Electricity <strong>Meter</strong>s BS<br />

RESIDENTIAL<br />

Landis+Gyr Domestic<br />

ZCE117AC / ZCE127AC<br />

ZCE118AC / ZCE128AC<br />

TECHNICAL DATA<br />

Frequency<br />

Rated frequency fn<br />

selectable: 50 or 60 Hz<br />

Measuring accuracy<br />

to IEC 62053-21 Class 1 and 2<br />

Power consumption<br />

Power consumption in voltage circuit<br />

< 2 W<br />

Power consumption in current circuit<br />

< 0.25 VA<br />

Voltage<br />

ZCE117 / ZCE127 Rated voltage Un 230 V<br />

ZCE118 / ZCE128 Rated voltage Un 120 V<br />

Voltage range<br />

80% - 115 % Un<br />

Operating behaviour<br />

Voltage interruption (Power Down)<br />

Blocking of inputs and outputs immediate<br />

Standby operation<br />

for 0.2 s<br />

Data storage<br />

after 0.2 s<br />

Switch off<br />

after approx. 0.3 s<br />

Restoration of voltage (Power Up)<br />

Function standby<br />

(depending on duration of failure)<br />

Detection of energy direction<br />

and phase voltage<br />

< 5 s<br />

< 5 s<br />

Current<br />

Base current Ib<br />

Starting current<br />

5, 10 or 20 A<br />

0.5 % Ib<br />

Environmental influences<br />

Temperature range<br />

Operation -25 °C − +60 °C<br />

Storage -40 °C − +70 °C<br />

Maximum current Imax<br />

metrological<br />

thermal<br />

short-circuit ≤ 10 ms<br />

100 A<br />

120 A<br />

3000 A<br />

Temperature coefficient<br />

Range<br />

from -20°C − +55°C<br />

Typical mean value<br />

± 0.02 % per K<br />

cosϕ=1 (from 0.1 Ib to Imax) ± 0.05 % per K<br />

cosϕ=0.5 (from 0.2 Ib to Imax) ± 0.075 % per K<br />

Impermeability to IEC 60529 IP 52<br />

H 71 0200 0260 a en - ZCE117AC / ZCE127AC ZCE118AC / ZCE128AC - Technical Data<br />

