AQUAMIST ® Systems utilize the newest and most unique nozzles developed and approved<br />
for fire protection. <strong>The</strong>y offer an alternative to gaseous, foam, and heavy density sprinkler systems.<br />
By utilizing a higher pressure than a normal sprinkler system, but a 50-80% lower water<br />
flow, the AquaMist Systems use less water more effectively, reduce pipe sizes and labor costs,<br />
and minimize cleanup and water damage.<br />
AM10 AQUAMIST ®<br />
K Factor K=0.24 (3,5)<br />
Thread Size<br />
Finish<br />
Tech Data<br />
1/2” (15 mm)<br />
Stainless Steel<br />
TD1174<br />
• Open spray nozzles<br />
• Designed for use in water mist systems<br />
protecting flammable liquids and turbine<br />
bearings<br />
• Minimal water demand, approximately<br />
3.1 GPM/nozzle at 170psi<br />
(11,73 lpm at 11,6 bar)<br />
• Mist represents latest in fire protection<br />
technology<br />
• For use in “low pressure” mist applications<br />
• Minimum operating pressure is<br />
170 psi (11,6 bar)<br />
• Nozzle coverage: maximum 86 sq. ft. (8m2)<br />
• Listed & Approved – UL, FM<br />
Open Type Mist Nozzle<br />
AM4 AQUAMIST ®<br />
K Factor K=0.24 (3,5)<br />
Thread Size<br />
Finish<br />
Tech Data<br />
1/2” (15 mm)<br />
Stainless Steel<br />
TD1173<br />
• Open, directional spray nozzles<br />
• Listed & Approved for the protection of<br />
flammable liquid hazards (UL/FM)<br />
• Approved for protection of gas turbines (FM)<br />
• Maximum ceiling height, 26' 3" (8 m)<br />
• Maximum compartment volume<br />
– UL - 56,500 ft3 (1,600 m3)<br />
– FM - 45,203 ft3 (1,280 m3)<br />
• Maximum utilization of water for<br />
flammable liquid fire protection<br />
• Nozzle coverage: maximum 172 ft2 (16 m2)<br />
• Nozzle pressure: 185 to 250 psi<br />
(12,8 to 17,2 bar)<br />
Open Type Mist Nozzle<br />
AM15 AQUAMIST ®<br />
K Factor 4.7 lpm/bar 1/2,<br />
0.33 gpm/psi 0.5<br />
Finish Stainless Steel<br />
Tech Data<br />
Contact <strong>Tyco</strong> <strong>Fire</strong> <strong>Products</strong><br />
• Listed & Approved – Marine Type Approved<br />
by Lloyds, USCG, DNV, American Bureau<br />
of Shipping, MCA, Germanischer Lloyd,<br />
Bureau Veritas<br />
• Intended Applications – IMO Mandated<br />
Local Application System for Protection of<br />
Class A Machinery Spaces<br />
• Maximum Distance between nozzles (to<br />
plane of protection) - Vertical Clearance<br />
Nozzle Spacing<br />
– 1m to 3.5m nozzles - 4.0 meter spacing<br />
– 3.5m to 5.0m nozzles - 3.5 meter spacing<br />
– 5.0 m to 10.0 m nozzles - 3.0 meter<br />
spacing<br />
• Nozzle pressure: 175-250 psi<br />
Open Type Mist Nozzle<br />