27.11.2014 Views

FD and DFD Curtain Fire Dampers with Integral Sleeves - Greenheck

FD and DFD Curtain Fire Dampers with Integral Sleeves - Greenheck

FD and DFD Curtain Fire Dampers with Integral Sleeves - Greenheck

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Document Number 453946<br />

<strong>FD</strong> & D<strong>FD</strong> 150X Models<br />

®<br />

1 1 ⁄2 Hour<br />

<strong>Curtain</strong> <strong>Fire</strong> <strong>Dampers</strong><br />

Vertical or Horizontal Mount<br />

Installation, Operation <strong>and</strong> Maintenance Instructions<br />

<strong>FD</strong> <strong>and</strong> D<strong>FD</strong> 150X Series models are intended for<br />

installation in accordance <strong>with</strong> fire damper<br />

requirements<br />

established by:<br />

National <strong>Fire</strong> Protection Association<br />

NFPA St<strong>and</strong>ard 80, 90A, & 101<br />

IBC International Building Codes<br />

CSFM California State <strong>Fire</strong> Marshal<br />

<strong>Fire</strong> Damper Listing (#3225-0981:102)<br />

New York City (BSA/MEA listing #260-91-M)<br />

L<br />

S TATE<br />

S<br />

I S<br />

T<br />

STATE OF CALIFORNIA<br />

FIR E MAR S HALL<br />

E R V<br />

I N G<br />

E<br />

I C<br />

Installation Supplements<br />

Refer to the appropriate <strong>Greenheck</strong> installation<br />

supplements for special requirements:<br />

• Support Mullions<br />

• Shaftwall Supplement<br />

• Drywall Supplement<br />

• Grille Installation Supplement<br />

• Drive Slip Supplement<br />

• Sealant Supplement<br />

• Sleeve Extension Supplement<br />

• Single side Retaining Angles Supplement<br />

Note: Refer to <strong>Greenheck</strong> IOM, Part #461335, for<br />

CFSD models to be installed in corridor ceiling<br />

applications.<br />

Refer to <strong>Greenheck</strong> IOM, Part # 452763 for<br />

st<strong>and</strong>ard D<strong>FD</strong> <strong>and</strong> <strong>FD</strong> models.<br />

“UL CLASSIFIED (see complete marking on product)”<br />

“UL CLASSIFIED to Canadian safety st<strong>and</strong>ards (see<br />

complete marking on product)”<br />

UL St<strong>and</strong>ard 555 (Listing #R13317)<br />

Safety WARNING:<br />

Improper installation, adjustment, alteration, service<br />

or maintenance can cause property damage, injury<br />

or death. Read the installation, operating, <strong>and</strong><br />

maintenance instructions thoroughly before installing<br />

or servicing this equipment.<br />

Receiving <strong>and</strong> H<strong>and</strong>ling<br />

Upon receiving dampers, check for both obvious <strong>and</strong><br />

hidden damage. If damage is found, record all necessary<br />

information on the bill of lading <strong>and</strong> file a claim <strong>with</strong><br />

the final carrier. Check to be sure that all parts of the<br />

shipment, including accessories, are accounted for.<br />

<strong>Dampers</strong> must be kept dry <strong>and</strong> clean. Indoor storage<br />

<strong>and</strong> protection from dirt, dust <strong>and</strong> the weather is highly<br />

recommended. Do not store at temperatures in excess of<br />

100°F.<br />

Warranty<br />

<strong>Greenheck</strong> warrants this equipment to be free from<br />

defects in material <strong>and</strong> workmanship for a period of one<br />

year from the shipment date. Any units or parts which<br />

prove to be defective during the warranty period will be<br />

repaired or replaced at our option. <strong>Greenheck</strong> shall not<br />

be liable for damages resulting from misapplication or<br />

misuse of its products. <strong>Greenheck</strong> will not be responsible<br />

for any installation or removal costs. <strong>Greenheck</strong> will not be<br />

responsible for any service work or backcharges <strong>with</strong>out<br />

prior written authorization.<br />

This manual is the property of the owner, <strong>and</strong> is required for future maintenance. Please leave it <strong>with</strong> the owner when the<br />

job is complete.<br />

Due to continuing research, <strong>Greenheck</strong> reserves the right to change specifications <strong>with</strong>out notice.


