

continuously.<br />

Compressor Time Delay (TD1)<br />

A compressor time delay is used to prevent compressor<br />

short cycling and to prevent the compressor from<br />

running backwards. When there is demand for a cooling<br />

cycle, the control delays the compressor from starting<br />

for a minimum of 8.5 seconds. Do not bypass the<br />

control.<br />

Discharge Thermostat<br />

The Copeland Scroll compressor is equipped with a<br />

discharge line thermostat that removes power from<br />

the compressor when discharge temperatures reach<br />

approximately 280E F (138EC). The thermostat resets<br />

automatically at 130E F (54EC).<br />

CAUTION<br />

Danger of equipment damage. Do not bypass the<br />

discharge thermostat.<br />

High Pressure Switch<br />

<strong>HS25</strong> units are equipped with a high pressure switch<br />

that is located in the discharge line of the compressor.<br />

The switch (SPST, manual reset, normally closed) removes<br />

power from the compressor when discharge<br />

pressure rises above factory setting at 410 + 10 psi<br />

(2827 + 69 kPa).<br />

Low Pressure Switch<br />

<strong>HS25</strong> units are also equipped with a low pressure<br />

switch that is located in the suction line of the compressor.<br />

The switch (SPST, auto--reset, normally closed) removes<br />

power from the compressor when suction line<br />

pressure drops below factory setting at 25 +5 psi (172 +<br />

34 kPa).<br />

MAINTENANCE<br />

WARNING<br />

Electric shock hazard. Can cause injury<br />

or death. Before attempting to perform<br />

any service or maintenance, turn<br />

the electrical power to unit OFF at disconnect<br />

switch(es). Unit may have<br />

multiple power supplies.<br />

At the beginning of each cooling season, the system<br />

should be checked as follows:<br />

1-- Clean and inspect condenser coil. Coil may be<br />

flushed with a water hose.<br />

2-- Condenser fan motor is prelubricated and sealed.<br />

No further lubrication is needed.<br />

3DJH


3-- Visually inspect connecting lines and coils for evidence<br />

of oil leaks.<br />

4-- Check wiring for loose connections.<br />

5-- Check for correct voltage at unit (unit operating).<br />

6-- Check amp--draw condenser fan motor.<br />

Unit nameplate _________ Actual ____________ .<br />

NOTE--If owner complains of insufficient cooling, the unit<br />

should be gauged and refrigerant charge checked. Refer<br />

to section on refrigerant charging in this instruction.<br />

Evaporator Coil<br />

1-- Clean coil, if necessary.<br />

2-- Check connecting lines and coils for evidence of oil<br />

leaks.<br />

3-- Check condensate line and clean, if necessary.<br />

Indoor Unit<br />

1-- Clean or change filters.<br />

2-- Adjust blower speed for cooling. The pressure<br />

drop over the coil should be measured to determine<br />

the correct blower CFM. Refer to the unit information<br />

service manual for pressure drop tables<br />

and procedure.<br />

3-- On belt drive blowers, check belt for wear and<br />

proper tension.<br />

4-- Check all wiring for loose connections<br />

5-- Check for correct voltage at unit (blower operating).<br />

6-- Check amp--draw on blower motor<br />

Unit nameplate_________ Actual ____________.<br />

<strong>HS25</strong> CHECK POINTS<br />

67$57 83 $1' 3(5)250$1&( &+(&. /,67<br />

-RE 1DPH<br />

-RE /RFDWLRQ<br />

,QVWDOOHU<br />

8QLW 0RGHO 1R<br />

1DPHSODWH 9ROWDJH<br />

-RE 1R<br />

&LW\<br />

&LW\<br />

6HULDO 1R<br />

$PSV<br />

'DWH<br />

6WDWH<br />

6WDWH<br />

6HUYLFHPDQ<br />

0LQLPXP &LUFXLW $PSDFLW\<br />

0D[LPXP 2YHUFXUUHQW 3URWHFWLRQ 6L]H<br />

6XSSO\<br />

&RPSUHVVRU<br />

&RQGHQVHU )DQ<br />

(OHFWULFDO &RQQHFWLRQV 7LJKW"<br />

6XSSO\ 9ROWDJH 8QLW 2II<br />

&22/,1* 6(&7,21<br />

5HIULJHUDQW /LQHV<br />

/HDN &KHFNHG"<br />

6HUYLFH 9DOYHV %DFNVHDWHG"<br />

3URSHUO\ ,QVXODWHG"<br />

&RQGHQVHU )DQ &KHFNHG"<br />

6HUYLFH 9DOYH &DSV 7LJKW"<br />

6HUYLFH 9DOYH &DSV 7LJKW"<br />

9ROWDJH :LWK &RPSUHVVRU 2SHUDWLQJ<br />

,QGRRU )LOWHU &OHDQ"<br />

,QGRRU %ORZHU 530<br />

63 'URS 2YHU (YDSRUDWRU 'U\<br />

&RQGHQVHU (QWHULQJ $LU 7HPSHUDWXUH<br />

'LVFKDUJH 3UHVVXUH<br />

6XFWLRQ 3UHVVXUH<br />

5HIULJHUDQW &KDUJH &KHFNHG"<br />

7+(50267$7<br />

&DOLEUDWHG" 3URSHUO\ 6HW"<br />

/HYHO"<br />

3DJH

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!