High performance surge protector<br />

for RS 485 interfaces<br />

Nominal impulse discharge current<br />

20 kA, 8/20 µs<br />

Operating current 0.5 A<br />

Direct mounting on DIN rail<br />

Equipment Protection for RS 485<br />

Interfaces<br />

Product description<br />

DataPro-RS485-Tr has been designed<br />

for the protection of RS485<br />

interfaces.<br />

Due to its high discharge capacity<br />

of 20 kA (line-to-ground, wave form<br />

8/20 µs) and to its easy installation<br />

on a DIN rail, it can be used universally.<br />

It consists of a two-stage protective<br />

circuit with gas-filled arresters used<br />

as primary protection. The fine protection<br />

is effected exclusively by<br />

filters and suppressor diodes. There<br />

are no significant leakage currents<br />

due to the absence of varistors,<br />

making remote alarm contact for<br />

fault indication and regular control<br />

checks unnecessary. In the event of<br />

an overload, the suppressor diodes<br />

will provoke a short-circuit (fail-safe)<br />

that will continue to protect the<br />

connected equipment and send a<br />

default message to the system.<br />

Dimensions (mm)<br />

70<br />

Subject to technical modifications, ©<strong>Leutron</strong><br />

<strong>Leutron</strong> <strong>GmbH</strong>, Humboldtstr. 30, D-70771 Leinfelden-Echterdingen<br />

Tel. +49 711 9 47 71-0, Fax +49 711 9 47 71-70, eMail: info@leutron.de, Internet: www.leutron.de


Surge Protection<br />

DataPro-RS485-Tr<br />

Technical Data<br />

Application<br />

Surge protective device for RS485-interfaces<br />

Type<br />

DataPro-RS485-Tr<br />

Rated D.C.voltage UN [V=] 5<br />

Max. D.C. operating voltage UB [V=] 6<br />

Max. A.C. operating voltage UB [V~] 4.25<br />

Max. operating current IB [A] 0.5<br />

Leakage current at Umax-DC IL [µA] ≤ 5<br />

Max. frequency (3 dB)* fG [kHz] 1000<br />

D.C. current resistance RDC [Ω] 1.8<br />

Longitudinal inductance L [µH] 10<br />

Capability line-to-ground C [nF] ≤ 3<br />

Protection level line-to-line (1kV/µs) Uas [V] ≤ 8.5<br />

Protection level line-to-ground (1kV/µs) Uas [V] ≤ 600<br />

Nom. impulse discharge current (8/20 µs) ISN [kA] 20<br />

Response time tA [ns] ≤ 1<br />

Operating temperature range t [°C] -25 - +85<br />

Max. cross section for terminal input [mm 2 ] 2.5 rigid or 1.5 stranded with sleeve<br />

Housing /Colour<br />

Polycarbonate halogen-free/yellow<br />

Casting compound<br />

Polyurethane<br />

Mounting 35 mm DIN 3 rail acc. to EN 50 022<br />

Article number 27 04 85<br />

* Measuring of insertion loss at 50 Ω<br />

Diagram<br />

Subject to technical modifications, ©<strong>Leutron</strong><br />

<strong>Leutron</strong> <strong>GmbH</strong>, Humboldtstr. 30, D-70771 Leinfelden-Echterdingen<br />

Tel. +49 711 9 47 71-0, Fax +49 711 9 47 71-70, eMail: info@leutron.de, Internet: www.leutron.de<br />

71

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!