Table of Contents<br />

Pre-Installation Guidelines.......................................................................................................................................... 2<br />

Installation................................................................................................................................................................3-5<br />

Breakaway Connections............................................................................................................................................. 6<br />

Installation for Steel Stud Connection Option........................................................................................................... 7<br />

Damper Maintenance.................................................................................................................................................. 8<br />

Damper Troubleshooting............................................................................................................................................. 8<br />

Pre-Installation Guidelines<br />

The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to<br />

prevent distortion <strong>and</strong> disruption of damper operation. This is accomplished by allowing the fire damper in rated<br />

separation openings to exp<strong>and</strong> <strong>and</strong> for the connecting duct to separate in the event of the collapse of the hanging<br />

system. The following items will aid in completing the damper installation in a timely <strong>and</strong> effective manner.<br />

1. Check the schedules for proper damper locations <strong>with</strong>in the building. Visually inspect the damper for damage <strong>and</strong><br />

verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace<br />

link. Never install a fire damper <strong>with</strong>out the proper UL approved fusible link in place. (Fusible link is st<strong>and</strong>ard<br />

control option. An electric link may have been provided.)<br />

2. Lift or h<strong>and</strong>le damper using sleeve or frame.<br />

3. Install damper accordingly to comply <strong>with</strong> manufacturer’s appropriate UL procedure file number.<br />

4. Damper must be installed into duct or opening square <strong>and</strong> free of twist or other misalignment. Damper must not be<br />

squeezed or stretched into duct or opening.<br />

5. Damper must be kept clean <strong>and</strong> protected from dirt, dust <strong>and</strong> other foreign materials prior to <strong>and</strong> after installation.<br />

Examples of such foreign materials include, but are not limited to:<br />

a. Mortar dust<br />

b. Drywall dust<br />

c. <strong>Fire</strong>safing materials<br />

d. Wall texture<br />

e. Paint overspray<br />

6. Damper should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray<br />

painting when performed <strong>with</strong>in 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper<br />

to bind <strong>and</strong> not operate properly.<br />

7. Caulking is not necessary, nor is it allowed, between the damper sleeve <strong>and</strong> the wall or floor opening (annular<br />

space). However, caulking may be applied to the retaining angles.<br />

8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection <strong>and</strong><br />

servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable<br />

section of duct. (Refer to NFPA 90A).<br />

9. The Code Authority Having Jurisdiction (AHJ) must evaluate <strong>and</strong> provide approval of final installation where<br />

variations to these instructions are necessary.<br />

2


Installation - Failure to follow these instructions will void all warranties.<br />

These instructions apply to 11/2 hour rated fire dampers<br />

mounted in masonry, block or stud walls <strong>and</strong> concrete<br />

floors. Specific requirements in these instructions are<br />

m<strong>and</strong>atory. These instructions meet the requirements of<br />

UL 555. Installation shall comply <strong>with</strong> the requirements<br />

of NFPA 90A St<strong>and</strong>ard for the Installation of Air<br />

Conditioning <strong>and</strong> Ventilating Systems. U.L. listing<br />

R13317, California State <strong>Fire</strong> Marshal listings 3225-<br />

981:102, <strong>and</strong> New York City BSA/MEA listing 260-91-M<br />

as they apply to these dampers.<br />

Note: <strong>Fire</strong> dampers are manufactured <strong>and</strong> labelled for<br />

either vertical or horizontal installation. The dampers<br />

must be installed in accordance <strong>with</strong> the labelling.<br />

Retaining<br />

Angle<br />

2 in. Max.<br />

Min. 1 in.<br />

Overlap*<br />

Wall or<br />

Floor<br />

Retaining<br />

Angle<br />

Sleeve<br />

Duct<br />

6 in. Max.<br />

Damper<br />

1. NO ADDITIONAL SLEEVES ARE REQUIRED<br />

The fire damper extended frame is an approved<br />

sleeve <strong>and</strong> can be properly installed <strong>with</strong>out the need<br />

