Scalable PLC <strong>AC<strong>500</strong></strong><br />

Overview of digital S<strong>500</strong> I/O modules<br />

Digital I/O modules, "Fast Counter" operating modes. Not applicable for DC541 or eCo-I/O modules (see technical<br />

documentation for details)<br />

Operating mode, configured in the user program of the <strong>AC<strong>500</strong></strong><br />

Occupied<br />

inputs<br />

DI or DC<br />

Occupied<br />

outputs<br />

DO or DC<br />

Maximum<br />

counting<br />

frequency<br />

kHz<br />

0 No counter 0 0 – –<br />

1 One count-up counter with "end value reached"<br />

indication<br />

2 One count-up counter with "enable" input and<br />

"end value reached" indication<br />

Notes<br />

1<br />

2<br />

1<br />

1<br />

50<br />

50<br />

Note for input module DI524:<br />

It is not possible to set an output directly.<br />

As an alternative, the status byte should be evaluated and<br />

applied to another output in the system.<br />

3 Two up/down counters 2 0 50 "End value" interrogation via status byte<br />

4 Two up/down counters with 1 counting input inverted 2 0 50<br />

5 One up/down counter with "dynamic set" input 2 0 50 Acts to the rising signal edge (0->1)<br />

"End value" interrogation via status byte<br />

6 One up/down counter with "dynamic set" input 2 0 50 Acts to the falling signal edge (1->0)<br />

"End value" interrogation via status byte<br />

7 One up/down counter with directional discriminator<br />

For synchro transmitters using two counting pulses with<br />

an offset of 90° (track A and B)<br />

8 – 0 0 – –<br />

9 One up/down counter with directional discriminator and<br />

double evaluation<br />

For synchro transmitters using two counting pulses with<br />

an offset of 90° towards each other (track A and B)<br />

10 One up/down counter with directional discriminator and<br />

fourfold evaluation<br />

For synchro transmitters using two counting pulses with<br />

an offset of 90° towards each other (track A and B)<br />

2 0 50 For synchro transmitters with 24 V signals. In case of 5 V<br />

synchro transmitters, the signal has to be increased to 24 V.<br />

The zero track of the synchro transmitter is not processed.<br />

Interrogation of the "end value" indication via the status byte.<br />

Single evaluation.<br />

2 0 30 See operating mode 7<br />

Difference: double evaluation, i.e. evaluation of the rising<br />

edge and the falling edge of track A -> higher accuracy due<br />

to the double number of counting pulses<br />

2 0 15 See operating mode 7<br />

Difference: fourfold evaluation, i.e. evaluation of the rising<br />

edge and the falling edge of track A and track B -> higher<br />

accuracy due to the fourfold number of counting pulses.<br />

ABB Automation products | 25