ARTICLE IN PRESS<br />

306<br />

T. Chen et al. / Fire Safety Journal 39 (2004) 297–307<br />

<strong>searching</strong> time varied with <strong>fire</strong> position, <strong>fire</strong> strength <strong>and</strong> computation depth of our<br />

detection algorithm, which will not be further discussed here.<br />

Calculated distance <strong>and</strong> the actual distance are fairly accordant. The deviation is<br />

mainly due to the low precision of the pivot angle fed back to the computer. The<br />

angle measuring device in the <strong>fire</strong> monitor is quite simple <strong>and</strong> the motor gears also<br />

have mechanical errors. Extinguishing time T is usually smaller than 6 s because the<br />

<strong>fire</strong> strength in our tests is very small while the water flux is relatively <strong>large</strong>.<br />

Generally, <strong>large</strong>r e caused longer extinguishing time. Usually, if the water stream<br />

dose not hit the <strong>fire</strong> spot initially, it will cover the <strong>fire</strong> spot while the <strong>fire</strong> monitor is<br />

swinging.<br />

4. Conclusion<br />

Fire <strong>searching</strong> <strong>and</strong> <strong>suppression</strong> were combined together <strong>and</strong> realized <strong>automatic</strong>ally<br />

in the <strong>automatic</strong> <strong>fire</strong> monitor <strong>system</strong>. Displacement <strong>and</strong> pivot angle of the CCD<br />

camera in <strong>fire</strong> <strong>searching</strong> process are the essential parameters to calculate the space<br />

coordinates of <strong>fire</strong>. Once the direction <strong>and</strong> the distance of the <strong>fire</strong> are obtained, the<br />

horizontal pivot angle <strong>and</strong> the vertical elevation of the <strong>fire</strong> monitor can be calculated<br />

according to water pressure. The <strong>fire</strong> <strong>searching</strong> precision is enough <strong>for</strong> practical use<br />

<strong>and</strong> the <strong>suppression</strong> effect is also satisfactory.<br />

Remote <strong>and</strong> <strong>automatic</strong> control of the <strong>fire</strong> monitor improves its efficiency <strong>and</strong><br />

adaptability. Moreover, it provides more safety in <strong>fire</strong> fighting <strong>and</strong> is very<br />

economical when incorporated with <strong>fire</strong> protection <strong>system</strong> <strong>for</strong> <strong>large</strong> <strong>spaces</strong> use.<br />

Instead of installing multiple layers of sprinklers, the application of the <strong>fire</strong> monitor<br />

will not influence the inside sight of the buildings. It can be very useful to apply this<br />

technology in <strong>large</strong> <strong>spaces</strong> such as <strong>large</strong> museums, palaestras, showplaces <strong>and</strong><br />

storehouses.<br />

References<br />

[1] Chow WK. Per<strong>for</strong>mance of sprinkler in atria. J Fire Sci 1996;14(6):466–88.<br />

[2] Gott JE, Natariani KA. <strong>An</strong>alysis of high bay hangar facilities <strong>for</strong> detector sensitivity <strong>and</strong> placement.<br />

Society of <strong>fire</strong> protection engineers. Honors Lecture Series, May 20, 1996, Proceedings. Engineering<br />

seminars: Fire Protection Design <strong>for</strong> High Challenge of Special Hazard Applications, May 21–22,<br />

1996, Boston, MA, 1996.<br />

[3] Hankins J. ESFR sprinklers–the facts you should know. Fire Prevention <strong>and</strong> Fire Safety Eng J 1995;<br />

2(6).<br />

[4] Kung HC, et al. Early <strong>suppression</strong> fast response (ESFR) sprinkler protection <strong>for</strong> 12 m high<br />

warehouses. Proceedings of the Fifth International Symposium on Fire Safety Science. Melbourne,<br />

1997.<br />

[5] Yao C. Overview of sprinkler technology research. Proceedings of the Fifth International Symposium<br />

on Fire Safety Science. Melbourne, 1997.<br />

[6] Chow WK. Full-scale burning facilities <strong>for</strong> atrium <strong>fire</strong> research. Fire Safety Sci 1993;2(2):61–4<br />

[in Chinese].