for a supplemental field installed sleeve. Damper<br />

frame shall extend a maximum of 6 in. (152mm)<br />

beyond the wall or floor opening on each side.<br />

2. CLEARANCES REQUIRED BETWEEN FIRE<br />

DAMPER SLEEVES AND WALL/FLOOR<br />

OPENINGS<br />

<strong>Fire</strong> damper assemblies exp<strong>and</strong> during periods of<br />

intense heat. Therefore, it is essential that openings<br />

in walls or floors be larger than the fire damper<br />

assembly to allow for this expansion. Minimum<br />

clearances required between the outside of fire<br />

damper sleeve assemblies <strong>and</strong> wall/floor openings<br />

are:<br />

• Galvanized steel fire dampers <strong>and</strong> sleeves: 1/8<br />

in. (3mm) per linear foot of damper width <strong>and</strong><br />

height <strong>with</strong> a minimum clearance of 1/4 in. (6mm)<br />

.Recommended clearances, for width <strong>and</strong>/or height<br />

dimensions of:<br />

1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance<br />

2) More than 48 in. (1219mm) <strong>and</strong> 96 in. (2438mm)<br />

or less: 1 in. (25mm) clearance<br />

3) More than 96 in. (2438mm): 11/2 in. (38mm)<br />

clearance<br />

These are total clearances (ignoring fastener heads)<br />

<strong>and</strong> do not need to be equally spaced around<br />

the damper. Refer to Section 3 <strong>and</strong> Figure 1 for<br />

additional installation considerations.<br />

Example:<br />

A 12 in. x 12 in. (305mm x 305mm) damper would<br />

require a minimum clearance of 1/4 in. (6mm).<br />

A 48 in. x 12 in. (1219mm x 305mm) damper<br />

would require a minimum clearance of 1/2 in.<br />

(13mm) on width <strong>and</strong> 1/4 in. (6mm) on height.<br />

6 in. Max.<br />

2 in. Max.<br />

*only applicable for damper sizes above 36 in. x 36 in.<br />

Figure 1: Retaining angle installation.<br />

3. SECURING THE FIRE DAMPER TO WALL AND<br />

FLOOR OPENINGS<br />

<strong>Fire</strong> damper assemblies must be installed in wall <strong>and</strong><br />

floor openings using retaining angles on each side of<br />

the wall or floor as described below:<br />

• Retaining angles for 11/2 hour rated dampers <strong>with</strong><br />

a width <strong>and</strong> height 48 in. (1219mm) or less must be<br />

a minimum of 20 ga. (1mm). Retaining angles for<br />

all 3 hour rated dampers <strong>and</strong> all dampers <strong>with</strong> a<br />

width or height greater than 48 in. (1219mm) must<br />

be a minimum of 16 gauge (1.5mm). The leg of the<br />

retaining angle on the damper sleeve shall be a<br />

minimum of 11/4 in. (32mm). The leg of the retaining<br />

angle on the wall/floor shall be long enough to cover<br />

the annular space <strong>and</strong> overlap the wall/floor by a<br />

minimum of 1 in. (25mm).<br />

• Retaining angles must be attached to the damper<br />

using one or more of the following methods of<br />

attachment:<br />

• tack or spot welds<br />

• #10 sheetmetal screws<br />

• 1/4 in. (6mm) bolts <strong>and</strong> nuts<br />

• 3/16 in. (4.7mm) steel pop rivets<br />

Attachments must be spaced a maximum of 6 in.<br />

(152mm) on center <strong>and</strong> a maximum of 2 in. (51mm)<br />

from corners. The angles must be attached to all 4<br />

sides of the sleeve <strong>with</strong> butt joints at each corner.<br />

A minimum of two attachments are required on<br />

each side, top <strong>and</strong> bottom. The angles need not be<br />

attached to each other at the corners.<br />

• Retaining angles should not be fastened to the wall/<br />

floor material. The angles should only s<strong>and</strong>wich the<br />

wall/floor <strong>and</strong> allow for damper expansion during<br />

periods of intense heat.<br />

3


4. CONNECTING DUCTS TO THE FIRE DAMPER<br />

All duct connections to <strong>FD</strong> & D<strong>FD</strong> 150X series extended frame dampers must be “breakaway” type connections. All<br />

connections shown 1/4 on in. minimum page 5 & 6 are considered breakaway. Factory furnished duct collars on types R & CR fire<br />

