Specification
Specification
Specification
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR<br />
2009 Samsung DVM Air Conditioners<br />
<br />
32 33<br />
<br />
<strong>Specification</strong> | DVM PLUS III / DVM PLUS III HR<br />
Module Type - High Efficiency<br />
Model<br />
28HP<br />
30HP<br />
32HP<br />
Model<br />
34HP<br />
36HP<br />
38HP<br />
Basic<br />
RVXVHT080GE / RVXVRT080GE<br />
1<br />
Basic<br />
RVXVHT080GE / RVXVRT080GE<br />
RVXVHT100GE / RVXVRT100GE<br />
2<br />
3<br />
2<br />
RVXVHT100GE / RVXVRT100GE<br />
2<br />
1<br />
1<br />
RVXVHT120GE / RVXVRT120GE<br />
1<br />
RVXVHT120GE / RVXVRT120GE<br />
1<br />
RVXVHT140GE / RVXVRT140GE<br />
RVXVHT140GE / RVXVRT140GE<br />
1<br />
1<br />
2<br />
Performance<br />
Horse Power<br />
HP<br />
28<br />
30<br />
32<br />
Performance<br />
Horse Power<br />
HP<br />
34<br />
36<br />
38<br />
Capacity<br />
Cooling * 1)<br />
kW<br />
78.4<br />
84.0<br />
89.6<br />
Capacity<br />
Cooling * 1)<br />
kW<br />
95.2<br />
100.8<br />
106.4<br />
Btu/h<br />
267,400<br />
286,500<br />
305,600<br />
Btu/h<br />
324,800<br />
343,900<br />
363,100<br />
Heating * 2)<br />
kW<br />
88.2<br />
94.5<br />
100.8<br />
Heating * 2)<br />
kW<br />
107.1<br />
113.4<br />
119.7<br />
Btu/h<br />
301,000<br />
322,500<br />
344,000<br />
Btu/h<br />
365,500<br />
387,000<br />
408,500<br />
Power<br />
Nominal Input<br />
Cooling<br />
kW<br />
21.32<br />
23.34<br />
25.96<br />
Power<br />
Nominal Input<br />
Cooling<br />
kW<br />
26.56<br />
29.18<br />
29.78<br />
Heating<br />
kW<br />
19.83<br />
21.48<br />
23.72<br />
Heating<br />
kW<br />
24.72<br />
26.96<br />
27.96<br />
Circuit Breaker (MCCB/ELB)<br />
A<br />
75<br />
100<br />
100<br />
Circuit Breaker (MCCB/ELB)<br />
A<br />
100<br />
100<br />
100<br />
Power Supply<br />
Ø/V/Hz<br />
3/380~415/50<br />
3/380~415/50<br />
3/380~415/50<br />
Power Supply<br />
Ø/V/Hz<br />
3/380~415/50<br />
3/380~415/50<br />
103/380~415/50<br />
Mode * 3)<br />
-<br />
HP/HR<br />
HP/HR<br />
HP/HR<br />
Mode * 3)<br />
-<br />
HP/HR<br />
HP/HR<br />
HP/HR<br />
COP<br />
Cooling<br />
-<br />
3.68<br />
3.60<br />
3.45<br />
COP<br />
Cooling<br />
-<br />
3.58<br />
3.45<br />
3.57<br />
Heating<br />
-<br />
4.45<br />
4.40<br />
4.25<br />
Heating<br />
-<br />
4.33<br />
4.21<br />
4.28<br />
Fan<br />
Type/Control<br />
-<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Fan<br />
Type/Control<br />
-<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Piping<br />
Liquid<br />
Ø,mm<br />
19.05<br />
19.05<br />
19.05<br />
Piping<br />
Liquid<br />
Ø,mm<br />
19.05<br />
19.05<br />
19.05<br />
Connections<br />
Gas<br />
Ø,mm<br />
31.75<br />
31.75<br />
31.75<br />
Connections<br />
Gas<br />
Ø,mm<br />
31.75<br />
38.10<br />
38.10<br />
Discharge Gas (DVM PLUS III HR)<br />
Ø,mm<br />
28.58<br />
28.58<br />
28.58<br />
Discharge Gas (DVM PLUS III HR)<br />
Ø,mm<br />
28.58<br />
31.75<br />
31.75<br />
Oil (Flare)<br />
