CTK.E Air cooled remote condenser with axial fans Main features Axial fans Vertical air flow Horizontal air flow LN version Technical features • Housing Frame made of goffered aluminium alloy to ensure total mechanical and weathering resistance • Air heat exchanger Finned coil made with copper pipes and aluminium fins offering a high exchange surface area. • Fan Low speed, axial-flow fans fitted with accident-prevention protective grille; directly coupled motor with built-in thermal cutout and IP 54 protection degree; aerodynamic housing and wing profile blades increase efficiency • Electrical board IP55 protection degree, <strong>com</strong>plete with main isolator. Accessories • Modulating fan speed condensing control (up to -15°C outdoor temperature) 88 www.euroklimat.it
TECHNICAL DATA CTK.E 0040 D 0050 D 0080 D 0100 D 0120 D 0150 D 0180 D 0220 D 0300 D Nominal capacity(1) kW 16,6 26,4 34 39,5 50,0 59,7 66,9 79,3 99,1 Independent gas circuits n° 1 1 1 1 1 1 1 1 1 Total air flow mc/h 4330 6900 9850 9600 14700 13750 16250 18200 27800 Fans: q.ty - power input n° x kW 1x0,28 1x0,37 1x0,63 1x0,63 2x0,37 2x0,37 2x0,63 2x0,63 3x0,63 Fans total current absorption A 1,3 1,7 3 3 3,4 3,4 6 6 9 Power supply - 230V/1/50Hz Sound power /Sound pressure(2) dB(A) 69/52 73/56 78/61 78/61 76/59 76/59 81/64 81/64 83/66 Lenght mm 1010 1165 1410 1410 1860 1860 1860 2415 3215 Depth mm 730 930 1130 1130 1130 1130 1130 1130 1130 Height mm 900 900 900 900 900 900 900 900 900 Shipping weight Kg 40 51 61 70 97 110 130 165 190 CTK.E 0350 D 0400 D 0450 D Nominal capacity(1) kW 113,1 127,4 145,3 Independent gas circuits n° 1 1 1 Total air flow mc/h 26480 36400 34500 Fans: q.ty - power input n° x kW 3x0,63 4x0,63 4x0,63 Fans total current absorption A 9 12 12 Power supply - 230V/1/50Hz Sound power /Sound pressure(2) dB(A) 83/66 84/67 84/67 Lenght mm 3215 3965 3965 Depth mm 1130 1130 1130 Height mm 900 900 900 Shipping weight Kg 220 235 275 Data reffered to 1 Outdoor air temperature 35°C - Condensing temperature 52°C (dew) 2 Data measured at 5m at open field CTK.E LN 0040 D 0050 D 0080 D 0100 D 0120 D 0150 D 0180 D 0220 D 0300 D Nominal capacity(1) kW 13,3 20,3 28,0 31,9 38,3 44,7 54,3 63,8 81,7 Independent gas circuits n° 1 1 1 1 1 1 1 1 1 Total air flow mc/h 3500 5600 7900 7700 11800 11000 13000 14600 22300 Fans: q.ty - power input n° x kW 1x0,15 1x0,22 1x0,31 1x0,31 2x0,22 2x0,22 2x0,31 2x0,31 3x0,31 Fans total current absorption A 0,7 1,1 1,6 1,6 2,2 2,2 3,1 3,1 4,7 Power supply - 230V/1/50Hz Sound power /Sound pressure(2) dB(A) 66/49 70/53 75/58 75/68 73/56 73/56 78/61 78/61 80/63 Lenght mm 1010 1165 1410 1410 1860 1860 1860 2415 3215 Depth mm 730 930 1130 1130 1130 1130 1130 1130 1130 Height mm 900 900 900 900 900 900 900 900 900 Shipping weight Kg 40 51 61 70 97 110 130 165 190 CTK.E LN 0350 D 0400 D 0450 D Nominal capacity(1) kW 91,3 105,2 118 Independent gas circuits n° 1 1 1 Total air flow mc/h 21200 29200 27600 Fans: q.ty - power input n° x kW 3x0,31 4x0,31 4x0,31 Fans total current absorption A 4,7 6,2 6,2 Power supply - 230V/1/50Hz Sound power /Sound pressure(3) dB(A) 80/63 81/64 81/64 Lenght mm 3215 3965 3965 Depth mm 1130 1130 1130 Height mm 900 900 900 Shipping weight Kg 220 235 275 Data reffered to 1 Outdoor air temperature 35°C - Condensing temperature 52°C (dew) 2 Dato measured at 5m at open field 3 Data measured at 5m at open field www.euroklimat.it 89