total clearance<br />

dampers are also considered breakaway(see Figure 2 & 3).<br />

1/4 in. minimum<br />

total clearance<br />

1/4 in. minimum<br />

total clearance<br />

Retaining Angles<br />

(See Section 4)<br />

Wall or Floor<br />

See Section 2<br />

Maximum<br />

6 in.<br />

Maximum<br />

6 in.<br />

Maximum<br />

6 in.<br />

Maximum Wall or Floor<br />

6 in.<br />

Wall or Floor<br />

Maximum<br />

6 in.<br />

Maximum<br />

6 in.<br />

“K” side<br />

Wall or Floor<br />

Sleeve<br />

(see sections 2 & 3)<br />

See Section 2<br />

Damper<br />

Duct<br />

Duct<br />

Duct<br />

Retaining Angles<br />

Retaining Angles<br />

(See Retaining Section Angles 3)<br />

(See Section 3)<br />

(See Section 3)<br />

Damper<br />

Damper Damper<br />

Type A<br />

Type A<br />

Wall Wall or Floor or Floor<br />

Wall or Floor<br />

Type A<br />

Retaining Angles<br />

(See Section 4)<br />

See Section 2<br />

Damper<br />

Damper<br />

Damper<br />

“K” side<br />

Wall or<br />

Floor<br />

See Section 2<br />

Damper<br />

Sleeve<br />

(see sections 2 & 3)<br />

Duct<br />

Duct<br />

Duct<br />

Duct<br />

Type B<br />

Wall or Floor<br />

On types R & CR factory<br />

furnished duct collar<br />

qualifies as breakaway<br />

connection.<br />

On types R & CR factory<br />

On types furnished R & duct CR factory collar<br />

furnished qualifies duct as breakaway collar<br />

qualifies connection. as breakaway<br />

connection.<br />

Type B<br />

Type B<br />

Wall or Floor<br />

Wall or Floor<br />

Type B<br />

Duct<br />

Duct<br />

Damper<br />

“K” side<br />

Wall or<br />

floor<br />

Type C, CO, CR, & R<br />

Sleeve<br />

Duct<br />

Damper<br />

Duct<br />

Type C, CO, CR, & R<br />

Damper<br />

On types R & CR factory<br />

furnished duct collar qualifies<br />

as breakaway connection, see<br />

Section 5<br />

Type C, CO, CR, & R<br />

Figure 2: Vertical Mount Type A, Type B, <strong>and</strong> Type C,<br />

CO, CR, R damper installation diagrams.<br />

Type C, CO, CR, & R<br />

Figure 3: Horizontal Mount Type A, Type B, <strong>and</strong> Type C,<br />

CO, CR, R damper installation diagrams.<br />

When dampers installed horizontally, the ramp must be<br />

positioned up as shown in above drawings.<br />

4<br />

Table 1<br />

Damper Model<br />

Maximum Sizes for Single<br />

Section <strong>Dampers</strong>*<br />

in. (mm)<br />

<strong>FD</strong>-150X (H or V) 48 x 48 (1219 x 1219)<br />

D<strong>FD</strong>-150X (V) 36 x 36 (914 x 914)<br />

D<strong>FD</strong>-150X (H) 30 x 30 (762 x 762)<br />

Note: V = Vertical mount & H = Horizontal<br />

* Sizes are based on damper <strong>with</strong> no transitions.


Recommended Preparation of Openings in Wood <strong>and</strong> Metal Stud Walls<br />

• Frame wall openings as shown in Figure 4 <strong>and</strong> 4A.<br />

• Gypsum wall board must be fastened 12 in. on center to all stud <strong>and</strong> runner flanges surrounding opening (see<br />

Figure 4 <strong>and</strong> 4A).<br />

• Prepare opening between studs <strong>and</strong> sleeve assembly as shown below (see Figure 5).<br />

• All construction <strong>and</strong> fasteners must meet then requirements of the appropriate wall design.<br />

