RETROFITTING WITH NON-CFC SUBSTITUTES<br />
important to follow the retrofit procedures.<br />
247 low temperature units retrofitted from R-502 to 69L.<br />
Evaporation temperature down to appr. -29°C. No lubrication change was necessary.<br />
Customers claim that energy requirement has decreased. There seems to be less compressor<br />
failures <strong>with</strong> retrofitted units than <strong>with</strong> R-502-units.<br />
7 medium temperature units retrofitted from CFC-12 to HFC-134a.<br />
Evaporation temperature down to appr. -0°C. Lubricant changed to polyol esteroil.<br />
2 units retrofitted from HFC-134a to 69 L.<br />
The <strong>retrofitting</strong> was done in order to increase the refrigeration capacity in the low temperature<br />
range. Lubricant changed to alcylbenzen lubricant.<br />
Due to less expensive <strong>retrofitting</strong>, Thermo King is also preparing for <strong>retrofitting</strong> from CFC-12<br />
to MP66 for old equipment.<br />