Lightning- and Surge Protection<br />
<strong>EnerPro</strong> <strong>502</strong>-<strong>Tr</strong> (/<strong>Pk</strong>)<br />
<strong>EnerPro</strong><br />
2-pole Lightning- and Surge Protective Device<br />
10kA (max. 20kA)<br />
For protection of DC–applications and Photovoltaic Systems<br />
• Lightning- und Surge Protection of DC-mains and photovoltaic solar systems<br />
• Protection circuit molded in water- and corrosion resistant polyurethane<br />
• Monitoring of line interruption and function control by green LED<br />
• Thermo-dynamic potential free remote signal contact <strong>Pk</strong> (option)<br />
• Large size multifunctional terminals<br />
• 2-pole, rigid 2-mod. DIN housing for snap-on 35mm DIN-rail<br />
Product description<br />
LEUTRON SPD type <strong>EnerPro</strong> <strong>502</strong>-<strong>Tr</strong> (/<strong>Pk</strong>), serves as Lightning and Surge Protective Devices (SPD) installed at<br />
the power supply side of DC equipments and systems. One SPD protects 2 lines (+ and -).<br />
These LEUTRON - <strong>EnerPro</strong> SPD are equipped with a safety disconnection device, which will response safely<br />
and cut off the SPD from net, if the built-in MOV would be thermally overloaded by a too high leakage current. In<br />
such case, the green operating indication LED will extinguish and the SPD has to be replaced.<br />
The thermic coupled remote signal contact (option) signalise that the SPD was overloaded and should be<br />
replaced before the SPD is cut-off from net, because of safety reason.<br />
The protective circuit is completely molded in Polyurethane and is built in an easy to install Polycarbonate<br />
housing to snap on a 35mm DIN-rail (EN50022). Large multifunctional terminals for connection of bus-bars and<br />
conductors for easy and safe wiring together with other DIN rail mounted devices.<br />
Application<br />
This robust and rigid protective device serves to protect DC- and photovoltaic systems against damages caused<br />
by lightning surges.<br />
If used in photovoltaic systems (PV) the <strong>EnerPro</strong> <strong>502</strong>-<strong>Tr</strong> (/<strong>Pk</strong>) should be preferred to install in the PV-generator<br />
connection box. Because the inverse rectifier probably is installed several meters far away, it is unprotected.<br />
Therefore SPDs of same types as installed at the generator output has to be installed at the DC-side of the<br />
inverse rectifier too.<br />
Protects People and Valuables
Technical Data:<br />
Application<br />
2-pole lightning SPD with function indication by LED. Mostly used for protection of Photovoltaic systems to be<br />
installed in the generator connection box and at the DC-input of inverse rectifiers. Option: remote signal contact<br />
Type <strong>EnerPro</strong> <strong>502</strong>-<strong>Tr</strong> <strong>EnerPro</strong> <strong>502</strong>-<strong>Tr</strong> /<strong>Pk</strong><br />
Article No. 38 20 55 38 20 57<br />
Nominal DC-voltage U n [V=] 500<br />
Max. continuous DC-operating voltage U max [V=] 550<br />
Max. mains-side overcurrent protection or SPD pre-fuse I [A] 100 A gL/gG<br />
Voltage protection level at 1 kV/µs …L1, L2 – PE U as [kV] < 2.5<br />
Voltage protection level at I N (i sn ) …...L1, L2 - PE U res [kV] < 2.5<br />
Response time t A [ns] < 25<br />
Nominal impuls discharge current…line to PE (8/20 µs) I N (i sn ) [kA] 10x 10kA<br />
Max. impulse discharge current…….line to PE (8/20µs) I max [kA] 20<br />
Operating temperature range T U [°C] - 25... +85<br />
Min. cross sectional area for lightning SPD [mm2] 10<br />
Max. cross sectional area (L1, L2 und PE) [mm2] 50 stranded / 35 flexible<br />
Recommended screw terminal mounting torque [Nm] 4,5<br />
Max. cross sectional area of remote signal contact (/<strong>Pk</strong>) [mm²] no 1,5<br />
Max. electrical load of remote signal contact (/<strong>Pk</strong>) [V/A] no 1 N.C, 250V / 0.5A<br />
Housing material / color<br />
Polycarbonate (halogen free) UL 94-V0 / yellow<br />
Molding material<br />
Polyurethane<br />
Degree of protection against ambient influence IP 20 (IEC 60529)<br />
Snap-on mounting on DIN- rail 35 mm (DIN EN 50 022)<br />
Dimensions in mm<br />
Diagram<br />
Housing size: 2 modules, acc. DIN 43880<br />
<strong>Pk</strong>…….thermic remote signal contact (option<br />
<strong>EnerPro</strong> <strong>502</strong> -<strong>Tr</strong><br />
21.09.2006 .pdf<br />
Copyright © 2006 by LEUTRON <strong>GmbH</strong><br />
Subject to technical modifications and<br />
delivery possibilities<br />
LEUTRON <strong>GmbH</strong><br />
Lightning- and overvoltage protection<br />
Humboldtstraße 30-32<br />
D-70771 Leinfelden-Echterdingen<br />
GERMANY<br />
Telephone +49 711 / 9 47 71-0<br />
Telefax +49 711 / 9 47 71-70<br />
Email: info@leutron.de<br />
www.leutron.de