(See UL <strong>Fire</strong> Resistance Directory)<br />

24 in. o.c.<br />

Maximum<br />

(metal studs)<br />

24 in. o.c.<br />

Maximum<br />

(metal studs)<br />

Ceiling Runner<br />

12 in.<br />

24 in. o.c.<br />

Maximum<br />

2 Panhead<br />

Screws<br />

2 in. (51mm)<br />

2 in. (51mm)<br />

16 in. o.c.<br />

Maximum<br />

(wood studs)<br />

16 in. o.c.<br />

Maximum<br />

(wood studs)<br />

Floor Runner<br />

Figure 4: Preparation detail for opening in stud wall.<br />

Second set of studs are not required on openings<br />

36 in. x 36 in. (914mm x 914mm) or smaller.<br />

Metal Stud Construction<br />

Gypsum Wallboard<br />

Stud or Runner<br />

Retaining<br />

Angle<br />

1 in. Min.<br />

Damper<br />

Sleeve<br />

In metal stud construction,<br />

exposed steel surfaces need<br />

not be covered <strong>with</strong> gypsum<br />

wallboard.<br />

Figure 4A<br />

Metal Stud Construction<br />

Metal stud only<br />

Wooden Stud Construction<br />

Gypsum Wallboard<br />

Gypsum Wa llboard<br />

Stud or Runner<br />

Stud or Runner<br />

Retaining<br />

Angle<br />

Retaining<br />

Angl e<br />

1 in. Min.<br />

1 in. Min.<br />

Damper<br />

Sleeve<br />

In metal stud construction,<br />

exposed steel surfaces need<br />

not be covered <strong>with</strong> gypsum<br />

wallboard.<br />

Wooden Stud Construction<br />

Damper<br />

Sleeve<br />

In wood stud construction,<br />

gypsum wallboard must cover<br />

all wood stud surfaces.<br />

Figure 5: Detail of retaining angles <strong>and</strong> gypsum board application for metal <strong>and</strong> wooden stud construction.<br />

5


Duct-Sleeve Connections<br />

Traditional Breakaway Style Transverse Joints<br />

Transverse joints illustrated in Figure 6 have always<br />

been approved as breakaway connections. SMACNA<br />

testing has also approved the following variations as<br />

breakaway connections.<br />

• The breakaway connections shown to the right can<br />

be applied <strong>with</strong> maximum of (2) #10 sheet metal<br />

screws on each side <strong>and</strong> on the bottom located in<br />

the center of the slip pocket <strong>and</strong> penetrating both<br />

sides of the slip pocket.<br />

• Transverse joints illustrated can<br />

be applied as top <strong>and</strong> bottom<br />

joints <strong>with</strong> Drive Slip - side<br />

Drive Slip Joint<br />

joints in duct heights up to 20<br />

in. (508mm).<br />

Round <strong>and</strong> Oval Duct Breakaway Connections<br />

Round or flat oval ducts connected to factory supplied<br />

Type R, CR, or CO damper collars may use #10 sheet<br />

metal screws as follows:<br />

• Ducts 22 in. (559mm) wide (or dia.) <strong>and</strong> smaller may<br />

use 3 screws.<br />

• Ducts larger than 22 in. (559mm) wide (or dia.) may<br />

use 5 screws.<br />

Plain “S” Slip Hemmed “S” Slip Double “S” Slip<br />

Inside Slip Joint St<strong>and</strong>ing “S” St<strong>and</strong>ing “S” (Alt.)<br />

St<strong>and</strong>ing “S” (Alt.) St<strong>and</strong>ing “S” St<strong>and</strong>ing “S”<br />

(Bar Reinforced) (Angle Reinforced)<br />

Figure 6: Traditional breakaway style transverse joints.<br />

NOTE: All breakaway connections described may have<br />

duct sealant, PA2084T duct sealant adhesive manufactured<br />

by Precision, DP1010 water base duct sealant by Design<br />

Polymetrics, Grey Pookie, Ductmate PROseal ® , or<br />

CL Ward S Seal applied in accordance <strong>with</strong> SMACNA<br />

recommendations.<br />

Proprietary Flange System Breakaway Connections<br />

(Ductmate, Ward, Nexus)<br />

Flanged connection systems manufactured by<br />

Ductmate, Ward, <strong>and</strong> Nexus are approved as breakaway<br />

connections when installed as illustrated in Figure 7.<br />

6 in. long 1/16 in. max.<br />

thickness plastic cleats;<br />

12 in. c-c (min. 1 per side)<br />

Flanged system angles<br />

<strong>Fire</strong> Damper Sleeve<br />

(TDC by Lockformer, TDF by Engle)<br />

TDC <strong>and</strong> TDF systems are approved as breakaway<br />

connections when installed as described in the SMACNA<br />

Duct Construction St<strong>and</strong>ards. St<strong>and</strong>ard 6 in. metal clips<br />