Landis+Gyr<br />

1 / 4


Electromagnetic Compatibility<br />

Electrostatic discharges to IEC 61000-4-2<br />

Contact discharges<br />

8 kV<br />

Electromagn. high frequency fields to IEC 61000-4-3<br />

80 MHz to 2 GHz at least 10 V/m<br />

Radio interference suppression to IEC/CISPR 22 Cl B<br />

Line transients (burst) to IEC 61000-4 with basic<br />

current I b :<br />

for current and voltage circuits<br />

2 kV<br />

for auxiliary circuits > 40 V<br />

1 kV<br />

with open current circuit<br />

for voltage and current circuits<br />

4 kV<br />

Surge immunity test to IEC 61000-4-5<br />

Impulse voltage<br />

6 kV<br />

Impedance of source<br />

2 Ω<br />

Rise-/ Decay time of impulse voltage 1.2 µs / 50 µs<br />

Rise- / Decay time of current 8 µs / 20 µs<br />

Insulation strength<br />

Insulation strength<br />

4 kV at 50 Hz for 1 min.<br />

Impulse voltage strength to IEC 62053-11<br />

Impulse voltage<br />

8 kV<br />

Impedance of source<br />

500 Ω<br />

Rise- /Decay time of impulse voltage 1.2 µs / 50 µs<br />

Optical Test Output<br />

Type<br />

Infrared LED<br />

physically combined with optical interface<br />

(i.e. infrared-LED is integrated in optical interface)<br />

Pulse length<br />

approx. 2 ms<br />

<strong>Meter</strong> constant R<br />

2000 imp/kWh<br />

Pulse output r53 (optional)<br />

Optional available for the single rate version only<br />

Type<br />

S0 interface<br />

Standard IEC 61393 / DIN 43864<br />

- Values 1000 imp/kWh<br />

Operating conditions<br />

- Supply voltage (nominal value) 24 V DC<br />

- Maximum supply voltage 50 V DC<br />

- Current 10 to 20 mA DC<br />

- Pulse length configurable from 10 … 120 ms<br />

in 10 ms steps<br />

- Default value 80 ms<br />

Communication Interface<br />

Optical interface<br />

Type<br />

serial, bi-directional interface<br />

Standard IEC 62056-21<br />

Application<br />

Data readout according to IEC 62056-21 (all data)<br />

Factory parameterisation<br />

Test output (physically combined with test diode)<br />

Protection class to IEC 60050-131 2<br />

Display<br />

Characteristics<br />

Type<br />

LCD liquid crystal display<br />

Digit size<br />

8.4 mm<br />

Number of digits 6<br />

Inputs and Outputs<br />

Control Inputs optional<br />

Control voltage Ut<br />

230 V<br />

Permissible range<br />

0.8 up to 1.15 x Ut<br />

Current input<br />

< 2 mA ohmic at 230 V<br />

(two rate version cannot include r53 option)<br />

Landis+Gyr<br />

2 / 4<br />

H 71 0200 0260 a en - ZCE117AC / ZCE127AC ZCE118AC / ZCE128AC - Technical Data


Weight and Dimensions<br />

Weight<br />

External dimensions<br />

Width<br />

Height (with short terminal cover)<br />

Height (with long terminal cover)<br />

Depth (without terminal cover)<br />

Depth (with terminal cover)<br />

Suspension<br />

Horizontal two screw suspension only<br />

Width<br />

Terminal cover<br />

Short<br />

Long<br />

approx. 300 g<br />

comply with BS<br />

125 mm<br />

80 mm<br />

125 mm<br />

32 mm<br />

42 mm<br />

105 mm<br />

no free space<br />

45 mm free space<br />

Connections<br />

Mains<br />

Type<br />

screw type terminals<br />

Diameter<br />

9.5 mm<br />

Minimum conductor cross-section 4 mm 2<br />

max. cross-section cable 35 mm 2<br />

max. cross-section strand 25 mm 2<br />

Screw dimensions M6 x 14<br />

head diameter<br />

max. 6.6 mm<br />

slot<br />

0.8 +0.2/+0.06 mm<br />

Tightening torque<br />

max. 3 Nm<br />

Other connections<br />

Type<br />

screw type terminal<br />

Max. cross-section cable / strand 2.5 mm 2<br />

Tightening torque<br />

max. 0.6 Nm<br />

Terminal layout and dimensions<br />

Dimensions (with short terminal cover)<br />

125 30 2<br />

ZCE127<br />

25 20 25<br />

70<br />

18<br />

78<br />

80<br />

42<br />

Dimensions (with long terminal cover)<br />

125 30<br />

2<br />

ZCE127<br />

125<br />

78<br />

42<br />

H 71 0200 0260 a en - ZCE117AC / ZCE127AC ZCE118AC / ZCE128AC - Technical Data<br />

Landis+Gyr<br />

3 / 4


Type designation<br />

ZCE 127 AC d r53<br />

Network type<br />

ZCD Single-phase two-wire network<br />

Connection type<br />

117 Direct connection 230 V, IEC class 1, BS<br />

127 Direct connection 230 V, IEC class 2, BS<br />

118 Direct connection 120 V, IEC class 1, BS<br />

128 Direct connection 120 V, IEC class 2, BS<br />

Measurement variants<br />

AC Simple active energy meter<br />

Tariff functions<br />

e<br />

d<br />

with single-rate tariff<br />

with double-rate tariff<br />

Pulse retransmission<br />

r53 Transistor output, S0 according IEC 61393/DIN 43 864,<br />

pulse length ti variable<br />

Landis+Gyr Ltd.<br />

Feldstrasse 1<br />

CH – 6301 Zug<br />

Switzerland<br />

Phone: +41 41 724 41 41<br />

www.landisgyr.com<br />

Landis+Gyr<br />

4 / 4<br />

H 71 0200 0260 a en - ZCE117AC / ZCE127AC ZCE118AC / ZCE128AC - Technical Data