AQUAMIST ® Systems utilize the newest and most unique nozzles developed and approved<br />

for fire protection. <strong>The</strong>y offer an alternative to gaseous, foam, and heavy density sprinkler systems.<br />

By utilizing a higher pressure than a normal sprinkler system, but a 50-80% lower water<br />

flow, the AquaMist Systems use less water more effectively, reduce pipe sizes and labor costs,<br />

and minimize cleanup and water damage.<br />

AM10 AQUAMIST ®<br />

K Factor K=0.24 (3,5)<br />

Thread Size<br />

Finish<br />

Tech Data<br />

1/2” (15 mm)<br />

Stainless Steel<br />

TD1174<br />

• Open spray nozzles<br />

• Designed for use in water mist systems<br />

protecting flammable liquids and turbine<br />

bearings<br />

• Minimal water demand, approximately<br />

3.1 GPM/nozzle at 170psi<br />

(11,73 lpm at 11,6 bar)<br />

• Mist represents latest in fire protection<br />

technology<br />

• For use in “low pressure” mist applications<br />

• Minimum operating pressure is<br />

170 psi (11,6 bar)<br />

• Nozzle coverage: maximum 86 sq. ft. (8m2)<br />

• Listed & Approved – UL, FM<br />

Open Type Mist Nozzle<br />

AM4 AQUAMIST ®<br />

K Factor K=0.24 (3,5)<br />

Thread Size<br />

Finish<br />

Tech Data<br />

1/2” (15 mm)<br />

Stainless Steel<br />

TD1173<br />

• Open, directional spray nozzles<br />

• Listed & Approved for the protection of<br />

flammable liquid hazards (UL/FM)<br />

• Approved for protection of gas turbines (FM)<br />

• Maximum ceiling height, 26' 3" (8 m)<br />

• Maximum compartment volume<br />

– UL - 56,500 ft3 (1,600 m3)<br />

– FM - 45,203 ft3 (1,280 m3)<br />

• Maximum utilization of water for<br />

flammable liquid fire protection<br />

• Nozzle coverage: maximum 172 ft2 (16 m2)<br />

• Nozzle pressure: 185 to 250 psi<br />

(12,8 to 17,2 bar)<br />

Open Type Mist Nozzle<br />

AM15 AQUAMIST ®<br />

K Factor 4.7 lpm/bar 1/2,<br />

0.33 gpm/psi 0.5<br />

Finish Stainless Steel<br />

Tech Data<br />

Contact <strong>Tyco</strong> <strong>Fire</strong> <strong>Products</strong><br />

• Listed & Approved – Marine Type Approved<br />

by Lloyds, USCG, DNV, American Bureau<br />

of Shipping, MCA, Germanischer Lloyd,<br />

Bureau Veritas<br />

• Intended Applications – IMO Mandated<br />

Local Application System for Protection of<br />

Class A Machinery Spaces<br />

• Maximum Distance between nozzles (to<br />

plane of protection) - Vertical Clearance<br />

Nozzle Spacing<br />

– 1m to 3.5m nozzles - 4.0 meter spacing<br />

– 3.5m to 5.0m nozzles - 3.5 meter spacing<br />

– 5.0 m to 10.0 m nozzles - 3.0 meter<br />

spacing<br />

• Nozzle pressure: 175-250 psi<br />

Open Type Mist Nozzle<br />

Other Styles of Closed (<strong>The</strong>rmally Sensitive) Nozzles are Available. For complete information, visit www.<strong>Tyco</strong>-<strong>Fire</strong>.com.