may be used <strong>with</strong> spacing (see Figure 8). Three-eighth<br />

in. metal bolts <strong>and</strong> nuts may be used to fasten together<br />

corner pieces (see Figure 9).<br />

(Attach per<br />

manufacturer’s<br />

instructions)<br />

Duct<br />

Figure 7:<br />

Neoprene gasket<br />

between all angles<br />

Detail of manufactured flanged system<br />

breakaway connections.<br />

Do not bolt corners<br />

60 in. Duct<br />

4 Req’d.<br />

Clip Spacing<br />

6 in.<br />

7 in.<br />

Std. Clip<br />

Length<br />

9 in.<br />

6 in. 6 in.<br />

7 in.<br />

Duct End<br />

Flange<br />

Corner Piece<br />

Sleeve<br />

Typical TDC/TDF joint<br />

Duct<br />

48 in. Duct<br />

3 Req’d.<br />

36 in. Duct<br />

3 Req’d.<br />

24 in. Duct<br />

2 Req’d.<br />

18 in. Duct &<br />

Smaller<br />

1 Req’d.<br />

5 in. 5 in.<br />

5 in.<br />

CL<br />

Duct<br />

5 in.<br />

3/8 in. bolt<br />

(optional)<br />

Figure 8:<br />

6<br />

Detail of proprietary flanged system breakaway<br />

connections.<br />

Figure 9: Detail of bolted corner.


Installation for Steel Stud Connection (SSC) Option<br />

These instructions apply to 11/2 hour rated fire dampers mounted in steel stud walls. Specific requirements in these<br />

instructions are m<strong>and</strong>atory. These instructions meet the requirements of UL555. Installation shall comply <strong>with</strong> the<br />

requirements of NFPA 90A St<strong>and</strong>ard for the Installation of Air Conditioning <strong>and</strong> Ventilating Systems. U.L. listings<br />

R13317 <strong>and</strong> R13743, California State <strong>Fire</strong> Marshal listings 3225-981:102 <strong>and</strong> 3225-1241:101, <strong>and</strong> New York City BSA/<br />

MEA listing 260-91-M as they apply to these dampers.<br />

1. NO ADDITIONAL SLEEVES OR ANGLES ARE<br />

REQUIRED<br />

The fire damper extended frame is an approved<br />

sleeve <strong>and</strong> the Steel Stud Connection (SSC) Option<br />

allows fastening of the fire damper sleeve directly<br />

to the wall's steel stud framing. Damper frame shall<br />

extend a maximum of 6 in. (152mm) beyond the wall<br />

opening on either side. Maximum size fire damper<br />

that may be installed using this SSC option is 36 in. W<br />

x 36 in. H (914mm x 914mm).<br />

2. INSTALLATION<br />

<strong>Fire</strong> damper <strong>with</strong> SSC option must be in place before<br />

