Modbus RTU protocol features<br />

Baud-rate Can be selected on parameter 70<br />

4800bit/sec<br />

9600bit/sec<br />

19200bit/sec<br />

28800bit/sec<br />

38400bit/sec<br />

57600bit/sec<br />

Format 8, N, 1 (8bit, no parity, 1 stop)<br />

Supported<br />

functions<br />

WORD READING (max 20 word) (0x03, 0x04)<br />

SINGLE WORD WRITING (0x06)<br />

MULTIPLE WORDS WRITING (max 20 word)<br />

(0x10)<br />

The list below includes all the available addresses, where:<br />

RO = Read Only<br />

R/W = Read/Write<br />

WO = Write Only<br />

Modbus<br />

address<br />

Description<br />

Read<br />

Write<br />

Reset<br />

value<br />

0 Device type RO EEPROM<br />

1 Software version RO EEPROM<br />

5 Slave Address R/W EEPROM<br />

6 Boot version RO EEPROM<br />

50 Automatic addressing WO -<br />

51 System code comparison WO -<br />

1000 Process (with tenths of degree for temperature RO ?<br />

sensors; digits for linear sensors)<br />

1001 Setpoint1 R/W EEPROM<br />

1002 Setpoint2 R/W EEPROM<br />

1003 Setpoint3 R/W EEPROM<br />

1004 Setpoint4 R/W EEPROM<br />

1005 Alarm1 R/W EEPROM<br />

1006 Alarm2 R/W EEPROM<br />

1007 Alarm3 R/W EEPROM<br />

1008 Setpoint gradient RO EEPROM<br />

26