<strong>Flow</strong> <strong>Meter</strong> (<strong>compressed</strong> <strong>air</strong>/<strong>gases</strong>) | <strong>FC100</strong>-<strong>CA</strong><br />
<strong>FC100</strong>-<strong>CA</strong> with relay outputs<br />
Connection diagrams<br />
1<br />
analogue outputs **<br />
C1, V1, V2<br />
signal outputs<br />
RS232<br />
communication<br />
interface<br />
TXD<br />
RXD<br />
GND<br />
SGND<br />
NC*<br />
1 2 3 4<br />
1 2 3 4 5 6 7 1 2 3 4 5 6 7<br />
XSE XAO XAH<br />
XV XSK XRE<br />
1 2 3<br />
1 2 3 4 5 6 7 8 9 10<br />
ANAO1<br />
white R(Tref) -LO<br />
calorimetric monitoring head<br />
ANA1GND<br />
blue AGND<br />
SGNDA1 ** LifYCY 4x 2x0,2 mm 2<br />
red IS<br />
SGNDA2 **<br />
ANAO2<br />
black SGND<br />
ANA2GND<br />
grey R(Tdiff)-LO<br />
NC*<br />
SGNDL 1<br />
LIM1<br />
LIM1COM<br />
/LIM1<br />
SGNDL 2<br />
LIM2<br />
LIM2COM<br />
/LIM2<br />
<strong>FC100</strong>-<strong>CA</strong> <strong>Flow</strong> Controller<br />
M<br />
1 2 3<br />
shield ground<br />
+U V<br />
power supply<br />
-U V<br />
yellow R(HEIZ) -LO<br />
green R(HEIZ) -H I<br />
brown R(Tref) -HI<br />
pink R(Tdiff)-HI<br />
totalizer reset<br />
* NC: not connected<br />
** SGNDA1<br />
SGNDA2} ungrounded<br />
Apply shield on one side only.<br />
analogue outputs **<br />
C1, V1, V2<br />
<strong>FC100</strong>-<strong>CA</strong> with transistor outputs<br />
signal outputs<br />
RS232<br />
communication<br />
interface<br />
TXD<br />
RXD<br />
GND<br />
SGND<br />
NC*<br />
1<br />
2<br />
3<br />
4<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
XSE XAO XAH<br />
<strong>FC100</strong>-<strong>CA</strong><br />
XV XSK XRE<br />
1 2 3<br />
1 2 3 4 5 6 7 8 9 10<br />
ANAO1<br />
white R(Tref) -LO<br />
ANA1GND<br />
calorimetric monitoring head<br />
blue AGND<br />
SGNDA1 ** LifYCY 4x 2x0,2 mm 2<br />
red IS<br />
SGNDA2 **<br />
ANAO2<br />
black SGND<br />
ANA2GND<br />
grey R(Tdiff)-LO<br />
NC*<br />
pink R(Tdiff)-HI<br />
/ERROR E/-<br />
/ERROR C/+<br />
/BUSY/PULSE E/-<br />
/BUSY/PULSE C/+<br />
LIM2<br />
E/-<br />
LIM2<br />
C/-<br />
totalizer reset<br />
E/- emitter terminal<br />
LIM1<br />
E/-<br />
C/+ collector terminal<br />
LIM1<br />
C/+<br />
* NC: not connected<br />
** SGNDA1<br />
SGNDA2} ungrounded<br />
Apply shield on one side only.<br />
<strong>Flow</strong> Controller<br />
M<br />
1 2 3<br />
yellow<br />
green<br />
brown<br />
shield ground<br />
+U V<br />
-U V<br />
R(HEIZ) -LO<br />
R(HEIZ) -H I<br />
R(Tref) -HI<br />
power supply<br />
<strong>FC100</strong>-<strong>CA</strong> - Recommended connection of pulse output<br />
Electronic signal processing Electromagnetic pulse counter<br />
XSE XAO XAH<br />
1 2 3 4 1 2 3 4 5 6 7<br />
8<br />
1 2 3 4 5 6 7<br />
8<br />
1<br />
XSE XAO XAH<br />
2 3 4 1 2 3 4 5 6 7<br />
8<br />
1 2 3 4 5 6 7<br />
8<br />
zener voltage<br />
i C<br />
t L t ON t<br />
U C<br />
U V<br />
i L ≤ 10 mA<br />
U V<br />
U C<br />
i C<br />
U V < 36 V<br />
t<br />
CD<br />
t ON - pick-up time<br />
t L - time constant of breaking current<br />
inductance of the counter drive<br />