the wall is constructed or it can be installed as the<br />

wall is being constructed. Wall opening is framed<br />

around the fire damper before sheet rock or other<br />

wall board material is applied to the steel studs. This<br />

installation provides appropriate protection for duct<br />

penetrations in fire resistant wall construction using<br />

steel studs <strong>with</strong> a fire resistance rating less than 3<br />

hours. The following wall design 3 numbers (as detailed<br />

in the UL <strong>Fire</strong> Resistance Directory) are appropriate<br />

for fire damper installations using this SSC option:<br />

1 Hour Design: U405, U406, U422, U434, U448, U451,<br />

U456, U457, U465, U468, U469, U485, U494<br />

11/2 Hour Design: U449, U452, U470, U471<br />

2<br />

2<br />

2 Hour Design: U403, U411, U412, U421, U425, U428,<br />

U429, U443, U453, U474, U475, U477, U484, U491,<br />

U495<br />

3. FRAMING OF WALL OPENING<br />

Form a wall opening 1/8 in. (3mm) to 1/4 in. (6mm)<br />

larger than the OD of the fire damper's extended<br />

frame (sleeve) using the same metal studs <strong>and</strong><br />

techniques required by the wall design per the UL<br />

<strong>Fire</strong> Resistance Directory. Open side of the steel stud<br />

channels shall face the fire damper <strong>and</strong> encompass<br />

the damper's retaining bar.<br />

4. APPLY WALLBOARD AFTER DAMPER<br />

INSTALLATION<br />

After damper is installed, wallboard shall be applied<br />

to steel stud framework in the manner required by<br />

the wall design per the UL <strong>Fire</strong> Resistance Directory<br />

listing. Around the damper perimeter use a minimum<br />

of 2 connections per side, spaced 12 in. (305mm)<br />

maximum <strong>and</strong> located a maximum of 2 in. (51mm)<br />

from each corner. No additional retaining angles are<br />

required to complete the installation.<br />

5. CONNECTING DUCTS TO THE FIRE DAMPER<br />

3<br />

All duct connections to <strong>FD</strong> & D<strong>FD</strong> 150X series<br />

extended frame dampers must be “breakaway” type<br />

connections. All connections shown on page 5 & 6<br />

are considered breakaway. Factory furnished duct<br />

collars on types R, CR, & CO fire dampers are also<br />

considered breakaway.<br />

Item<br />

3 Description<br />

3<br />

1 <strong>FD</strong>150X fire damper <strong>with</strong> SSC option<br />

2 Steel stud wall (see UL <strong>Fire</strong> Resistance Directory for specific<br />

details)<br />

3 Steel stud frame around opening in wall<br />

4 Duct connection (see section 6)<br />

5 Wallboard (see UL <strong>Fire</strong> Resistance Directory for specific<br />

details)<br />

6 Fasteners (see UL <strong>Fire</strong> Resistance Directory <strong>and</strong> Section 5)<br />

2<br />

3<br />

3<br />

3<br />

6<br />

3<br />

6<br />

3<br />

5<br />

3<br />

5<br />

1<br />

1<br />

Retaining<br />

Bar<br />

1<br />

Retaining<br />

Bar<br />

1<br />

4<br />

4<br />

Top Cross-section View<br />

4 2<br />

Top Cross-section ViewSide Cross-Section View<br />

of Damper in Wall<br />

3<br />

5<br />

4 2<br />

Side Cross-Section View<br />

of Damper in Wall<br />

3<br />

6<br />

7<br />

1<br />

Retaining<br />

1<br />

4


Damper Maintenance<br />

<strong>Dampers</strong> shall be maintained, cycled, <strong>and</strong> tested in intervals as stated in the latest editions of NFPA 90A, 92A, <strong>and</strong> UL<br />

864 unless local codes require more frequent inspections.<br />

<strong>Dampers</strong> do not typically require maintenance as long as they are kept dry <strong>and</strong> clean. If cleaning is necessary, use<br />

mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract<br />

contaminant’s such as dust.<br />

Damper Trouble Shooting<br />

The following is a cause <strong>and</strong> correction list for common concerns <strong>with</strong> the dampers.<br />

Symptom Possible Cause Corrective Action<br />

Damper does not fully open <strong>and</strong>/or<br />

fully close<br />

Frame is 'racked' causing blades to<br />

bind on jamb<br />

Screws in damper linkage<br />

Contaminant's on damper<br />

Link separated Heat Replace link<br />

Adjust frame such that it is square<br />

<strong>and</strong> plumb<br />

Locate screws <strong>and</strong> remove<br />

Clean <strong>with</strong> a non-oil based solvent<br />

(see Damper Maintenance)<br />

Our Commitment<br />

As a result of our commitment to continuous improvement, <strong>Greenheck</strong> reserves the right to change specifications<br />

<strong>with</strong>out notice.<br />

Specific <strong>Greenheck</strong> product warranties are located on greenheck.com <strong>with</strong>in the product area tabs <strong>and</strong> in<br />

the Library under Warranties.<br />

®<br />

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com<br />

453946• D<strong>FD</strong> & <strong>FD</strong> 150X Series Rev. 15, August 2013 Copyright 2013 © <strong>Greenheck</strong> Fan Corporation<br />

8

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!