OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR<br />
2009 Samsung DVM Air Conditioners<br />
<br />
42 43<br />
<br />
<strong>Specification</strong> | DVM PLUS III / DVM PLUS III HR<br />
Module Type - Compact<br />
Model<br />
48 HP<br />
50 HP<br />
52 HP<br />
Model<br />
54 HP<br />
56 HP<br />
Basic<br />
RVXVHT080GE / RVXVRT080GE<br />
Basic<br />
RVXVHT080GE / RVXVRT080GE<br />
RVXVHT100GE / RVXVRT100GE<br />
RVXVHT100GE / RVXVRT100GE<br />
1<br />
1<br />
RVXVHT120GE / RVXVRT120GE<br />
3<br />
3<br />
RVXVHT120GE / RVXVRT120GE<br />
1<br />
RVXVHT140GE / RVXVRT140GE<br />
1<br />
RVXVHT140GE / RVXVRT140GE<br />
1<br />
RVXVHT160GE / RVXVRT160GE<br />
3<br />
1<br />
RVXVHT160GE / RVXVRT160GE<br />
2<br />
2<br />
Performance<br />
Horse Power<br />
HP<br />
48<br />
50<br />
52<br />
Performance<br />
Horse Power<br />
HP<br />
54<br />
56<br />
Capacity<br />
Cooling * 1)<br />
kW<br />
134.4<br />
140.0<br />
145.6<br />
Capacity<br />
Cooling * 1)<br />
kW<br />
151.2<br />
156.8<br />
Btu/h<br />
458,700<br />
477,600<br />
496,700<br />
Btu/h<br />
515,900<br />
535,100<br />
Heating * 2)<br />
kW<br />
151.2<br />
157.5<br />
163.8<br />
Heating * 2)<br />
kW<br />
170.1<br />
176.4<br />
Btu/h<br />
516,000<br />
537,500<br />
559,000<br />
Btu/h<br />
580,500<br />
602,000<br />
Power<br />
Nominal Input<br />
Cooling<br />
kW<br />
44.40<br />
42.20<br />
46.00<br />
Power<br />
Nominal Input<br />
Cooling<br />
kW<br />
47.78<br />
48.38<br />
Heating<br />
kW<br />
45.00<br />
38.60<br />
43.20<br />
Heating<br />
kW<br />
46.56<br />
47.56<br />
Circuit Breaker (MCCB/ELB)<br />
A<br />
125<br />
150<br />
150<br />
Circuit Breaker (MCCB/ELB)<br />
A<br />
150<br />
150<br />
Power Supply<br />
Ø/V/Hz<br />
3/380~415/50<br />
3/380~415/50<br />
3/380~415/50<br />
Power Supply<br />
Ø/V/Hz<br />
3/380~415/50<br />
3/380~415/50<br />
Mode * 3)<br />
-<br />
HP/HR<br />
HP/HR<br />
HP/HR<br />
Mode * 3)<br />
-<br />
HP/HR<br />
HP/HR<br />
COP<br />
Cooling<br />
-<br />
3.03<br />
3.32<br />
3.17<br />
COP<br />
Cooling<br />
-<br />
3.16<br />
3.24<br />
Heating<br />
-<br />
3.36<br />
4.08<br />
3.79<br />
Heating<br />
-<br />
3.65<br />
3.71<br />
Fan<br />
Type/Control<br />
-<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Fan<br />
Type/Control<br />
-<br />
Propeller/BLDC<br />
Propeller/BLDC<br />
Piping<br />
Liquid<br />
Ø,mm<br />
19.05<br />
22.23<br />
22.23<br />
Piping<br />
Liquid<br />
Ø,mm<br />
22.23<br />
22.23<br />
Connections<br />
Gas<br />
Ø,mm<br />
38.10<br />
44.50<br />
44.50<br />
Connections<br />
Gas<br />
Ø,mm<br />
44.50<br />
44.50<br />
Discharge Gas (DVM PLUS III HR)<br />
Ø,mm<br />
31.75<br />
38.10<br />
38.10<br />
Discharge Gas (DVM PLUS III HR)<br />
Ø,mm<br />
38.10<br />
38.10<br />
Oil (Flare)<br />
Ø,mm<br />
6.35<br />
6.35<br />
6.35<br />
Oil (Flare)<br />
Ø,mm<br />