Ø,mm<br />
6.35<br />
6.35<br />
6.35<br />
Oil (Flare)<br />
Ø,mm<br />
6.35<br />
6.35<br />
6.35<br />
Installation<br />
Max.Length<br />
m<br />
200<br />
200<br />
200<br />
Installation<br />
Max.Length<br />
m<br />
200<br />
200<br />
200<br />
Limitation<br />
Max.Height<br />
m<br />
50 (40)<br />
50 (40)<br />
50 (40)<br />
Limitation<br />
Max.Height<br />
m<br />
50 (40)<br />
50 (40)<br />
50 (40)<br />
Refrigerant<br />
Type<br />
-<br />
R410A<br />
R410A<br />
R410A<br />
Refrigerant<br />
Type<br />
-<br />
R410A<br />
R410A<br />
R410A<br />
Factory Charging<br />
kg<br />
7.5x3<br />
7.5x3<br />
7.5x3<br />
Factory Charging<br />
kg<br />
7.5x2+11x1<br />
7.5x2+11x1<br />
7.5x1+11x2<br />
Sound<br />
Sound Pressure * 4)<br />
dB(A)<br />
63<br />
63<br />
64<br />
Sound<br />
Sound Pressure * 4)<br />
dB(A)<br />
64<br />
64<br />
64<br />
Set Size<br />
Net Weight<br />
DVM PLUS III<br />
kg<br />
240x3<br />
240x3<br />
240x3<br />
Set Size<br />
Net Weight<br />
DVM PLUS III<br />
kg<br />
240x2+320x1<br />
240x2+320x1<br />
240x1+320x2<br />
DVM PLUS III HR<br />
kg<br />
242x3<br />
242x3<br />
242x3<br />
DVM PLUS III HR<br />
kg<br />
242x2+323x1<br />
242x2+323x1<br />
242x1+323x2<br />
Shipping Weight<br />
DVM PLUS III<br />
kg<br />
253x3<br />
253x3<br />
253x3<br />
Shipping Weight<br />
DVM PLUS III<br />
kg<br />
253x2+337x1<br />
253x2+337x1<br />
253x1+337x2<br />
DVM PLUS III HR<br />
kg<br />
255x3<br />
255x3<br />
255x3<br />
DVM PLUS III HR<br />
kg<br />
255x2+340x1<br />
255x2+340x1<br />
255x1+340x2<br />
Net Dimensions (WxHxD)<br />
mm<br />
(880x1,703x765)x3<br />
(880x1,703x765)x3<br />
(880x1,703x765)x3<br />
Net Dimensions (WxHxD)<br />
mm<br />
(880x1,703x765)x2+(1,200x1,703x765)x1<br />
(880x1,703x765)x2+(1,200x1,703x765)x1<br />
(880x1,703x765)x1+(1,200x1,703x765)x2<br />
Shipping Dimensions (WxHxD)<br />
mm<br />
(948x1,868x832)x3<br />
(948x1,868x832)x3<br />
(948x1,868x832)x3<br />
Shipping Dimensions (WxHxD)<br />
mm<br />
(948x1,868x832)x2+(1,268x1,868x832)x1<br />
(948x1,868x832)x2+(1,268x1,868x832)x1<br />
(948x1,868x832)x1+(1,268x1,868x832)x2<br />
Operating<br />
Cooling<br />
ºC<br />
-5~43<br />
-5~43<br />
-5~43<br />
Operating<br />
Cooling<br />
ºC<br />
-5~43<br />
-5~43<br />
-5~43<br />
Temp. Range<br />
Heating<br />
ºC<br />
-20~24<br />
-20~24<br />
-20~24<br />
Temp. Range<br />
Heating<br />
ºC<br />
-20~24<br />
-20~24<br />
-20~24<br />
Notes<br />
*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*3) Mode - HP: Heat Pump, HR: Heat Recovery<br />
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.<br />
- <strong>Specification</strong>s are subject to change without prior notice for product improvement.<br />
Notes<br />
*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*3) Mode - HP: Heat Pump, HR: Heat Recovery<br />
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.<br />
- <strong>Specification</strong>s are subject to change without prior notice for product improvement.