6.35<br />
6.35<br />
Installation<br />
Max.Length<br />
m<br />
200<br />
200<br />
200<br />
Installation<br />
Max.Length<br />
m<br />
200<br />
200<br />
Limitation<br />
Max.Height<br />
m<br />
50 (40)<br />
50 (40)<br />
50 (40)<br />
Limitation<br />
Max.Height<br />
m<br />
50 (40)<br />
50 (40)<br />
Refrigerant<br />
Type<br />
-<br />
R410A<br />
R410A<br />
R410A<br />
Refrigerant<br />
Type<br />
-<br />
R410A<br />
R410A<br />
Factory Charging<br />
kg<br />
11x3<br />
7.5x3+11x1<br />
7.5x3+11x1<br />
Factory Charging<br />
kg<br />
7.5x2+11x2<br />
7.5x1+11x3<br />
Sound<br />
Sound Pressure * 4)<br />
dB(A)<br />
65<br />
66<br />
66<br />
Sound<br />
Sound Pressure * 4)<br />
dB(A)<br />
66<br />
66<br />
Set Size<br />
Net Weight<br />
DVM PLUS III<br />
kg<br />
320x3<br />
240x3+320x1<br />
240x3+320x1<br />
Set Size<br />
Net Weight<br />
DVM PLUS III<br />
kg<br />
240x2+320x2<br />
240x1+320x3<br />
DVM PLUS III HR<br />
kg<br />
323x3<br />
242x3+323x1<br />
242x3+323x1<br />
DVM PLUS III HR<br />
kg<br />
242x2+323x2<br />
242x1+323x3<br />
Shipping Weight<br />
DVM PLUS III<br />
kg<br />
337x3<br />
253x3+337x1<br />
253x3+337x1<br />
Shipping Weight<br />
DVM PLUS III<br />
kg<br />
253x2+337x2<br />
253x1+337x3<br />
DVM PLUS III HR<br />
kg<br />
340x3<br />
255x3+340x1<br />
255x3+340x1<br />
DVM PLUS III HR<br />
kg<br />
255x2+340x2<br />
255x1+340x3<br />
Net Dimensions (WxHxD)<br />
mm<br />
(1,200x1,703x765)x3<br />
(880x1,703x765)x3+(1,200x1,703x765)x1<br />
(880x1,703x765)x3+(1,200x1,703x765)x1<br />
Net Dimensions (WxHxD)<br />
mm<br />
(880x1,703x765)x2+(1,200x1,703x765)x2<br />
(880x1,703x765)x1+(1,200x1,703x765)x3<br />
Shipping Dimensions (WxHxD)<br />
mm<br />
(1,268x1,868x832)x3<br />
(948x1,868x832)x3+(1,268x1,868x832)x1<br />
(948x1,868x832)x3+(1,268x1,868x832)x1<br />
Shipping Dimensions (WxHxD)<br />
mm<br />
(948x1,868x832)x2+(1,268x1,868x832)x2<br />
(948x1,868x832)x1+(1,268x1,868x832)x3<br />
Operating<br />
Cooling<br />
ºC<br />
-5~43<br />
-5~43<br />
-5~43<br />
Operating<br />
Cooling<br />
ºC<br />
-5~43<br />
-5~43<br />
Temp. Range<br />
Heating<br />
ºC<br />
-20~24<br />
-20~24<br />
-20~24<br />
Temp. Range<br />
Heating<br />
ºC<br />
-20~24<br />
-20~24<br />
Notes<br />
*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*3) Mode - HP: Heat Pump, HR: Heat Recovery<br />
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.<br />
- <strong>Specification</strong>s are subject to change without prior notice for product improvement.<br />
Notes<br />
*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,<br />
Equivalent refrigerant piping: 7.5m, Level differences: 0m<br />
*3) Mode - HP: Heat Pump, HR: Heat Recovery<br />
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.<br />
- <strong>Specification</strong>s are subject to change without prior notice for product improvement.